1 / 6

室内气流组织

室内气流组织. 采暖空调、通风对 气流组织的要求. 通风对气流组织的要求: 1 、 排风口应尽量靠近有害物缘浓度高的区域。 2、送风口应尽量接近操作地点。 3、通风房间尽量送风气流均匀分布减少涡流。. 空调气流组织的要求. 经过处理的空气送入被调节的区域、房间或空 间,在与周围空气进行热质交换的同时,保持一定 受控区内的温度、湿度、清洁度和风速处于合理的 数值范围内,且并以不同的方式从被调节对象排出 等量的空气,保持空气量平衡。. 气流组织的评价指标. 不均匀系数:.

jase
Download Presentation

室内气流组织

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 室内气流组织

  2. 采暖空调、通风对 气流组织的要求 • 通风对气流组织的要求: 1、排风口应尽量靠近有害物缘浓度高的区域。 2、送风口应尽量接近操作地点。 3、通风房间尽量送风气流均匀分布减少涡流。 • 空调气流组织的要求 经过处理的空气送入被调节的区域、房间或空 间,在与周围空气进行热质交换的同时,保持一定 受控区内的温度、湿度、清洁度和风速处于合理的 数值范围内,且并以不同的方式从被调节对象排出 等量的空气,保持空气量平衡。

  3. 气流组织的评价指标 • 不均匀系数: 测点温度、风速的不均匀系数 Kt、Ku愈小,则气流的 分布均匀性愈好。 • 空气分布特性指标: (ADPI)定义为满足规定风速和温度要求的测点与总测数 之比。 即: ADPI=(-1.7<ΔET<1.1的测点数)/总测数×100% • 换气效率 换气效率为可能最短的空气受命与平均空气寿命之比 • 能量利用系数 能源利用系数用η来表示,即η(tp+to)/(tn+ to) 式中 tp、to、tn——分别为排风温度,工作区空气平均温度和送风温度。

  4. 气流组织的典型流型及其特点 传统的送风形式,能够 形成比较均匀的温 度场和速度场 • 上送下回 将送排(回)风管道 集中于空间 上部 • 上送上回 具有一定的节能效果 有利于改善工作 区温度 • 下送下回 • 中送式 存在着温度分层现象

  5. 送风口与回风口 • 侧送风口类型 • 顶棚送风口类型 • 活动百叶送风口 • 固定百叶送风口 • 喷口送风口 • 球型可旋送风口 • 孔板(铜板制)送风口 • 散流器型送风口 • 盘型送风口 • 顶棚喷口型送风口 • 顶棚条逢型送风口 • 顶棚方形送风口 • T型缝型送风口 • 轴流、扩散两用送风口

  6. 典型气流组织的计算 • 孔板送风设计计算步骤: • 确定孔板送风的型式 • 确定孔板送风出口的风速vs • 选取送风温差 • 根据送风速度vs和送风量ls,计算孔口总面积fk • 确定孔口中心距l(m)和孔口数目n • 校核工作区的最大风度vx,使其不大于工作区允许风度 • 校核工作区最大轴心温差Δtx • 稳压层的高度hW

More Related