第四章 冷热负荷计算

第四章 冷热负荷计算. 韩文泉. 第二节 计算. 一、房屋热损失 (一)热损 通过平壁的稳定传热 吸热 导热 散热 Q1/an=anF(tn-Tn) (δ∕λ)Q2F(Tn-Tw) Q3/aw=F(Fw-tw) Qs={1/(1/ɑn+δ∕λ+1/aw)F(tn-tw) 或 Qs=KF(tn-tw) K=1/a+δ/λ+1/aw 即传热系数 热阻 R¹=1/K 空气层的厚度一般不大于 5cm Qs=KF(tn-tw)a a— 温度修正系数. 2 、室外计算温度的确定 历年 50h 3 、围护结构面积的丈量

Download Presentation

第四章 冷热负荷计算

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 第四章 冷热负荷计算 韩文泉

  2. 第二节 计算 • 一、房屋热损失 • (一)热损 • 通过平壁的稳定传热 吸热 导热 散热 • Q1/an=anF(tn-Tn) (δ∕λ)Q2F(Tn-Tw) • Q3/aw=F(Fw-tw) Qs={1/(1/ɑn+δ∕λ+1/aw)F(tn-tw) • 或 Qs=KF(tn-tw) K=1/a+δ/λ+1/aw 即传热系数 • 热阻 R¹=1/K 空气层的厚度一般不大于5cm • Qs=KF(tn-tw)a a—温度修正系数

  3. 2、室外计算温度的确定 历年50h • 3、围护结构面积的丈量 • 原则:避免重复和遗漏 • 4、维护结构的最大传势系数 • 为了防止凝水 Tn=t1+1ºC kmax=an{tn-(t1+1)/tn-tn}a} • 为了排除凝结水,玻璃要垂直安装,同时窗下应装有排水管来收集和排除凝结水

  4. (二)房屋热损失的附加值 • 1.方向附加 风力附加 外门开启附加和纺高附加 • 2.方向附加 • 3.风力附加 5%—10% • 4.外门开启附加 • 5.房高附加 当h>4m时,没增高1m应附加2%

  5. (三)渗入冷空气的热损失 单门与双门

  6. 二、车间的散热散湿量 • (一)、夏季的传热量 • 外传热只占10%—20% • 太阳辐射——屋顶与墙壁 玻璃窗 • 纺织厂车间温度一般在下午四时左右最高 • 围墙结构的蓄热作用

  7. (二)机器的散热量 • Q3=10³nNφа N=Ne n=0.7—0.9 • (三)、照明设备散热量 • 白炽灯 Q4=10³N 日光灯 Q4=10³(N1+N2)

  8. (四)人体的散热量 Q5=nq • (五)液槽面的散热和散湿量 W=β(P2-P1)F(101325/B)

  9. 三、总冷热负荷的确定 • 夏季 Q1=Q+Q2+Q3+Q5 冬季 Qr=Qs-Q3-Q5

  10. 本章小节 • 1、防止凝露是最基本的要求 • 2、冬季需考虑附加热损。 • 3、太阳辐射可简化。 • 4、机器散热应按实值。 • 作业: 4-6 4-7