Chiller Panel Controller

Chiller Panel Controller. Hardware Description. Navigation Key. Short Cut Key. LCD Display. Switching Cool Mode. On/Off Indicator. Switching Heat Mode. Navigation Key (Up & Down). On/Off Shortcut Key. Execute Instruction Key. Show Alarm Key. Cancel Instruction Key.

thalia
Download Presentation

Chiller Panel Controller

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Chiller Panel Controller

  2. Hardware Description Navigation Key Short Cut Key LCD Display Switching Cool Mode On/Off Indicator Switching Heat Mode Navigation Key (Up & Down) On/Off Shortcut Key Execute Instruction Key Show Alarm Key Cancel Instruction Key We can ONLY use the short cut key in the summary page !

  3. Hardware Description CMOS Reset Jumper (JH2) Backup Battery Reset some of the settings to the DEFAULT value Chiller Terminal Unit Connection (CN8) Memorize of Date, Time & Timer Schedule +12Vdc, GND; A, B

  4. Input Signal Fan Overload (FO) Low Pressure switch (LP) High Pressure Switch (HP) Compressor overload (CO) Water Flow Error (FL) Pump Overload (PO) Defrost Sensor Error (DE) Discharge Sensor Error (CD) Sensors Defrost Sensor Compressor Discharge Sensor Outdoor Ambient Sensor Leaving / Entering water Sensor Mini Chiller Main Board (MC 01)

  5. Outdoor fan (1) Alarm In Antifreeze heater Outdoor fan (2) Compressor (1) 4-Way valve (1) Water Pump Compressor (2) 4-Way valve (2) Output Signal If the Relay is activated, there is a 240V power supply out from the board

  6. Panel Connection Input and Output Signal Display the Operation Status/ Control the Operation

  7. Features • Graphical LCD Display • Network to link up the Chiller (Chiller BUS) • Password Protected Advance Parameter Setting • Individual Cool Set Temperature and Heat Set Temperature • Status Display (Panel Temperature, Defrost and Discharge Sensor Temperature, erasable compressor run time) • Manual Defrost Selection • Real Time Clock (RTC) and Date Display • 7 days Programmable timer ( 2 ON/OFF timer) • 47 Types of Alarm Display • 20 erasable Alarm Memories • Screen Saver Display

  8. Installation Of Chiller Panel Controller • Supply +12 Vdc as a power source to the device • Maximum current is 200 mA • Isolated all the low voltage wiring (communication bus, etc) from high voltage power supply wiring • 4 way wires (CN8 – CN8) provides the easiest solution to communicate between panel and chiller main board

  9. Wiring Connection Connect the Communication Between main board (MC 01) to the Panel with CN8-CN8

  10. Wiring Connection

  11. Press ENTER Press ENTER Press and Hold ENTER for 1s Menu Structure Diagram for Chiller Operation Menu Setting Menu Main menu Timer Menu Summary Pages Unit Selection Menu Alarm Menu Display Menu

  12. Summary Pages • 4 Summary Pages • Display the Operation Status of Chiller • Using All Short cut key • Running Mode • Cooling • Heating Cool Temperature that we set in the Operation Menu 01/01/2000 12:00 am Status : ON Mode : Cooling Cool Temp : 12.0 o C [00] Chiller ID

  13. Display the status of Compressor 01/01/2000 12:00 am Compressor 1 : ON Compressor 2 : Off [00] Summary Page 2

  14. Summary Page 3 Water Return and Water Leaving Temperature Temperature of the Panel 01/01/2000 12:00 am Water In : 19.8 oC Water Out : 13.0 oC Outdoor Air : 32.0 oC Panel : 20.5 oC [00] Outdoor Temperature

  15. Summary Page 4 Number of Compressor in the Chiller Chiller = Cooling Mode Heatpump = Cooling& Heating Mode 01/01/2000 12:00 am Model : Chiller No. Comp : 2 Comp Unit No. : 0 [00] Unit ID (main board ID) Model of Chiller

  16. Operation Menu • Control On/Off status of chiller • Switching Mode • Adjust the Cool and heat Temperature OPERATION MENU Status : ON Mode : Cooling Cool Temp : 12.0 oC Heat Temp : 40.0 oC

  17. Timer Menu • Set the Time and Date • Set The ON/OFF Schedule of the Chiller Set Clock hh : mm TIMER MENU Clock Setting Date Setting Timer Schedule Timer : Disable Set Date yy mm dd • 7 Days Programmable Timer Schedule • 2 ON/OFF timers per day

  18. Set Schedule How to set the Timer Schedule ? Timer 1 Timer 2 ON OFF ON OFF Sun ---- ---- ---- ---- Mon 0800 1200 1300 1700 Tue 0800 1200 1300 1700 Wed 0800 1200 1300 1700 Timer 1 Timer 2 ON OFF ON OFF Thu 0800 1200 1300 1700 Fri 0800 1200 1300 1700 Sat 0800 1200 ---- ---- Set the ON/OFF for timer 1 & 2 Set the timer to “----” in order to disable the event

