An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. SURGICAL ROOM AIR CONDITIONERS

  2. SURGICAL ROOM AIR CONDITIONERS

  3. The air conditioning system for surgical rooms must assure a“high air quality”.

  4. To get it the following “six goals” must be achieved:

  5. First goal Elimination or minimization of the chemical contamination due to the anestetical gas

  6. Second goal Elimination of the batteriological contamination coming from the external environement (through fresh air).

  7. Third goal Elimination of the batteriological contamination coming from the surrounding environments

  8. Fourth goal Reduction of the batteriologicalcontamination due to the surgical team or to the patient himself Fourth goal Reduction of the batteriological pollution due to the surgical team or to the patient himself

  9. Fifth goal Guaranty a good level of control of temperature and humidity

  10. Sixth goal Obtain the first 5 goals guarantiing the maximum energy saving

  11. The air conditioning system for surgical rooms must assure a “high air quality”.

  12. First goal: Elimination or minimization of the chemical contamination due to the anestetical gas Chemical contamination cannot be filtered; the only solution is the dilution with a great quantity of fresh air.

  13. First goal: Elimination or minimization of the chemical contamination due to the anestetical gas How great? This depends by the local Standard: In Italy 15 volumes per hour In Germany 1.200 m3/per hour In Switzerland 800 m3/per hour

  14. The fresh air flow must be constant in time even if the filters become dirty and therefore raise there pressure drop. Technical considerations about the first goal Within the unit an air flow measurer is therefore foreseen to informs the microprocessor of the reduction. The microprocessor raises through the inverter the number of revolution of the fan so to get the set air flow.

  15. Double fan for supplying and expelling air for the maximum functionment security. (Accessory)

  16. The batteriological pollution coming from outside is eliminated through the absolute filters to be fitetd at the end of the supply ducts: H12 for general surgery, and H14 for orthopedics and more delicate operations. Second goal Eliminationg of the batteriological pollution from the external environement (through fresh air).

  17. The absolute filter must be the last component of the aeraulic circuit since everything between it and the patient can contaminate the treated air. The absolute filter is therefore installed in the surgical room immediately above the operating bed. Technical considerations about the second goal

  18. The EN10339 Standard , for the duration in time of the fresh air filters, foresees that before an absolute filter another F9 fine filter be installed and before this a G4 filter. Technical considerations about the second goal

  19. Direct expansion surgical room air conditioner MODEL OHA 132/R407 AIR FLOW: 4.400 m3/h

  20. The blocking device of the filter on its gasket must guaranty that the air cannot by-pass the filter itself. The good efficency of the filtrating section must be guarantied and not only of the filter according to the EN 1886 Standard Technical considerations about the second goal

  21. Third goal Elimination of the batteriological contamination from the surrounding environments The batteriological contamination coming from the surrounding environments is eliminated by mantaining the room is overpressure respect to them.

  22. Third goal Elimination of the batteriological contamination from the surrounding environments To mantain an environment in over/underpressure in respect to a reference one it is sufficient to extract more or less air than the one supplyed in.

  23. Third goal Elimination of the batteriological contamination from the surrounding environments The opposite is true in case of septic or dirty operations; the surgical room must be mantained in depression so not to pollute the surrounding environements.

  24. A differential pressure pressostat mounted between the surgical room and the clean corridor informs the microprocessor of the situation of over/underpressure in the room. The microprocessor then confronts this with the desired situation and acts on the exaust fan inverter raising or reducing the quantity of the expelled air from the environment. Technical considerations about the third goal

  25. Mounting within the room

  26. Fourth goal Reduction of the batteriological pollution due to the surgical team or to the patient himself The endogenous batteriological pollution from the patient or from the surgical team is eliminated by filtering with absolute filters as frequently as possible the treated air.

  27. How is it done? With treatment sections that guaranty the high quantity of fresh air throught thermodynamic components both for the control of humidity and temperature with modulating capacity control. Even in the case of direct expansion units the frigorific capacity is modulated by an electronic injection of hot gas. Fifth goal Guaranty a good level of control of temperature and humidity

  28. How is it done? Sixth goal Guaranty the maximum energy saving Raising as much as possible the recirculation: obviously in respect to the local Standard

  29. How is it done? Night Stand-by of the units, activable from the presence feelers, BMS, hour timetables or manualy: Sixth goal Guaranty the maximum energy saving 1: Reducion of the capacity by 1/3 of theal fffffffnominal one, external one 2: Mantaining the overpressure 3: Raising the dead range from 0,3 ° to 10 °

  30. How is it done? In case of no recirculation: Local Standards or septic environemnts to be mantained in depression a heat recovery system must be foreseen. Sixth goal Guaranty the maximum energy saving

  31. CHILLED WATER SURGICAL ROOM AIR CONDITIONER WITH HEAT RECOVERY SYSTEM MODEL OHU 208 AIR FLOW: 6.900 m3/h

  32. DIF-O.T. CEILING FILTRATION SYSTEM

  33. DIF-O.T. CEILING FILTRATION SYSTEM