FLUSARC 24kV

FLUSARC 24kV. 24 kV GIS Switchgear for Secondary Distribution. Main Data. 12 - 24kV SF 6 insulated switchgear Compact, extensible or modular Indoor or Outdoor With either fuse combination or circuit breaker for transformer protection Electric data:. Main Features Installation.

barney
Download Presentation

FLUSARC 24kV

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. FLUSARC 24kV 24 kV GIS Switchgear for Secondary Distribution

  2. Main Data • 12 - 24kV SF6 insulated switchgear • Compact, extensible or modular • Indoor or Outdoor • With either fuse combination or circuit breaker for transformer protection • Electric data:

  3. Main Features Installation • Easy installation • Can reach installation site already pre-assembled • No need for specialized civil works • Fast cable connection due to standardized bushing + coupling MV cable terminals • Reduced dimensions • (CCT1, 2 disconnecting switch & 1 disconnecting switch+fuses) • Width 1065mm • Height 1665mm • Depth 825mm • Also available in 1290mm height • SF6 compartment is the same • Smaller footprintand cable compartment

  4. Main FeaturesMaintenance • Cable testing • Easy cable testing thanks to standardized bushings • Cable testing can be done without interruption of service Terminal cover Capacitive insulator Test kit rod Adapter terminal

  5. Main FeaturesMaintenance • Maintenance-free SF6 compartment • Sealed for life • No adjustement or filling with gas during the whole life • SF6 pressure gauge+ warning and alarm contacts available

  6. Main FeaturesOperation • Several versions available: • Indoor or outdoor • Modular, extensible or compact • Regular or reduced height • Suitable for very harsh & polluted environments • Operates in severe conditions: • Several installations already in Saudi Arabia • Several installations already in Finland Flusarc 24 outdoor version

  7. Main FeaturesOperation • Reliable working of the operating devices • Field-proven experience with thousand of installations over 15 years • All the operations are carried out from the front • Mechanical signals show the position of the various switching components • Correct sequence instructions is showed on switchgear front

  8. Main FeaturesOperation • Also Type tested under water • Proved to be highly reliable • Maximum service continuity • Remote operation possible

  9. Main FeaturesMaximum service continuity • Insulation of all the live parts with SF6 gas • Simple and reliable system thanks to the low pressure gas ensuring maintenance-free operation for 30 years • Suitable for applications in polluted or high humidity areas • Flusarc not affected by external ambient conditions • Flusarc can operate completely immersed in the water for a defined period (24 h)

  10. Main featuresPersonnel safety • Direct earthing of the whole switchgear structure • Total segregation of live parts located in a completely sealed SF6 stainless steel metal housing • Access to fuses without any danger with earthing at both sides • Mechanical interlocks ensure correct sequence of operations • Security and simplicity of locking devices • Internal arc proof in the tank • On request also in cable compartment • CESI type tests certification

  11. Main featuresPersonnel safety • SF6 prevents fires from spreading • Overpressure valves are placed under the switchgear: • allows the hot exhaust gas escape into cable conduit • eliminates any risk for the operator Overpressure valves

  12. Applications • Compact secondary substations • Light industries • Hotels, shopping centres, office buildings, business centres etc. • Airports, hospitals, tunnels, light mining applications and railways • Utilities (e.g. Iberdrola, ENEL, Endesa, EDP, Fortum, SEC)

  13. Circuit Breaker Function • Characteristics: • 24kV 630A • Short-time current: 16kA 1s • Option of two different relay types for CB (Self powered and Auxiliary powered) • Manual and motorized versions • Several versions available • Outdoor • Extensible • Reduced height

  14. Circuit Breaker Function • Vacuum CB with 3 positions disconnector in series Connected Disconnected Earthed

  15. Vacuum interruption technology guarantees high performance and reliability 30 years without maintenance Circuit breaker placed inside SF6 compartment Reduced dimension Disconnecting switch placed inside SF6 compartment Reduced dimension High reliability, same mechanism for disconnecting switch and earthing switch Circuit Breaker Function

  16. CCCC CCCC CC CCC C Flusarc 24 configurations,Block version I NB: Also versions with reduced basement height 400 mm are available

  17. T1CC T1CC T1CCC T1CCCC Flusarc 24 configurations,Block version II

  18. T1T1CC T1T1CCC Flusarc 24 configurations,Block version III

  19. CBCC CBCCC CBCBCCC CBCCCC CBCBCC Flusarc CB 24 CBC

  20. Flusarc 24 Modular Version

  21. Inner View

  22. FLUSARC 24 is fully type tested

  23. FLUSARC 24 is fully type tested

  24. CUSTOMERCOUNTRY ENEL ITALY ACEA ITALY AEM ITALY SELMA / ENDESA SPAIN FASYMON / IBERDROLA SPAIN ELCONTROL BULGARIA TECHNICAL UNIVERSITY-SOFIA BULGARIA BEIJING POWER UTILITY CHINA ZHUHDI POWER UTILITY CHINA ELKAMO FINLAND NOAVARAN BARQARIA IRAN TENAGA NATIONAL BERHAD MALAYSIAPower Utility LME (EDP Power Utility) PORTUGAL TIEPCO (SEC Power Utility) SAUDI ARABIA ARKO S.R.O. SLOVENSKA INTERSWITCH PTY LTD SOUTH AFRICA CRYSTAL CONSULTING & ENG. SWITZERLAND STATIONENBAU AG SWITZERLAND GIRISIM ELEKTRIC D.S. TURKEY(Tedas Power Utility) BINH SON ELECTRIC CO.LTD VIETNAM ONE CO.LTD VIETNAM MAIN REFERENCES