An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Benjamin C. Whitehead, PE Benjamin J. Klayman, PhD, PE Case Study: Commissioning New Rapid Sand Filters at Donald K. Shine Water Treatment Plant

  2. Plant Flow Schematic

  3. South Treatment Facility – Phase IB Expansion

  4. Type of Filtration • Six New Conventional Rapid Sand Filters • Roberts Leotech Underdrain w/IMS Cap • 12-inches Sand • 24-inches Anthracite • Water and Air Scour Backwash • 1360 sq.ft. per Filter • 4 gpm / sq.ft.

  5. New Filter Installation • Filter Underdrain • J-Tube Riser Air Scour Manifold

  6. New Filter Installation • Grout Bed • Grout Infill

  7. New Filter Installation • Completed Underdrain

  8. Filter Media Installation

  9. Completed Filter Cell

  10. Filter Backwash Equipment • Air Scour Blower • Gardner-Denver • Multi-stage Centrifugal • 300 Hp • 5440 scfm @ 6.2 psig • Backwash Pump • Perless Pump Company • Vertical Turbine Mixed Flow • 250 Hp • 32 MGD @ 17.5-feet TDH

  11. Filter Backwash • Backwash Sequence • Drain filter to 6-inches above media • Initiate Air Scour 2 minutes • Add 4 gpm/sq.ft. Low Rate BW (8 MGD) until just below troughs • Stop Air Scour and continue Low Rate water only to top of trough • Initiate 17 gpm/sq.ft. High Rate BW (32 MGD) 4 minutes • Low rate BW (8 MGD) for 1 minute • 10 minute settling delay • Open effluent valve 2 minutes after filling starts • Backwash is reclaimed / returned to raw water influent of the plant

  12. STF Filter

  13. Filter Backwash – Selectable Parameters

  14. Backwash with Air Scour

  15. Backwash with Air Scour

  16. Backwash Backwash

  17. Backwash

  18. MDNRE Requirements • 2 Consecutive 15 min. NTU > 1.0 • 2 Consecutive NTU > 0.5 first 4 hours • 2 Consecutive NTU > 1.0, 3 consecutive months • 2 Consecutive NTU > 2.0, 2 consecutive months • Maintain NTU < 0.3 (<0.1 normally) • < 0.1 NTU @ 7 MGD B&V / City of Wyoming Start-up Goals

  19. Commissioning Plan How do we get there? • Careful Planning • Start Slowly • Filter to Rest • Monitor/Operate Closely • Flow • Turbidity • Headloss

  20. Commissioning Pre-requisites • Media Washing/Screening • VOC testing • Chlorination • Instrumentation / Alarms • Monitoring / Trending • SCADA Control • Backwash Equipment • Backwash Sequence • Transfer Pumping

  21. Commissioning Plan • Initial Start-up: • Initiate Filter Off-line (Filter-to-Waste) • 1 MGD, Filter-to-Waste until < 0.3 NTU • Filter On-line: 1 MGD • > 0.3 NTU, Initiate Settling-delay: 4 hours • Re-test: <0.1 NTU up to 3 MGD • Seasoning: • 2 weeks up to 3 MGD • 1 week off-line

  22. Commissioning Plan Performance Test: • Run Filter Several minutes • Backwash • Place On-line, 1 to 3 MGD • Ramp 0.5 MGD @ 30 min intervals • > 0.2 NTU Initiates Continuous Monitoring • > 0.3 NTU Initiates Filter-to-Waste • Ramp to 7 MGD for 1 hour < 0.1NTU

  23. SCADA Screen – STF Filter Overview

  24. Filter No. 13 Start-up

  25. Filter Performance (Results) • Filter Influent Turbidity: +/- 0.3 NTU • Filter Effluent Turbidity: < 0.1 NTU @ 7 MGD • Filter Effluent Turbidity: 0.02-0.07 after Initial Commissioning & Current Conditions • Filter Headloss: 1 to 7.5-feet • Run Time: 200 hours - New and Existing Filters • 4X longer after expansion • Previously 40-60 hours

  26. Filter Performance • Meurer Research Inc. Plate Settling Equipment

  27. Field Engineering Improvements • Reduced Washwater Quantity • Reduced High Rate Wash: 10 minutes to 4 minutes • Total Wash Volume = 75 gal / sq.ft. (100,000 gal) • Industry Standard = 150-180 gal / sq.ft. (250,000 gal) • Allows for 5 Consecutive Backwashes to Reclaim • Operator Adjustable Settling Delay • Washwater Launder Stabilization • Headloss Instrumentation Calibration • Air Distribution Optimization

  28. Questions? - 31