Ivo Pinkiewicz, IENOT, POLANDDISTRIBUTION TRANSFORMER POPULATION and EFFICIENCY LEVELS IN POLAND
DISTRIBUTION OF • RATED POWER • YEAR OF MANUFACTURING • LOSSES
RATED POWERDISTRIBUTION OF RATED POWER IN ONE OF UTILITIES IN POLAND
RATED POWER DISTRIBUTIONOF TRANSFORMERS IN SEVERAL UTILITIES IN POLAND
MANUFACTURING YEAR DISTRIBUTIONOF 160 kVA TRANSFORMERS IN ONE OF UTILITIES IN POLAND
MANUFACTURING YEAR DISTRIBUTIONOF 400 kVA TRANSFORMERS IN ONE OF UTILITIES IN POLAND
Units with age above 25, 30 and 35 years in groups of transformer rated 160, 250 and 400 kVA.
LOSSES DISTRIBUTIONRELATION OF LOSSES IN TRANSFORMERS RATED 160 kVA IN ONE OF UTILITIES IN POLAND
LOSSES DISTRIBUTIONRELATION OF LOSSES IN TRANSFORMERS RATED 400 kVA IN ONE OF UTILITIES IN POLAND
LOSSES DISTRIBUTIONNO LOAD and LOAD LOSSES OF 160 kVA TRANSFORMERS IN ONE OF UTILITIES IN POLAND
LOSSES DISTRIBUTIONNO LOAD and LOAD LOSSES OF 400 kVA TRANSFORMERS IN ONE OF UTILITIES IN POLAND
EFFICIENCY LEVELSDATA NECESSARY TO ESTIMATE EFFICIENCY LEVEL: • Rated value of no load and load losses • Yearly Load profiles specified by: • Yearly peak load • Running time • Loss time
EFFICIENCYCOMMON VALUES OF LOAD PROFILE COOFFICIENTS IN POLAND • Yearly peak load...............0,30....0,35 • Running time..................3500....4560 h • Loss time........................2100....3100 h
EFFICIENCYIMPROVEMENT EFFICIENCY THROUGH REPLACEMENT THE OLD TRANSFORMER 100 kVA by C-C' TRANSFORMER
EFFICIENCYYEARLY ENERGY SAVING THROUGH REPLACEMENT THE OLD TRANSFORMER 100 kVA by C-C' TRANSFORMER
EFFICIENCYCOMPARISON TYPICAL LOAD PROFILES AVERAGE LOADED TRANSFORMER 100 kVA IN WEST EUROPE AND POLAND
Energy savings and efficiency improvement in Polish Utilitieswhen existing population is replaced by C-C’ Transformers