1 / 6

Electric network faults seen by a wind farm – analysis of measurement data

Electric network faults seen by a wind farm – analysis of measurement data. Sanna Uski, Seppo Hänninen, Bettina Lemström. 5x600 kW. Measurements - 2,5 sec 500 Hz - 0,33 sec 3,7 kHz - triggered by U0. Ur, Us, Ut Ir, Is, It. Ur, Us, Ut Ir, Is, It, U0 Ir, Is, It, U0. Measurement site.

armine
Download Presentation

Electric network faults seen by a wind farm – analysis of measurement data

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Electric network faults seen by a wind farm – analysis of measurement data Sanna Uski, Seppo Hänninen, Bettina Lemström

  2. 5x600 kW Measurements - 2,5 sec 500 Hz - 0,33 sec 3,7 kHz - triggered by U0 Ur, Us, Ut Ir, Is, It Ur, Us, Ut Ir, Is, It, U0 Ir, Is, It, U0 Measurement site x Olos • Measurement at Olos wind farm on 21 kV level • 5 x 600 kW fixed speed wind turbines • Turbines equipped with • squirrel cage induction generator • capacitor bank • Dyn step-up transformer • Connected to relatively weak 21 kV grid (Sk~50MVA) • 21 kV grid reactance grounded Helsinki

  3. Voltage dip distribution • Voltage dips detected in 196 cases out of 260 • Several dips involved in one incident, 5.4 dips in average (max 36) • Multiple types of faults, 3 phase, single phase etc. No. of dips Dip duration Residual voltage

  4. Voltage dip examples;Two phase fault Autoextinguished earth fault • Autoextinguished earth fault • Caused by thunder • Three voltage dips • 28…34 ms, Ures 0.44, 0.74 and 0.85 pu • Two phase short-circuit • Triggered at fault clearing  caused a change in neutral voltage • Residual voltage 0.6 pu • Duration of the dip 258 ms

  5. Varying faults • Most of the faults are varying • fault resistance • fault type • Example case; • starts with two phase short circuit • changes to two phase-to-ground fault • and to a three phase short circuit • fault cleared, earth capasitance discharge causes multiple short voltage dips • Available in Annex database

More Related