1 / 28

2010 HVACR/Plumbing Instructors Workshop

2010 HVACR/Plumbing Instructors Workshop. Practical Psychrometrics Presented by Richard Wirtz, Associate Director of Education Heating, Air conditioning & Refrigeration Distributors International (HARDI). Thank you for being here today. For Everyone’s Consideration.

tinasawyers
Download Presentation

2010 HVACR/Plumbing Instructors Workshop

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 2010 HVACR/Plumbing Instructors Workshop Practical Psychrometrics Presented by Richard Wirtz, Associate Director of Education Heating, Air conditioning & Refrigeration Distributors International (HARDI)

  2. Thank you for being here today. For Everyone’s Consideration

  3. What seems to be the problem? Who teaches psychrometrics on a normal basis? Why is this area not taught more? Confusion? Misunderstanding? Intimidation?

  4. Let’s eliminate the confusion – Right Now. Air properties: Composition Weight Wet or Dry Specific Heat Pressure Volume

  5. The Chart Willis Carrier December 3, 1911 “Rational Psychrometric Formulae” ASME Psychro = cold Metrics = measure of Different temperature ranges Different elevations

  6. “Points on a Map”

  7. North H West East South

  8. Points on the “Map” Dry Bulb Wet Bulb Enthalpy Dew Point Relative Humidity Specific Volume Specific Density Specific Humidity (Grains of Moisture) Sensible Heat Dot Sensible Heat Factor

  9. Where’s Waldo??? North West East South

  10. Process line shows grains of moisture change as well as temperature change. Heating & Humidification Sensible Heating Only Sensible Heating Only Cooling & Dehumidification

  11. Dry Bulb Enthalpy Wet Bulb Grains of Moisture Dew Point Relative Humidity Specific Volume

  12. Sensible heating only No change in the dew point or the grains of moisture.

  13. Let’s Do Some Quick Math Qs = Quantity of Sensible Heat 64,000 Net Output = 1.08 x CFM x ▲T 64,000 = 1.08 x CFM x 40 1481 CFM 64,000 = 1.08 x 1,481 x 40

  14. Continuing QL = Quantity of Latent Heat QL = .68 x CFM x ▲Grains of Moisture QL = .68 x CFM x 0 QL = 0 QT = 4.5 x CFM x ▲Enthalpy QT = 4.5 x CFM x (31.62 – 21.79) QT = 4.5 x 1,481 x 9.83 QT = 65,911 64,000/65,512 = 97.69% or 2.31% difference

  15. Let’s Do Some More Quick Math Qs = Quantity of Sensible Heat 23,680 = 1.08 x CFM x ▲T 23,680 = 1.08 x 1,096 x 20 1.08 x 20 = 21.6 23,680/21.6 = 1,096 CFM

  16. Continuing QL = Quantity of Latent Heat QL = .68 x CFM x ▲Grains of Moisture QL = .68 x 1,096 x 8 QL= 5,962 Btu QT = 4.5 x CFM x ▲Enthalpy QT = 4.5 x 1,096 x (26.80 – 20.58) QT = 4.5 x 1,096 x 6.22 QT = 30,677 29,600/30,677 = 96.49% or 3.51% difference

  17. “Created Equal” does not mean “Equal Outcome”

  18. Additional Information Free software @ handsdownsoftware.com or from a manufacturer or wholesaler or someone here. Just ask someone. Carrier SST-03 “Air Properties and Measurement”

  19. Questions??