An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. First look at Gas Systems (preliminary)

  2. Content • RICH Gas System • STRAW Tracker Gas System • CEDAR

  3. RICH Gas System Assumed Requirements • Detector Volume: ~200m3 • Gas: 100% Neon (CO2, Air <1%. H2O < 1000 ppm) • Cost of one Fill ~ 27 kCHF • Operating Pressure: 1000 mbar (at constant density) • Max. over/under pressure (rel. to Atmosphere) +100 mbar and – 0 mbar (no vacuum pumping possible) • Operating Stability (2 options): • Closed gas volume (no gas replacement) • Regulate constant density [Pset = ro/MNe*R*(273.2+T)]

  4. A: during operation replenishing • of gas only (no recirculation) • B: during operation gas circulation • and O2 and H2O filtering RICH Gas System

  5. Straw Tracker Gas System Assumed Requirements • Detector Volume: 1.2 m3 • 4 Stations with 1’792 Straws/Station • Gas: CO2 / iC4H10 / CF4 (CF4 ≤10% and iC4H10 ~5%, mix non-flammable ) • Gas Flow: 0.16 cm3/min per Straw (68.8 l/h for full detector = 1 gas volume change in 16 hours) ( expected gas leak is ~1% of inlet flow) • Operating Pressure: ( 2 options) • Patm + 2 mbar • 1000 mbar absolute • Operating Mode (2 possibilities): • Single pass system (baseline) • Closed loop gas system ( to be considered only if gas flows increase)

  6. STRAW Tracker Distribution System • 1 Rack per station • Each Rack has 8 gas channels equipped with remote shut-off valves and • in/out flow metering (1 channel supplies 1 half view) • Each Channel supplies 14 sub-channels equipped with manual valves Pressure regulation

  7. STRAW Tracker Full System single pass system Mixing zone will be a flammable gas zone

  8. CEDAR Gas System Assumed Requirements • Detector Volume: ~1.1 m3 • Gas: 100% H2 (flammable gas) • Operating Pressure: 3.5 bara • Operating Stability (2 options): • Closed gas volume (no gas replacement) • Regulate constant Density [Pset = ro/MNe*R*(273.2+T)]

  9. CEDAR Gas System