  19. Timer Schedule • Before the timer schedule will carry any effect, it is needed to set “Enable” in the Timer menu • Set it to “Disable” in order to cancel the timer schedule TIMER MENU Clock Setting Date Setting Timer Schedule Timer : Enable Confirmation of timer schedule

  20. New Alarm Display Faulty or Alarm is triggered “Beeping” sound An New Alarm Message will pop up on the LCD Backlight blinking [Ch 0] Alarm 1 Comp 1 overload 01/01/00 11:00am Alarm occurred type Alarm occurred Unit (chiller ID) Alarm occurred Date Alarm occurred time

  21. How To Clear The Alarm CASE 1 Stop “Beeping” & Backlight blinking via pressing Anykey Press Up & Down key to scroll the alarm display if more than one alarms occurred Dissolve the ALARM For example, If Alarm 1 have been dissolved, Alarm 1 Message will disappear and only display other alarm messages Dissolve the others ALARM It will exit to the Summary Pages automatically

  22. How To Clear The Alarm CASE 2 Unit will Not ON if there is any existing alarms Pressing ESCafter “beeping” sound & backlight blinking stop It will back to summary pages with a sign [A] Press ALARM keyor Go to show alarm in Alarm Menu to display current existing alarms and dissolved them 01/01/2000[A]12:00 am Status : ON Mode : Cool Set Temp : 24 o C Fan : High Room Temp : 27 oC Unit : G0U0 [00] Sign [A]

  23. Alarm Menu Content in Alarm Menu If there is no existing alarms, “show alarms” will display the old record alarm ALARM MENU Show Alarm Erase All Alarms Keep Up to 20 Alarms Erase the records of histories alarms

  24. Alarm Menu Status Of Mini Chiller IF unit detected having faulty Alarm will trigger & Unit will be turn OFF After the alarms have been dissolved Unit can only be turn ON via Manual Reset (Off & On the power supply of Unit) or Auto Reset (Unit will restart all 3 minutes) Setting of reset type can be done in the “Alarm & Contact” in “SET PARAMETER”

  25. Display Menu Display the temp of Discharge sensor for monitoring the high temperature of compressor discharge DISPLAY MENU Defrost Sensor Discharge Sensor Comp run Time Display the temp of defrost sensor for Condensing Unit Compressor Run time of the Chiller

  26. Application with two compressors Partial load capabilities • Two separate refrigerant circuit • Two compressors • 0-50-100% of rated capacity • Improve the reliability and energy efficiency of chiller • If one compressor is spoiled, the unit still can run with one compressor

  27. How chiller works with single compressor? Difference temp of the set-temp and sensed temp (temp of water return/leaving) Temperature Comp on Cooling Set-temp. + Differential Cooling Set-Temp. Comp off

  28. Example Cooling Set-Temp = 12 oC Differential = 3 oC Cooling Set-temp. + Differential. = 15 oC Temperature Comp on 15 oC 12 oC Comp off

  29. How chiller works two compressors? Temperature Comp 2 On Cooling Set temp. + Differential Comp 1 On Cooling Set temp. + ½ Differential Comp 2 Off Cooling Set Temp. Comp off

  30. Example Cooling Set-Temp = 12 oC Differential = 3 oC Room Temperature Comp 2 On (12 +3) = 15.0 oC Comp 1 On (12 + ½ * 3) = 13.5 oC Comp 2 Off 12.0 oC Comp off

  31. Setting of Temperature R1 Cool SP : 12.0 oC R2 Cool Diff : 1.5 oC R3 Heat SP : 40.0 oC R4 Heat Diff : 1.5 oC R5 Min Cool SP : 7 oC R6 Max Cool SP : 20 oC R7 Min Heat SP : 30 oC <ENTER> <ENTER> Setting Menu Main Menu Summary Pages <ESC> <ESC> <ESC> <ENTER> Set Parameter 3. Regulator

  32. Defrost Cycle of Mini Chiller D1 Start Temp : 0 oC D2 End Temp : 14 oC D3 Max Dura : 10 m D4 Interval : 45 m D5 Dly Bfr Def : 0 s D6 Dly Aft Def : 120 oC <ENTER> <ENTER> Setting Menu Main Menu Summary Pages <ESC> <ESC> <ESC> <ENTER> <ENTER> Set Parameter G5 Defrost <ESC> 5. Defrost

  33. Start Defrosting Conditions D1 = 0 oC Defrost timer start counting Defrost sensor <= D1 oC Defrost time reset to 0 Defrost sensor > D1+2 oC For >150 s D4 = 45m After interval time ( D4 ) & Defrost sensor <= D1 oC Defrost Cycle START

  34. Manual Condenser Defrost OPERATION MENU Status : ON Mode : Heating Cool Temp : 12.0 oC Heat Temp : 45 m Manual Defrost <ENTER> <ENTER> Operation Manual Main Menu Summary Pages <ESC> <ESC> “Manual Defrost” only appear in Heating mode

  35. Manual Defrost With Condition D2 = 14 oC Defrost Sensor < D2 oC Select “Manual Defrost” Defrost Cycle Start Compressor will display as DEFROST in Summary Page 2

