Wiring of Communication Modules mMINT, PMINT, MCAM and PCAM

This guide explains the wiring requirements for communication modules in mMINT, PMINT, MCAM, and PCAM devices. It includes instructions for Modbus RTU and PROFIBUS DP networks.

rruggles
Download Presentation

Wiring of Communication Modules mMINT, PMINT, MCAM and PCAM

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Wiring of Communication ModulesmMINT, PMINT, MCAM and PCAM

  2. mMINT Communication Wiring Modbus RTU Network Master RS-485 Modbus SW3 should be moved to the ON position only when it is the last device in a chain of devices or if it is a single device. A Tx/Rx + Tx/Rx - B GND* SHD *) Connect shield to ground at master device end only. Interconnect shielding where devices are daisy-chained. (For diagnostics) SW1 should be moved to the ON position only when it is the last device in a chain of devices or if it is a single device. IZM26 Integrated -Status (on/off) sensors -Shunt trip and spring release control only available with Digitrip models 1150x **) for diagnostic mode, to configure the mMINT Feed control voltage to A14 and A15 for breaker remote control and for Trip Unit operation without current flow. Terminal B1 Terminal B2 +, P 0V, N INCOM +, P Terminal A14 0V, N Terminal A15

  3. PMINT Communication Wiring PROFIBUS DP Master RS-485 PROFIBUS DP Connect the INCOM Shield wire to ground at master device (PMINT) end only. SHIELD Position of breaker in drawer IZM-CS in position D IZM-CS in position C 6 5 4 3 2 1 IZM26 NO C NO C Integrated -Status (on/off) sensors -Shunt trip and spring release control only available with Digitrip models 1150x INCOM +, P 0V, N Feed control voltage to A14 and A15 for breaker remote control and for Trip Unit operation without current flow. GND CBSW2 Terminal B1 CBSW1 Terminal B2 +, P Terminal A14 0V, N Terminal A15

  4. MCAM Communication Wiring* (Front View of MCAM) (Top View of a mounted MCAM on IZM) wiring for remote control (Shunt trip and spring release) Modbus Communications Adapter Module Cat. MCAM 5 Close 4 Open 3 COM - R 2 0V 24 Vdc- 1 24 Vdc+ 24 Vdc+ Modbus RTU Master Integrated Status (on/off) sensors in breaker Modbus Control 4 Shield GND** 3 Enable COM - C 2 Disable inverting A (Tx/Rx-) Tx/Rx- 1 B (Tx/Rx+) Tx/Rx+ Source Ground non-inverting RS-485 Modbus MCAM

  5. PCAM Communication Wiring* (Front View of PCAM) (Top View of a mounted PCAM on IZM ) wiring for remote control (Shunt trip and spring release) Series NRX PROFIBUS Communications Adapter Module Cat. PCAM PROFIBUS DP Master RS-485 PROFIBUS DP PROFIBUS Control 5 Close 4 Enable Open Integrated Status (on/off) sensors in breaker 3 Disable COM - R 2 0V 24 Vdc- Source Ground 1 24 Vdc+ 24 Vdc+ PCAM

  6. ECAM Communication Wiring* (Front View of ECAM) (Top View of a mounted ECAM on IZMX) wiring for remote control (Shunt trip and spring release) Series NRX Ethernet Communications Adapter Module Cat. ECAM 5 Close 4 Open 3 COM - R 2 0V 24 Vdc- 1 24 Vdc+ 24 Vdc+ Integrated Status (on/off) sensors in breaker Ethernet Control Enable Ethernet Network, Switch, or PC Connection Disable Source Ground ECAM

  7. Remote Control Possibilities through Network

  8. Modbus RTU Network RS-485 XV-102 USB-RS 485 Converter RS485 B A Pin 3 A Pin 7 B + - Pin 3 Pin 2 Modbus RTU B A TB2-1 B TB2-2 A XIOC-SER Tx/Rx- Tx/Rx+ XC200