EAGLE QUANTUM PREMIER SYSTEM TRAINING July 2006

DETECTOR ELECTRONICS CORPORATION. EAGLE QUANTUM PREMIER SYSTEM TRAINING July 2006. Systems Class 102. Welcome Agenda Introductions Systems Overview. Agenda. Day 1 EQP Overview EQP Flame Detection EQP Gas Detection Break for Lunch EQP System Q & A Hardware Exercise. Agenda. Day 2

nigel-berry
Download Presentation

EAGLE QUANTUM PREMIER SYSTEM TRAINING July 2006

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. DETECTOR ELECTRONICS CORPORATION EAGLE QUANTUM PREMIER SYSTEM TRAINING July 2006

  2. Systems Class 102 Welcome Agenda Introductions Systems Overview

  3. Agenda Day 1 EQP Overview EQP Flame Detection EQP Gas Detection Break for Lunch EQP System Q & A Hardware Exercise

  4. Agenda Day 2 S3 Software Introduction S3 Software Exercise Break for Lunch Logic Programming Product Approval Q & A

  5. Agenda Day 3 Redundancy and Development Discussion Support

  6. Systems Group Overview Definition Goals Market Structure & System Types Organization Capabilities Eagle Quantum Premier Brief Overview

  7. Definition • What is a Systems Project? • An Engineered solution that includes • Any combination of flame and/or gas detectors or other field devices • A signal receiver/controller • Any combination of output signals and/or devices required by the customer • A system enclosure or panel • Power source/battery back-up • Custom Documentation

  8. Group Goals • To be the world’s leading supplier of- • Conventional Fire & Gas Detection Systems • Addressable Fire & Gas Detection Systems • Fire Suppression & Emergency Shutdown Systems • Special & Custom Systems

  9. Bechtel Brown & Root TOTAL PROJECT/EPC ABB Siemens Honeywell MICC Hima, Triconex ICS, Wormald Silvertech ESD SYSTEM Growth with greater systems offering Dooley Tackeberry Hiller Wilson F & G SYSTEM High Hazard Component Suppliers DEVICES Supplied by Det-Tronics Growth with greater device offering F & G Systems Market Structure EPC = Engineering Procurement & Construction MICC = Main Instrument Controls Contractor Det-Tronics Systems Market Growth Plan

  10. TypicalPlant Control Systems Stand-alone systems Plant SIS - Fire Alarm, Flame Detection, Gas Detection & Suppression System Plant ESD - Emergency Shut Down Plant SCADA or Distributed Control System

  11. Logic Solver/PLC/Panel by others Conventional System Configurations • Home-run Field Wiring

  12. Supervised Inputs Heats, Smokes and MAC’s UV/IR Fire Detection Agent Release 4-20mA input DCIO Module DCIO Module UV Fire Detection IR Fire Detection HC Gas Detection Toxic Gas Detection Premier Controller • Ports • RS-485 serial Link (Modbus RTU) • Configuration (serial port) • Redundant media ControlNet MIR Fire Detection KNUS GLASSET TRYKK HER PRESS HERE BREAK GLASS BN- 300 BRANNALARM Tilpasningsenhet FIRE ALARM Interface unit Nr. No. Addressable Fire & Gas System European Certifications 94/9/EC ATEX EN50081-1 & 2 Electromagnetic compatibility EN50130-4 Immunity of fire, intruder and social alarm systems EN 50270 Detection and measurement of gases North American Certifications FM 3260-2000 Flame performance FM 6310/6320 Gas performance NFPA 72 1999 National Fire alarm code CSA - gas performance and Haz locations

  13. Capabilities • Project Management • USA, Singapore, and UK • Project Engineering • USA, Singapore • Systems Staging • USA (Minneapolis and Houston), Singapore • Field Service • USA (Minneapolis and Houston), London, France Singapore, & China plus representative organization

  14. Capabilities • Total Safety Solutions • Fire Detection /Mitigation systems: • Fire Detection • Gas Detection • Fire Suppression systems • CO2, Water Mist, FM200 • Emergency Shutdown (ESD) Systems • Safety controllers • Triconex, HIMA, others • Fire Alarm Systems • Eagle Quantum Premier • Fire alarm panels (Pegasys, KI 1019, FENWAL, Vega)

  15. Capabilities • System Support • Power Supply systems (batteries…etc) • Human Machine Interface (HMI) systems • Documentation - • Non-standard/custom requirements • Manufacturing Record Books, Test Plans, • Support • Field Service • Installation Supervision • FAT/SAT • In-house Expertise

