Solar. OEM Boiler & Burner Equipment. RVS - Solar Functions. Delta-T functions with…. Swimming pool. Buffer storage tank. DHW. RVS - Solar Functions. Delta-T function. Q5 on: Temp B6 > Temp B31/B41 + SdOn. Q5 off: Temp B6 < Temp B31/B41 + SdOff. RVS - Solar Functions.
E N D
Solar OEM Boiler & Burner Equipment
RVS - Solar Functions Delta-T functions with… Swimming pool Buffer storage tank DHW
RVS - Solar Functions Delta-T function Q5 on: Temp B6 > Temp B31/B41 + SdOn Q5 off: Temp B6 < Temp B31/B41 + SdOff
RVS - Solar Functions Minimum charging temperature collector Q5 off: TKol < TKolMin. Q5 on: TKol > TKolMin + (SdOn – SdOff)
RVS - Solar Functions Frost protection collector Q5 on: TKol < TKolFrost. Q5 off: TKol > TKolFrost + 1K
RVS - Solar Functions Charging temperature maximum tank Q5 off: TSp > TSpMax. Q5 on: TSp < TSpMax - 1K
RVS - Solar Functions Overtemperature protection collector Q5 on: TKol > TKolUe and TSp < TSpSMax. Q5 off: TKol < TKolUe – SdUe or TSp > TSpSi
RVS - Solar Functions Tank recooling function with collector pump Q5 on: TSp > TRKw + 2K and TSp > TKol + SdEin Q5 off: TKol > TSp – 2K or TSp < TRKw +1K
RVS - Solar Functions Solar pump protection - flow medium evaporation Q5 off: TKol > TVerd Q5 on: TKol < TVerd – SdVerd
RVS - Solar Functions Temperature scale solar functions Flow medium evaporator protection (e.g. 130 °C) TVerd Collector overtemperature protection (e.g. 100 °C) TKolUe DHW/buffer storage tank maximum temperature (90 °C) TSPSi TSpMax Charging temperature maximum (80 °C) TRKw Recooling temperature (60 °C) Minimum charging temperature (e.g. 20 °C) TKolMin TKolFrost Frost protection collector (e.g. 0 °C)
RVS - Solar Functions Minimum pump Q5 running time Hours run counter Counter for running time of pump Q5 resettable
RVS - Solar Functions Pump kick function To prevent damage to pump Q5, the pump is activated for 30 s every Friday morning at 10:00 Solar start functions This functions is required if sensor B6 is improperly located Between 07:00 and 21:00, pump Q5 is activated every x minutes (adjustable) for a minimum period of time. If there is sufficient solar energy, pump Q5 keeps running.
RVS - Solar Functions 3 exchanger 2 exchanger
RVS - Solar Functions Applications with 2 collector fields
RVS - Solar Functions Priority DHW/Buffer storage tank, Priority swimming pool • Charging priority tank • No priority -> buffer and DHW tank are charged alternately on 5°C steps • Absolute priority -> buffer, DHW tank and swimming pool are charged to • nominal setpoint following the programmed sequence • Relative priority -> waiting time and charging time for relative priority must • be set. Parallel or alternative mode Schematics with pumps
RVS - Solar Functions Auxiliary functions • Modulating solar pump via 0…10V output • Solar sensor for yield • measurement • External heat exchanger for solar • The switch on of pump K9 is delayed