1 / 44

< Water Source Solution >

< Water Source Solution >. Updated by: Yap Boon Thiam Technical Engineer Email: yapbt@oyl.com.my Date: 20/6/2012. Contents. Introduction What is WSS? Advantages Product Line Up Installation Piping Sizing Troubleshooting. What is WSS?. Water Outlet. HP Switch. LP Switch.

darryl
Download Presentation

< Water Source Solution >

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. < Water Source Solution > Updated by: Yap Boon Thiam Technical Engineer Email: yapbt@oyl.com.my Date: 20/6/2012

  2. Contents • Introduction • What is WSS? • Advantages • Product Line Up • Installation • Piping Sizing • Troubleshooting

  3. What is WSS? Water Outlet HP Switch LP Switch Finned Tube Heat Exchanger Compressor Tube In Tube Heat Exchanger Water Inlet Expansion Device

  4. What is WSS?

  5. Advantages • 1. Space Saving • The system utilizes space-saving concepts that • are interconnected by way of water loop-rather • than ductwork. • Improved energy efficiency for lower operating costs. • Lower maintenance costs. • Quiet, comfortable performance.

  6. Advantages • 2. Zoned Comfort & Control • Equipped with individual room sensor and temperature controller. • Can be monitored and controlled centrally by using HydroIntel.

  7. Advantages • 3. Lower Maintenance Cost • Designed with easier accessibility, especially compressor, blower and control section. • Removable top & side panel greatly reduce the time for maintenance work.

  8. Advantages • 4. Coupling Versatility • Left or right return piping and various ducting • discharge configuration (horizontal unit) has • contributed in towards optimizing job layouts • with minimum ductwork and piping. • Easier, lower initial installation & expansion cost.

  9. Advantages • 5. Installation Flexibility • The split configuration allows to: • Install the units at the most convenient position. • Fit the unit with reduction of space utilization due to size compactness.

  10. Advantages • 5. Protection • Hi-Low Pressure Switch

  11. Product Line Up Cooling Only Heatpump

  12. < Installation>

  13. Installation • 1. Installation Clearance • Install the unit at the shortest path to the coupling fan coil unit. • There should be sufficient space for piping connection, service & maintenance.

  14. Installation 2. Hanging Method • This unit will be mounted on the ceiling by the support of four threaded rods. • Ensure that the supports are strong enough and properly anchored to withstand the weight of the unit. • Use isolator rubber (natural rubber) with hardness of 35º for better noise and vibration control. • Do not locate the drainage system at any point above the drain connection.

  15. Installation • 3. Refrigerant Piping • Do not use copper tube less than 0.8mm • Long piping cause the capacity and compressor reliability dropped.

  16. Installation • 4. Additional Charge • Pre charged for standard piping up to 7.6m • For additional piping, refer table below.

  17. Installation • 5. Water Piping • Install a 40-60 mesh strainer to ensure water quality is good. • Air vents must be installed at the highest position while a drainage system at the lowest position of the water circuit.

  18. Installation 6. Electrical Wiring

  19. < Piping Sizing >

  20. Loop Water Flow • 1.Determine System Flow Rate • DON’T sum up directly the total nominal water flow of each WSS unit. • Total system design flow rate is determined by the performance of the water cooler, where most of them are evaporative type and is very much dependent on the entering air wet bulb temperature. • Lower flow rate are preferred in area with lower wet bulb temperatures. In more humid areas, a higher water flow rate will supply a higher water temperature to water source units, but with a lower differential.

  21. Loop Water Flow • 2.Determine WSS Unit Flow Rate • - Total Cooling load must be known. • Diversity Effect must be considered. This is to prevent over sizing water cooler. • Recommended diversity factor; • 85% for system up to 40 tons • 80% for system between 40 and 60 tons • 75% for system greater than 60 tons • System diversity will only affect the range of the water cooler. Diversity Factor, D = Block Load / Σ(Peak Load)

  22. Loop Water Flow • 2.Determine WSS Unit Flow Rate • - By using diversity factor, D, the average range of the water source units, Rp : • where typical value of range are between 5C to 8C or equally 9F to 14.4F. Range of Water Cooler, Rs = Twi – Two where Twi = entering water temperature Two = leaving water temperature Rp = Rs /D

  23. Loop Water Flow • 3.Determine individual unit peak cooling load • - By assuming 30% of heat rejection ratio • Substitute 1 into 2: , Qh = 1.3 *D* Qc 1 Qh = mw * Cp * (Twi – Two) where mw = mass flow rate of water Cp = water specific heat Qh = gpm* 500* Rs 2 1.3 *D* Qc = 500 * gpm * Rs Rp = 1.3 * qc / (500 * gpm) By taking qc as individual unit peak cooling load

  24. Loop Water Flow Example 1 A water loop system consists of 30 units of water source heat pump units with a combined total peak loading of 450,000btu/hr. the system is served by a centrifugal water pump. A closed loop water cooler is used to give a leaving water temperature of 30C. the ambient air wet bulb temperature is 25C. Determine the required total system water flow rate. From the given table, at 25C wet bulb temperature, the water flow rate is 2.36 gpm/ton. Therefore, the total system water flow rate is 2.36 gpm/ton * (450000/12000)ton = 88.5 gpm Calculate the average range of the water source units. The system range is first calculated; Rs = 1.3 * D * Qc / gpm / 500 = 1.3 * 0.85 * 450,000 / 88.5 / 500 = 11.24F or 6.24C Rp = Rs / D = 13.22F or 7.35C If one of the water source units has been designed to give a cooling capacity of 11,000btu/hr, calculate the water flow rate required. Rp = 1.3 * qc / (gpm *500) 13.22 = 1.3 * 11000 / (gpm *500) ; gpm = 2.16gpm