  16. Organization Chart

  17. Systems Support Singapore Minneapolis • CAPABILITIES • Sales • Proposals • Proj. Mgmt • System Integration • Subcontract • FAT • CAPABILITIES • Worldwide Coordination • Sales • Proposals • Proj. Mgmt • System Integration • FAT Houston UK • CAPABILITIES • Sales • Proposals • Proj. Mgmt • System Integration • FAT • CAPABILITIES • Sales • Proposals • Proj. Mgmt • FAT

  18. Eagle Quantum Premier System Overview and Features

  19. Addressable - Hazardous Location

  20. Det-Tronics - Eagle Systems Evolution • Evolved to meet our customer’s needs • Eagle2000™ Hazardous Event Monitoring System • Introduced 1993 • Eagle Quantum • Introduced 1996 • Eagle Quantum Premier • Introduced 2003

  21. EQP - Description • Eagle Quantum Premier (EQP) System- • is the latest generation in the Eagle addressable system family • combines “fire detection and extinguishing agent release” and “hazardous gas monitoring” in one complete package • is intended for use in hazardous locations • is designed to meet the requirements of global approval agencies • supports up to 246 devices • supports a LON length of 2000 meters with base system • can be expanded using network extenders to a max LON distance of 10,000 meters

  22. 24 vdc power supply PSM European Certifications 94/9/EC ATEX EN50081-1 & 2 Electromagnetic compatibility EN50130-4 Immunity of fire, intruder and social alarm systems EN 50270 Detection and measurement of gases North American Certifications FM 3260-2000 Flame performance FM 6310/6320 Gas performance NFPA 72 1999 National Fire alarm code CSA - gas performance and Haz locations KNUS GLASSET TRYKK HER PRESS HERE BREAK GLASS Battery BN- 300 BRANNALARM Tilpasningsenhet FIRE ALARM Interface unit Nr. No. EQP Addressable Fire & Gas System246 node maximum Supervised Inputs Heats, Smokes and MAC’s Agent Release Signal / Audible Devices SAM UV/IR Fire Detection X5200 • I/O Modules • Relay • AIM • IPM DCIO Module ARM UV Fire Detection X2200 IR Fire Detection X9800 Network Extender IDC HC Gas Detection Eclipse Toxic Gas Detection DCU / DCUEX Supervised Digital inputs Premier Controller • Ports • Configuration (serial port) • RS-485 serial Link (Modbus RTU) • Redundant media ControlNet MIR Fire Detection X3301 Operator Interface Station running S3 software Ver 2.8 OPC option

  23. EQP - Controller • The system consists of a “multi-channel programmable controller” and a number of addressable microprocessor based field devices. • Scrolling alphanumeric display provides status information • Flexible communication options • Significantly smaller, yet far more powerful than Eagle Quantum system controller

  24. EQP - Field Devices - Legacy • Supports Eagle Quantum “Legacy” field devices. • EQ2500ARM Agent Release Module. • EQ2500SAM Signal Audible module. • EQ2200IDC Initiating Device Circuit module. • EQ2200IDCGF Ground Fault monitor. • EQ2200DCU & EQ2200DCUEX Digital Communication Units. • EQ2400 Network Extender • EQ2100 Power Supply Monitor

  25. EQP Field Devices - Gas Detector • PIRECL Pointwatch Eclipse • Combustible hydrocarbon detector • Software programmable for various gases: Methane,Ethane Propane, Butane, Ethylene, Propylene • Supports handheld interrogator connection in field using HART protocol.

  26. EQP – Field Devices - Flame • X-Series is EQP ready • UV/IR (X5200) • UV (X2200) • IR (X9800) • Multispectrum IR (X3301)

  27. Ultraviolet Flame Detector (X2200) • Improved ARC rejection algorithm • 1850 –2450 Angstroms solar blind • Multiple fuel verified

  28. Single Frequency Infrared Flame Detector (X9800) • Time Domain Signal Analysis, IR signal processing • Analyzes the raw IR sensor signal “randomness” • Rejects signals that do not meet randomness criteria • 4.45 micron solar blind • Quick fire response • Heated optic • Multiple fuel verified

  29. Ultraviolet Infrared Flame Detector (X5200) • Dual signal processing UVIR • ARC rejection algorithm, UV signal • Time Domain Signal Analysis, IR signal processing • 1850-2450 angstroms solar blind • 4.45 micron solar blind • Quick fire response • Heated optic • Multiple fuel verified

  30. X3301 Multispectrum Infrared Flame Detector • Multiple Patents • Wavelength • Algorithm • Digital signal Processing • Heated optics • Extended Cone of Vision • Combines the longest detection range with the best false alarm rejection capabilities • Multiple fuel verified, lowest cost of coverage all fuels

  31. Flame Detectors Optical Integrity • Calibrated MAG-Oi, no test lamp required! • Automatic and manual optical integrity test verified to perform a calibrated test of the detector operation. • Manual and MAG-Oi perform system activation

