Surge Protective Device 配置及選用

Surge Protective Device 配置及選用. 突波器裝了根本沒用?. 很常聽到業主、工程顧問公司抱怨,突波消除器裝了很多,但是一打雷,設備還是燒壞一片。 會有這樣的狀況,問題不外乎在於突波器的 配置、選用 與 品質 三個部分。 本簡報之重點在於:如何 配置 及 選用 。. 完整的 避雷 保護方案. 六點保護計劃. 1. 將雷電攔截到最佳和已知的點. 2. 將雷電能量安全地傳送至大地. 3. 將雷電能量排放到低阻抗之接地系統. 4. 將所有接地連接以消除接地迴路和建立等電位面. 5. 保護進入室內之所有電力線路.

errin
Download Presentation

Surge Protective Device 配置及選用

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Surge Protective Device 配置及選用

  2. 突波器裝了根本沒用? 很常聽到業主、工程顧問公司抱怨,突波消除器裝了很多,但是一打雷,設備還是燒壞一片。 會有這樣的狀況,問題不外乎在於突波器的配置、選用與品質三個部分。 本簡報之重點在於:如何配置及選用。

  3. 完整的避雷保護方案

  4. 六點保護計劃 1. 將雷電攔截到最佳和已知的點 2. 將雷電能量安全地傳送至大地 3. 將雷電能量排放到低阻抗之接地系統 4. 將所有接地連接以消除接地迴路和建立等電位面 5. 保護進入室內之所有電力線路 6. 保護低壓資訊/電信等控制信號線路

  5. Point 1 ERICO公司之六點保護計劃 Point 6 Point 5 Point 2 Point 4 Point 3

  6. 接地等電位 4. 將所有接地系統予以連結以消除接 地迴路和建立等電位面.

  7. 接地等電位了嗎?

  8. 接地分開之法規 建築物屋內外電信設備工程技術規範 99年版

  9. 連結各接地系統 等電位箝制器(PEC)可被用來達成符合法規且避免電位差破壞設備的目的,在平常正常狀況下會是接近開路狀態,遇到突波時會瞬間短路,以達到等電位,避免電位差。 PEC PEC

  10. AC 電力線保護 5. 保護進入室內之AC 電力線

  11. 突波保護架構圖(配置)

  12. 電力突波選用參數 突波保護器需要: 1. 好的突波額定(8/20μs)-產品壽命 Imax:1次。 In:15次 2. 低的電壓保護額定值-保護設備 3. 可承受故障電流-周邊安全 4. 第三公正單位測試認證 5. 符合現場電力系統

  13. 突波保護 典型的突波波形

  14. 突波額定 (IEEE C62.41.2-2002)IEEE建議值

  15. 突波額定 (NFPA 780/2011) 4.18.3.1 Electrical Power Circuits 4.18.3.1.2 SPDs at the service entrance shall have a nominal discharge current (In) rating of at least 20kA 8/20μs per phase.

  16. 突波額定 (NFPA 780/2011) 4.18.3.2. Signals, Data, and Communication Protection SPDs shall be listed for the protection of signal, data, and communications systems and shall have an Imax rating of at least 10kA 8/20μs or greater when installed at the entrance.

  17. 突波額定 建議之突波額定 用於每相AC系統之突波保護器

  18. CRITEC TDX100M、200M介紹 1. 好的突波額定(8/20μs). Imax 100~200kA (8/20 μs),Iimp 12~20kA (10/350 μs),In 40~80kA (8/20 μs),符合國際標準。 2. 低的電壓保護額定值 <600V (120V@3kA),<1000V(240V@3kA) <1200V (120V@20kA),<1800V(240V@20kA) 3. 可承受故障電流 200kAIC 4. 第三公正單位測試認證 UL、ETL認證,依照UL 1449標準 5. 搭配各種系統電壓 TDX100M 100kA 8/20us per phase TDX200M 200kA 8/20us per phase

  19. CRITEC TDX200M 典型安裝圖

  20. CRITEC SES40PVC系列 價格較低的選擇 1. 突波額定(8/20μs). Imax 40kA (8/20 μs),In 20kA (8/20 μs) ,適合用在二次盤以後。 2. 低的電壓保護額定值 <800V(120V@3kA),<1200V(240V@3kA) 3. 可承受故障電流 200kAIC 4. 第三公正單位測試認證 UL1449 第三版認證 5. 搭配各種系統電壓

  21. 突波保護器之安裝– 漏電斷路器 SPD SPD

  22. 電話和資訊線路保護 6.保護低壓資訊/電信迴路

  23. 信號突波器UTB系列 1. 好的突波額定(8/20μs) Imax 20kA 2. 低的電壓保護額定值 <10V (5V @3kA) <25V (15V @3kA) <44V (30V @3kA) 3. 第三公正單位測試認證 UL 497B認證 4. 適用於DC 5V、15V、 30V、60V和110V

  24. 信號接地與設備接地

  25. 信號接地與設備接地

  26. ERICOMWESS基本規格 戶外三合一監視系統突波器 1. 好的突波額定(8/20μs) Imax 25kA 2. 低的電壓保護額定值 <50V L-L (power and data @3kA) <60V (viedo @500A) 3. 第三公正單位測試認證 UL 497B認證

  27. ERICOMWECSPOE基本規格 戶外網路突波保護器(Cat.5) 1. 好的突波額定(8/20μs) Imax 25kA 2. 低的電壓保護額定值 <50V L-L (L-L @3kA) 3. 第三公正單位測試認證 UL 497B認證

  28. 電信系統

  29. 突波產品(電 信, 資 訊) CSP DEP CCTV LCP UTB LAN