  36. Defrost Termination Conditions D2 = 14 oC Defrost sensor > D2 oC OR D3 = 120 min Maximum duration of defrost cycle elapsed (>D3 min) Defrost End

  37. Cool Mode Antifreeze Heater Turn on to prevent freezing on Brazed Plate Heater Exchanger when running cooling mode <ENTER> <ENTER> Setting Menu Main Menu Summary Pages <ESC> <ESC> <ESC> <ENTER> Set Parameter 6. Cool Mode Antifreeze ONLY Apply in COOLING MODE A1 Heater SP : 5 oC A2 Heater Diff. : 2.0 oC A3 Sensor : Leave A4 Alarm SP : 3 oC A5 Alarm Diff : 2.0 oC

  38. A3 Antifreeze Sensor Selection • Entering water temp. sensor • Leaving water temp. sensor A1 Heater SP : 5 oC A2 Heater Diff. : 2.0 oC A3 Sensor : Leave A4 Alarm SP : 3 oC A5 Alarm Diff : 2.0 oC

  39. Antifreeze Alarm Antifreeze alarm set Point = 3 oC Differential = 2 oC Temperature Alarm will OFF = 5 oC Alarm Off Antifreeze alarm Set Point + Differential Antifreeze alarm Set Point Alarm will trigger = 3 oC Alarm On Compressor will stop running Temp of BPHE will rise to avoid freezing

  40. Cool Mode Antifreeze Heater Example : Antifreeze Heater On = 5 oC Differential = 2 oC Antifreeze Heater use to Heat Up the BPHE before it drop to Antifreeze Alarm set temperature Temperature Antifreeze heaterOFF= 7 oC Heater off Heater Set Point + Different Heater Set Point Antifreeze heater ON= 5 oC Heater on

  41. Network Between Chiller Panel Controller Chiller Panel 0 (Master) Chiller Panel 1 (Slave) Chiller Panel 2 (Slave) Chiller ID 1 Chiller ID 2 Chiller ID 0 B A Chiller BUS CN8 – CN8

  42. Connection of C BUS Using 2 Insulated wires to link up the C BUS

  43. Setting unit address for main board in the chiller <ENTER> <ENTER> Setting Menu Main Menu Summary Pages <ENTER> G7 Unit No. 1. General Set Parameter <ENTER> <ENTER> • Only Power On one main board in the chiller bus, make sure others main boards are Off (power supply off) • Key in the unit address (G7) and execute • Please label the Main board Unit ID after execute a unit address for it (In order to communicate by controller) • De-energized the main board, and repeat for other main boards in Chiller Bus G1 Model : Chiller G2 No. Comp : 1 Comp G3 On/Off In : Disable G4 Co/Heat In : Disable G5 Ext Alarm In : Disable G6 Water Sys : Isolated G7 Unit No : 0

  44. Chiller Panel 0 (Master) Chiller Panel 1 (Slave) Chiller Panel 2 (Slave) Chiller ID 1 Chiller ID 2 Chiller ID 0 B A Chiller BUS CN8 – CN8 Set Chiller Unit Address OFF OFF OFF

  45. Chiller BUS Features • Monitor mini chiller status and control mini chiller settings (global or individual) • Alarms can be shown in the Master Panel and Slave Panel Chiller Bus Specification • Only aMaster Chillerin a C BUS(Chiller Unit ID is 0) • Master Panel can be more than one in a C Bus (Panel ID is 0) G1 Model : Chiller G2 No. Comp : 1 Comp G3 On/Off In : Disable G4 Co/Heat In : Disable G5 Ext Alarm In : Disable G6 Water Sys : Isolated G7 Unit No: 0 SETTING MENU Set Parameter Change Password Panel Option Set Panel ID

  46. Set Panel ID SETTINGS MENU Set Parameter Change Password Panel Option Set Panel ID • Please enter the • Panel ID … • Unit 0 Enter the Panel ID with 0 Is Master Panel and others No. are Slave Panel

  47. Master Panel Control in C Bus • Master Panel (Set Panel ID O ) • Master Panel can control and view the status for all the chiller in a C Bus Display Status of Master Chiller (Unit No.0) 01/01/2000 12:00 am Status : ON Mode : Cooling Cool Temp : 12.0 o C [00] Control the Settings of Master Chiller (Unit No. 0)

  48. Slave Panel Control in C Bus • Slave Panel ( Set Panel ID is not O ) • Slave Panel only can control and view the status for a specific chiller Display Status of Slave Chiller (Unit No.1) 01/01/2000 12:00 am Status : ON Mode : Cooling Cool Temp : 12.0 o C [01] Control the Settings of Slave Chiller (Unit No. 1)

  49. Can be done in Summary pages only Changing Display Unit Master Panel (Panel ID is 00) can choose to control and display each chiller status in the Chiller-BUS Mastercan control all the slave settings globally and Display the Master operation status Unit Selection : Select All Select one : 0 Mastercan control the slavesettings and display the slaveoperation status individually

  50. Master Panel Control If user choose Select All Display Status of Master Chiller 01/01/2000 12:00 am Status : ON Mode : Cooling Cool Temp : 12.0 o C [All] All other chillers in C Bus will follow the changes of the Master Chiller