200 likes | 364 Views
Engineered Solutions for Engineered Buildings. Pressure independend control valves. Dynamic balancing. „Cocon Q “ P ressure i ndependent d ynamic c ontrol v alve. Main features: Combination of automatic regulator and regulating valve Constant, high valve authority
E N D
Engineered Solutions for Engineered Buildings Pressure independend control valves Dynamic balancing
„Cocon Q “ Pressure independentdynamiccontrolvalve
Main features: • Combination of automatic regulator and regulating valve • Constant, high valve authority • Adjustment / Control of the presetting with mounted actuator possible • Direct reading of presetting in l/h or m³/h • Good optical display of the presetting • Presetting is lead lockable • Pump setting optimization • Small dimensions, especially “Cocon QTZ” • Complete flow and size range • Multiple control options • For chilled ceiling, fan coil unit, air handling unit, convector, one-pipe-system, surface heating and cooling etc. „Cocon Q“ Valve for hydronic balancing and regulation of heating and cooling systems
Combination of automatic regulator and regulating valve Legend 1. Diaphragm unit 2. Control valve 3. Balancing valve 4. Handwheel 5. Diaphragm 6. Sleeve “p1” is the inlet and “p3” the outlet pressure of the valve. “p2” is the pressure actuating the diaphragm unit and maintaining the differential pressure “p2” – “p3” at a constant level.
Flow rate [0 – 100%] Differential pressure [bar] Linear valve characteristic when used with proportional actuators Valve stroke [%] Flow rate [0-100%] Combination of automatic regulator and regulating valve 1. Limit the flow rate with the handwheel • 2. Control the flow rate with the actuator • 2-point control • 3-point control • Proportional control (0-10V)
Valve Authority P1 Valve Authority, a = P1 + P2 Ideal is a valve authority of a = 1
Therefore, the valve authority of the regulating valve „Cocon Q“ amount to 100% (a = 1) Constant and high valve authority “Cocon Q” • „p2 – p3“ is kept constant, • even where high differential pressure variations („p1“ – „p3“) occur during part load conditions
Adjustment / Control of the presettingwith mounted actuator possible
„Cocon QTR“ and „Cocon „QFC“ „Cocon QTZ“ Direct reading of presetting in l/h or m³/h
Good optical display of the presettingof the “Cocon QTZ” in different installation positions
Check the min. differential pressure in the manual,depending on the presetting • Check the differential pressure of the “Cocon Q” with the “OV-DMC2” Save Energy due to optimum setting! Pump setting optimizatione.g. for the Cocon QTZ • Adjust the pump setting. Thus the last “Cocon QTZ” hasa bit more (e.g. 5%) than the min. differential pressure.
Less space required to install the „Cocon QTZ“ with actuator Small dimensions, especially “Cocon QTZ”
Flow and size range Q = Flow T = Thread Z = dezincification resistant brass Q = Flow T = Thread R = Bronze
Flow and size range Q = Flow F = Flange C = Cast iron
Actuator Actuator Actuator Current Current Current Control Control Control 2-Point 2-Point 2-Point 3-Point 3-Point 3-Point Proportional Proportional Proportional Electro- thermal Electro- thermal Electro- thermal 24 V 24 V 24 V 1012816/26 1012816/26 1012816/26 1012951 (0-10V) 1012951 (0-10V) 1012951 (0-10V) 230 V 230 V 230 V 1012815/25 1012815/25 1012815/25 Electro- motive Electro- motive Electro- motive 24 V 24 V 24 V 1012701 1012701 1012701 1012700 (0-10V) 1012700 (0-10V) 1012700 (0-10V) 230 V 230 V 230 V 1012710 1012710 1012710 1012703 1012703 1012703 EIB EIB EIB 1156065/66 1156065/66 1156065/66 LON LON LON 1157065 1157065 1157065 “Cocon QTZ” Control options
electromotive actuators for “Cocon QTR” (DN40+50) 24V supply voltage 0-10V control voltage or 2-point or 3-point control 8 mm piston stroke characteristic lines: linear, equal percentage or quadratic adjustable installation position: vertical upright up to horizontal, not overhead Item-No. 115 80 10 Cocon QTR
electromotive actuators for “Cocon QFC/QTR” (DN40-150) 24V supply voltage 0-10V or 4-20 mA control voltage or 2-point or 3-point control up to 40 mm piston stroke characteristic lines: linear, equal percentage or quadratic adjustable installation position: vertical upright up to horizontal, not overhead Electromotive actuator Squeeze connection 24 V 115 80 30 24 V, with spring return 115 80 31 Cocon QTR / QFC