  25. Piping Sizing • Pipe Sizing Procedure • The layout drawing should give dimensional lengths of the piping network. • The layout must include all the floors of the building where the water-source units are installed. • Location of water cooler, pumps and boiler must be identified. • All fittings and accessories used in the piping installation should be clearly identified. • Study the pipe circuit layout and do preliminary check if the circuits are balanced. Re-arrange if • necessary. Use balancing valves only if it is not possible to have balanced circuits. • Size the pipes by using the pipe chart. The water velocity should be in the range of 2 – 9 fps, with a • recommended max friction loss of 10 ft of water per 100 ft. • Calculate equivalent pipe length. Include the losses for all the valves and fittings used. Calculate • the total pipe friction loss by using the friction loss value from the pipe chart. Add this with the • pressure drop in heat exchangers, water cooler and boiler. • Select a pump which will match these total system water flow rate and total head pressure.

  26. Piping Sizing Example 2 The water source units which serve the main building has a total installed cooling capacity of 560,000 btu/hr (peak load). There a altogether 40 sets, with 10 sets for each of the four floors. The water source units have been selected based upon the following conditions: Entering air = 25C DB / 18C WB Entering water = 32C All the units are connected to an evaporative water cooler located on top of an adjoining service building outside of the main building. Ambient WB = 24C

  27. Piping Sizing

  28. Piping Sizing • 1. Calculate the total system water flow rate. • Total installed capacity = 560,000 btu/hr (46.67 tons) • Therefore, the total system water flow rate @ 24C wet bulb is 2.19 gpm/ton * 46.67 tons • = 102.2 gpm. • Calculate the range (Rs) of water cooler • For 46.67 tons, use diversity factor of 0.80. • Rs = 1.3 * D * Qc / (gpm*500) • = 1.3 * 0.80 * 560000 / (102.2*500) • = 11.4F or 6.3C. • Calculate the range (Rp) of water source units. • Rp = Rs / 0.80 • = 11.4 / 0.80 • = 14.25F or 7.9C.

  29. Piping Sizing 4. The unit on the 4th floor have been sized to give the following peak loads: By using equation Rp = 1.3 * qc / (500 * gpm) , assume the total system water flow rate is distributed to all the four floors of the main building in such manner.

  30. Piping Sizing Hence, we can no look into the pipe sizing all the way up to 4th floor. Focus is given to determine the route which is having max friction loss to the water pump. Reference is then made to pipe chart to determine a suitable pipe size.

  31. Closed System Piping Flow Graph

  32. Piping Sizing Each of the WSS has fittings as shown below: The water pump has been installed as shown below:

  33. Piping Sizing Water pipe connection to the evaporative water cooler as shown below :

  34. Piping Sizing

  35. Fitting Loses

  36. Valve Loses

  37. < Troubleshooting>

  38. Troubleshooting • 1.Unit cannot Start • Power supply plug disconnected. • Circuit breaker or fuse tripped / blown. • Wiring connection. • 2. Neither Fan Coil Unit & Compressor Run • The fuse may be blown or circuit breaker opened. • Check electrical circuit or motor winding for shorts or grounds. Investigate for • possible over loading. Replace fuse if necessary. • Check wiring connections. It might be caused by loose wire. Replace or tighten. • Control system may be faulty.

  39. Troubleshooting • 3.Compressor does not Operate • Check capacitor if available. Replace capacitor if faulty. • Check wiring connection. Wire connections might be loose. Replace or tighten. • The high pressure switch may tripped due to: • No or insufficient water flows into and leaves heat exchanger. May be clogged. • Water entering temperature higher than the maximum operating conditions. • Not enough air flow into fan coil unit. May be due to dirty filter or block by object, • cardboard • Unit over-charged. Release some of the refrigerant charge. • The compressor internal/external overload protection is opened. If the compressor body is extremely hot, the overload will not reset until it cooled down. • The compressor winding may be grounded to the compressor shell. If so, replace the compressor.

  40. Troubleshooting • 4.Insufficient Cooling • Power supply plug disconnected. • Check controller temperature setting. • Filter may be clogged. Check and clean the filter. • Check capillary tube for possible restriction of refrigerant flow. Replace capillary tube. • The reversing valve may be defective (valve position is not shifted properly), creating a bypass of refrigerant. Check the reversing valve coil connection. • Check for restriction of air and water flow. • Refrigerant leakage. Check all piping bends and connection for leakage. Repair the leakage area or replace with new piping. • Window or door wide open. • Unit may be under-sized.

  41. Troubleshooting • 5. Insufficient Water Flow through Heat Exchanger • Valves are not opened fully. • Circulating water pump is faulty. • Water pipes or strainers are clogged. • 6. Noisy Operation • Check for loose bolts or screws & ensure rubber isolators are used for installation. • Check for water balance to unit for proper water flow rate. • Check for tubing touching compressor or other surface. Readjust tubing by bending it slightly. • Fan (fan coil unit) knocking / hitting on its housing. • May be due to worn compressor bearing.

  42. < FAQ>

  43. FAQ • How to judge water capacity in the system if water pressure meter is not available? • Measure the pressure drop across the inlet & outlet tube. The nominal flow rate can be • estimated from table below.

  44. FAQ 2. Minimum & maximum recommended water flow rate? It is advisable to maintain within 10% of the nominal water flow rate so that the temperature diffrential wouldn’t too great. 3. Minimum & maximum water entering temperature?

More Related