照明负荷的计算

照明负荷的计算. 照明负荷的计算(需要系数法). 1 、白炽灯、卤钨灯: P 30 =K d P e 对于有镇流器的电光源: P 30 =K d P e(1+a) P 30 表示照明计算负荷( kw ); Pe 表示线路装灯容量( kw ); Kd 表示需要系数,需要系数表示不同性质的建筑对照明负荷的需要程度,一般按表选取; a 为镇流器的功率损耗系数. 各种建筑的照明负荷需要系数. 3. 照明负荷的计算. 举例 1 :. 白炽灯的功率为 100W ,学校(医院). 当照明负荷为不均匀分布时:. P 30 =K d P emax

lowell
Download Presentation

照明负荷的计算

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 照明负荷的计算

  2. 照明负荷的计算(需要系数法) 1、白炽灯、卤钨灯: P30=KdPe 对于有镇流器的电光源: P30=KdPe(1+a) P30表示照明计算负荷(kw); Pe表示线路装灯容量( kw ); Kd表示需要系数,需要系数表示不同性质的建筑对照明负荷的需要程度,一般按表选取; a为镇流器的功率损耗系数

  3. 各种建筑的照明负荷需要系数

  4. 3 照明负荷的计算 举例1: 白炽灯的功率为100W,学校(医院)

  5. 当照明负荷为不均匀分布时: P30=KdPemax Pemax表示最大一相的装灯容量()

  6. 计算插座容量 P30=KdKtPe • Kt表示同时系数 • Pe表示插座组的额定功率之和(W)

  7. 照明负荷的计算 举例2:某照明平面图,如下: 其中:日光灯的功率为40W,吸顶灯的功率为40W,插座按100W计算,计算照明干线的计算负荷?

  8. t t t t 3 3 3 3 3 WL1 WL3 WL2 AL2

  9. 线路工作电流计算 (1)白炽灯或卤钨灯 单相线路: I30=P30/UP 三相线路:I30=P30/√3UL UP:照明线路额定相电压;UL照明线路额定线电压;

  10. 线路工作电流计算 带镇流器的照明线路工作电流: 单相线路: I30=P30/UPCOSa 三相线路的工作电流计算

  11. 线路工作电流计算 计算例1和例2的工作电流

  12. 照明导线的选择: 满足三个条件: 1、按载流量选择 2、按电压损失选择 3、按机械强度选择

  13. 电气照明设计的步骤: 1、选择灯具,确定灯具数量 采用比功率法 2、负荷计算,并计算工作电流 3、选择导线截面,按大一级选取 4、穿管管径选择