ON DIMENSIONING LVDC NETWORK CAPACITANCIES AND IMPACT ON POWER LOSSES

ON DIMENSIONING LVDC NETWORK CAPACITANCIES AND IMPACT ON POWER LOSSES. Andrey Lana, Tero Kaipia, Tuomo Lindh, Pasi Nuutinen, Jarmo Partanen LUT Energy, LAPPEENRANTA UNIVERSITY OF TECHNOLOGY (LUT) Lappeenranta, Finland. Andrey Lana – Finland – RIF Session 2 – Paper ID 1099.

zaide
Download Presentation

ON DIMENSIONING LVDC NETWORK CAPACITANCIES AND IMPACT ON POWER LOSSES

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ON DIMENSIONING LVDC NETWORK CAPACITANCIES AND IMPACT ON POWERLOSSES Andrey Lana, Tero Kaipia, Tuomo Lindh, Pasi Nuutinen, Jarmo Partanen LUT Energy, LAPPEENRANTA UNIVERSITY OF TECHNOLOGY (LUT) Lappeenranta, Finland Andrey Lana – Finland – RIF Session 2 – Paper ID 1099

  2. Presentation outline • Introduction • The LVDC network • Dimensioning of the DC capacitors • Technicalapproach • Modelling, analysis and resultingboundaries • Power losses • Network transient response • Economicalapproach • Conclusions

  3. Introduction

  4. Introduction • What should be taking into account for dimension of DC capacitors? • How network power losses are affected by DC capacitor dimensioning? • When the dimensioning from harmonic losses is economical profitable?

  5. Voltage ripple • Standard on low-voltage electrical installations [IEC60364] requires that DC voltage ripple (in the systems up to 1500VDC) is in 10% range of rated DC voltage. • The front-end 3 phase six pulse rectifier produces 300Hz voltage ripple. • DC capacitor on customer end

  6. Momentary interruptions • The voltage hold up time during MV supply interruption gives one more guideline for selecting the size of capacitors. • The difference in the energy stored in the system capacitors in the beginning and in the end of the supply interruption is equal to the energy needed for load feed.

  7. Maximum DC capacitance • After voltage sag etc., large amount of recharge current may flow to the DC network. • Maximum amount of recharge current should be restricted below the trip current of protection and current handling capacity of the rectifier. • Start-up control of the system is required or size of capacitors have to be limited (Nuutinen et al., START-UP OF THE LVDC DISTRIBUTION NETWORK”, CIRED 2011)

  8. The DC network stability condition • DC network stability condition is the requirement for customer side DC capacitor size. • derived from applying Liénard–Chipart conditions on system characteristic polynomial • Boundaries for the size of the system capacitors derived from the stability conditions are less then from dc voltage ripple requirements.

  9. The DC network resonance System frequency response. Inverter DC capacitance is varied; Rectifier DC capacitance is fixed at 500µF. System frequency response. Rectifier capacitance is varied; Inverter capacitance is fixed at 1600µF.

  10. The DC network resonance System frequency response (from inverter load to rectifier side). Rectifier side DC capacitance is varied. • Small size of the rectifier capacitance can cause possible amplification of the high switching frequency harmonics.

  11. Power Losses in LVDC network • The capacitor placed on the DC terminals of a converter affect directly on the harmonic currents it excites. • The power losses due to current distortion decrease quadratic proportionally to the decrease of harmonic currents

  12. Network transient response HSAR from 3p short circuit @ 1s, t=0.5s Voltage dip @ 1s, t=0.04s

  13. Economical approach • The increase of capacitance in the DC network to reduce the losses is justified, if the reduction in the costs of losses is higher than the price of added capacitance. • If the price of losses is 0.05 €/kWh, peak operation time of losses 1000 h, utilisation period 40 aand the interest rate is 5 %, the unit price for power losses over the utilisation period becomes 857.95 €/kW. Thus, the costs of doubling the size of capacitors from the values used in simulation case 1 to the values used in simulation case 2 can be in maximum 323.45 € during the utilisation period regardless of the lifetime of the capacitors.

  14. Conclusions • Voltage ripple (300Hz) due to 6-pulse bridge and due to inverter operation under unbalanced load condition (100 Hz) have to stay in standard range [IEC60364]: 10% of rated DC voltage • Need to ride through possible short MV supply interruptions due to auto-reclosing operations require energy storing in DC capacitors • System stability set requirements on minimum size of capacitors • Capacitor sizing has direct impact on harmonic losses • Resonance situations need to be checked • Charging currents may limit the size of capacitors • System protection have to be considered • Economical profitability of reducing power losses by increasing capacitance size could be estimated

  15. Thank you! Andrey Lana – Finland – RIF Session 2 – Paper ID 1099