  32. EQP – Field Devices - Flexible • EQ3700DCIO • Eight channel Direct Current Input/Output module. • EQ 3720RM • Eight channel relay output module • EQ3710AIM • Eight channel Analog input module • EQ3720IPM • Intelligent Protection Module

  33. EQP – Controller Details • Controller logic processing 10X faster than LCU. • New LON transceivers process field data 2X faster than LCU. • 8 onboard dry contact inputs. • 8 onboard relay outputs. • Dedicated fault relay. • Dual media Control-Net option for Allen-Bradley compatibility. • Future Expansion capability. • 2 onboard serial interfaces for configuration and data exchange. 8 Dry Contact Inputs 8 Relay Outputs Fault Relay Field Device Network (LON) Field Device Network (LON) EQP CONTROLLER Dual Media ControlNet Interface (Optional) Future Expansion Capabilities Onboard Serial Interface RS-232 Configuration PC RS-485 Modbus RTU Master

  34. DI DO EQP CONTROLLER AB MB EQP System Overview • EQP Controller is the start and end of the network. • Local Operating Network & Signaling Line Circuit (LON/SLC) • Up to 2000 meters and 60 devices in base configuration. • Power Supply Monitor, power supplies, battery charger, etc. Power Supply Monitor Battery Charger & PS

  35. DI DO EQP CONTROLLER AB MB EQP System Overview - Loop • LON Diagnostics and Integrity testing done by the controller. • Network extenders allow for the LON/SLC to grow. • An additional 2000 meters distance per extender. • An additional 60 devices per extender Network Extender Power Supply Monitor Battery Charger & PS

  36. DI DO EQP CONTROLLER AB MB EQP System Overview - Flame • Flame detection from a full range of technologies. • IDC Provides two channels for supervised inputs from heat detectors, smoke detectors, etc. • Quantum UV detector. • Quantum UV/IR detector • X3301 Multi-spectrum IR detector • NFP IR detector Initiating Device Circuits (IDC) UV High Temp Detector X2200 UV Flame Detector X2200 UV/IR Flame Detector X5200 X3301 Flame Detector IR Flame Detector X9800 Network Extender Power Supply Monitor Battery Charger & PS

  37. DI DO EQP CONTROLLER AB MB EQP System Overview - Gas • Gas detection from a full range of technologies. • PIRECL provides IR hydrocarbon detection • OPECL open path • DCU provides 4-20 ma input capability for toxics and special purpose detectors. • DCUEX provides input capability for catalytic sensors. Initiating Device Circuits (IDC) UV Flame Detector UV/IR Flame Detector X3301 Flame Detector IR Flame Detector Network Extender Eclipse PIR Gas Detector Digital Com. Unit DCU Digital Com. Unit DCUEX Power Supply Monitor Battery Charger & PS

  38. DI DO EQP CONTROLLER AB MB EQP System Overview - Flex I/O • Supervised output capabilities for signaling and releasing requirements. • Signal Audible Module (SAM) provides two independent supervised output channels. • Agent Release Module (ARM) provides supervision and control of one or two releasing solenoids. Initiating Device Circuits (IDC) UV Flame Detector UV/IR Flame Detector X3301 Flame Detector IR Flame Detector Network Extender Eclipse PIR Gas Detector Digital Com. Unit DCU Agent Release Module (ARM) Signal Audible Module (SAM) Digital Com. Unit DCUEX Power Supply Monitor Battery Charger & PS

  39. 8 Channel DCIO Intelligent Protection Module (IPM) DI DO EQP CONTROLLER AB MB EQP System Overview - Flex I/O • High density I/O Modules. • DCIO provides eight channels that can be configured as either inputs or outputs. • Relay module provides eight non-supervised relay outputs. • AIM eight channel analog input module • IPM intelligent protection module Initiating Device Circuits (IDC) UV Flame Detector UV/IR Flame Detector X3301 Flame Detector IR Flame Detector Analog Input Module(AIM) Network Extender Eclipse PIR Gas Detector Relay Output Module(RM) Digital Com. Unit DCU Agent Release Module (ARM) Signal Audible Module (SAM) Digital Com. Unit DCUEX Power Supply Monitor Battery Charger & PS

  40. S3 Software Package • PC-based System Software package • Data Collection Distributor (DCD) • Configuration of field devices • Creation of user logic (IEC61131-3) • offline simulation/testing of user logic • on line logic monitoring • creates drawings of the logic • Diagnostics • Alarm/Event logging • Custom Graphics • customer specific graphics of plant layout, etc.

  41. EQP – Questions & Answers • Smaller • Faster • Smarter