1 / 19

Tecomat Foxtrot & INELS

Tecomat Foxtrot & INELS. Description, Components, Applications. Suite of HW products Tecomat Foxtrot. Important features: • High performance • Modularity • Installation module „circuit-breaker” design • Two-wire „free” I/O topology • Connectivity of CIB components

Download Presentation

Tecomat Foxtrot & INELS

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Tecomat Foxtrot & INELS Description, Components, Applications

  2. Suite of HW productsTecomat Foxtrot Important features: • High performance • Modularity • Installation module „circuit-breaker”design • Two-wire „free” I/O topology • Connectivity of CIB components • Number of I/O up to 134 + I/O CIB elements • Ethernet, Web server • On-line programming • SW backup • OPC server • Slot for MMC card for secondarymemory • MODBUS, PROFIBUS DP, CAN Tecomat Foxtrot – small powerful modular PLC system for a wide range of small-size to medium-size applications in industry and building. Inels – intelligent electrical system for building applications using CIB bus.

  3. Tecomat Foxtrot – description

  4. Tecomat Foxtrot – modules

  5. Tecomat Foxtrot – communication Ethernet

  6. Tecomat Foxtrot – Communication modes Channel CH1 • Mode PC - communication with superior systems through the EPSNET protocol • Mode PLC - data sharing among PLCs in the EPSNET-F network • Mode UNI - common channel with arbitrary asynchronous communication • Mode MPC - data exchange with subordinated PLCs in the EPSNET multimaster network • Mode MDB - communication with superior systems through the MODBUS protocol • Mode PFB - master for the connection of stations PROFIBUS DP slave Channel CH2 • Mode PC - communication with superior systems through the EPSNET protocol • Mode PLC - data sharing among PLCs in the EPSNET-F network • Mode UNI - common channel with arbitrary asynchronous communication • Mode MPC - data exchange with subordinated PLCs in the EPSNET multimaster network • Mode MDB - communication with superior systems through the MODBUS protocol • Mode PFB - master for the connection of stations PROFIBUS DP slave • Mode UPD - operation of special submodules • Mode DPS - realization of station PROFIBUS DP slave • Mode CAN - connection of stations on the CANopen bus • Mode CAS - realization of station CANopen • Mode CAB - connection of the CAN bus • Mode CSJ -connection of CAN interface with SJA1000 driver Ethernet ETH1 • Mode PC - communication with superior systems through the EPSNET UDP protocol in TCP/IP networks • Mode PLC - data sharing among the PLCs in the TCP/IP network

  7. Tecomat Foxtrot – controlling with I/O Energy monitoring Direct controlling energy sources and consumption (IRC systems] Process optimization. All standard PLC functions, fast inputs for counters, incremental position encoders, measurement of pulse length, period and phase shift.

  8. What is an intelligent electro installation system? System of sensors and actuators which are situated on one bus and connected to control system. They work as remote I/O.

  9. FOXTROT = communication + I/O Communication part – at the left part Ethernet 10/100 (RJ45) CH1-RS232 UART up to 340kbit/s CH2 – optional for 1 submodule RS232 - MR0104 RS482 RS422 1xCAN 2xCAN Profibus DP slave …LON atd. Expansion by peripherals I/O modules - Bus TCL2 Expansion INELS - Installation elements Power supplying 24V/DC 24V DC INELS RS232 TCL2 Ethernet10/100baseTX UTP Optional interface/for submodule MR

  10. FOXTROT = communication + I/O CP-1004 Basic I/O – at the right INPUTS - basic functions 8x DI 24V DC (DI0-DI7) INPUTS - alternative functions DI4-DI7 = analog AI0-AI3 0-10V 10bit, bez GO DI0-DI3 = special functions FI0-FI3 Fast counter, Incremental sensor OUTPUTS 6x DO/RO, Switching /NO/ contact relay 230V AC/3A Optical indication FI0..FI3 AI0…AI3 DI0……………..….DI7 RO0………………RO5

  11. FOXTROT = basic types of I/O 4DI/FI 0DI 4DI/FI 12DI 0DI 0AI 0AI 8AI 0AI 4DI/AI FI0..FI3 AI0…AI3 SPI0..SPI3 FI0..FI3 DI0……………..….DI7 DI0….DI3 DI0….DI3 DO0..DO3 A00…A01 Vref 3M 3M 6M 3M 3M 12DO 0RO 6RO 8RO 0RO 0AO 2AO 0AO 0AO 0AO RO0………………RO5 DI4……………..….DI11 RO0………………RO7 AI0……………..AI7 DO4……………DO11 0S -1401 IR -1501 IB -1301 CP -1004 IT -1601

  12. FOXTROT – modularity, connection 24V DC • Module address0-9 • System bus • 345kbit/s • BUS/RS485 • 200-300m • Terminator is required • Basic module has to be at the left • Power supplying 24VDC Up to 300m

  13. Bus installation units for the CIB bus • Individual work with remote I/O • Free topology – two wires • Mosaic libraries of function blocks for simple building installations • heating (air conditioning, ventilation), • illumination (dimming, time functions), • electronic alarm system functions • dim-out control, • … • For sophisticated technological applications in the field of building, source and heat distribution control.

  14. FOXTROT is expandable by CIB elements 24V DC • CIB • Data + Power supplying • 2 wires • Free topology • 24V DC • 32 units • CIB MASTER • Next 2 buses • 2x32 units • CIB is suitable for building IRC(Individual room control) • Lighting • Heating • Air-conditioning • Alarm system • … CIB 230V AC

  15. FOXTROT – Expansion of CIB buses CIB-2 CIB-6 CIB-3 CIB-7 Power 230V AC/ 27.2V DC CIB-4 CIB-8 CIB-5 CIB-9 CIB -1 9 x 32units = 288 units 288 x 14DI = 4032 DI = max.

  16. CIB works with safety voltage SELV Power 230V AC/ 27.2V DC 230V AC 24V DC SELV CIB -1 4 kV 4 kV

  17. Building Management System TECOMAT FOXTROT + CIB/INELS For control panels Roominstallation Interier components Acces control Security Fire signalization INTEGRATION DIRECT CONTROL Ethernet RS485 IntelligentInstallation Electricity supply DDC/PLC CCTVVideo Cooling DDC/PLC Heating DDC/PLC

  18. Web server & client, File server • Embedded web server • It uses XML, which is more structured than HTML and doesn't spend the capacity of CPU. • Foxtrot uses file system on Flash disc, internal or on MMC/SD card • Limitation is only the size of MMC/SD card

  19. CIB Units - overview Voice Light Infra Button Infra