1 / 20

Module 1

Module 1. Basic Terminologies and Characteristics of Switchgear. The low voltage switchboard. A vital link for electrical distribution. To satisfy the increasing needs of safety of people and equipment and availability of electrical power : its realization is not improvised…. Safety.

amina
Download Presentation

Module 1

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Module 1 Basic Terminologies and Characteristics of Switchgear

  2. The low voltage switchboard A vital link forelectricaldistribution • To satisfy the increasing needs of safety of people and equipment and availability of electrical power : its realization is not improvised… Safety Availability Reliability Maintenability • and to provide a continual balance between: • the needs of safety and availability • and the constraints of reliability and maintenability of installation. Contents Definitions

  3. Basic Terminologies Switchgear Assembly A combination of one or more low voltage switching devices together with Control, Measuring, Signalling, Protective equipment etc., completely assembled under the Responsibility of manufacturer with all internal electrical and mechanical inter-connections and structural parts. Role of Switchgear Electrical Protection Safe Isolation from live parts Local or remote switching

  4. Basic Terminologies Safety Reliability Availability Maintenability

  5. Basic Terminologies

  6. Basic Terminologies Type Tested L.V. Switchgear & Controlgear Assembly (TTA) Assembly conforming to an established type or system without deviations likely to significantly influence the performance from the typical Assembly verified to be in accordance with the standard (IEC 60947) Partially Type Tested Assembly Assembly containing both Type Tested and Non type tested arrangements provided that the latter are derived (ex: by calculation) from the Type Tested arrangements. Dead Front Assembly An assembly with a front covering which provides a degree of protection of at least IP2X from the front. However, live parts may be accessible From other directions.

  7. Basic Terminologies Enclosed Assembly An Assembly which is enclosed on all sides with the possible exception of its Mounting surface in such a manner as to provide a degree of protection of at least IP 2X. Cubicle type Assembly An enclosed Assembly of Floor standing type, which may comprise several sections, sub-sections or compartments. Spare Spaces Free space :An empty space of a section. Unequipped space :A part of a section incorporating busbars only. Partially equipped space :A part of a section fully equipped except for functional units. The functional units which can be installed are defined in number of modules and size. Fully equipped space :A part of a section fully equipped with functional units not assigned to a specific use.

  8. Basic Terminologies Insulation co-ordination Clearance : The distance between two conductive parts along a string stretched shortest way between these conductive parts. Creepage distance : Shortest distance along the surface of an insulating material between two conductive parts. - Defines the withstand to surface dielectric ageing; - Defines surge withstand (lightning impulse, switching surge, over voltage at power frequency.

  9. Basic Terminologies Altitude

  10. Basic Terminologies Rated Voltages: Rated Operational Voltage (Ue) : Value of Voltage, which combined with rated current of the circuit, determines its application. Rated Insulation Voltage (Ui) : Voltage value to which dielectric test voltages and creepage distances are referred. Rated Impulse withstand voltage (Uimp): Peak value of Impulse voltage of prescribed form & polarity the Assembly is capable of withstanding without failure under specified conditions & clearances referred.

  11. Basic Terminologies Rated Current (In) : Stated by Manufacturer taking into account ratings of components in Assembly, their disposition & application. Rated short time current (Icw) : Assigned by manufacturer which Assembly can withstand without damage under test conditions. Unless stated by manufacturer, the time is 1 sec. Rated Peak withstand current (Ipk) : Assigned by manufacturer which Assembly can withstand satisfactorily under test conditions. Rated Conditional Short circuit current (Icc) : Value of Short circuit prospective current, stated by Manufacturer, with that circuit, protected by a short circuit protective device specified by Manufacturer, can withstand satisfactorily for operating time of the device, under test conditions.

  12. Basic Terminologies

  13. Basic Terminologies Prospective Short circuit current (Icp) :A current which flows when the supply conductors to the circuit are short circuited by a conductor of negligible impedance located as near as possible to the supply terminals of the assembly. Cut-off current ; let through current :The maximum instantaneous value of current attained during the breaking operation of a switching device or fuse.

  14. Basic Terminologies Relationship between Ipk & Icw :

  15. Basic Terminologies Conventional free air thermal current (Ith) : The maximum value of test current to be used for temperature-rise tests of Unenclosed equipment in free air. Conventional enclosed thermal current (Ithe): The value of current stated by manufacturer to be used for temperature-rise tests Of the equipment when mounted in a specified enclosure. The above values of ratings shall be at least equal to the maximum value of The rated operational current in eight-hour duty.

  16. Basic Terminologies Rated diversity factor : It is the ratio of maximum sum, at any one time, of the assumed currents of all the main circuits involved, to the sum of the rated currents of all the main circuits of Assembly.

  17. Basic Terminologies IEC: International Electro technical Commission NEC : National Electric Code (counterpart to NFC15-100) Defines a number of general practical rules to ensure the safety of life and property. Defines cables, protection, installation, earthing etc. ANSI: American National Standards Institute (counterpart to UTE) Follows the recommendations of the IEEE (Institute of Electrical and Electronic Engineers) NEMA: National Electrical Manufacturers Association UL: counterpart to Bureau Veritas Independent organization.- Founded by insurance companies. Certifies conformity to NEC &ANSI. Covered only small commercial & Residential {panel boards,MCCBs & load centers}. Its influence has spread to switchboards and even to MV

  18. Basic Terminologies Temperature Class:

  19. Basic Terminologies

  20. Basic Terminologies