1 / 18

Wireless Remote Monitoring and Control DistribuTECH 2002 March 1, 2002

Wireless Remote Monitoring and Control DistribuTECH 2002 March 1, 2002 by Carl R. Goeckeler, P.E. 1997 DA/DSM “Best Utility Project” Innovation Award, KCP&L KCP&L Service Territory 2000 System Peak 3,374 MW 91% Metro Load Customer Retail Base 409,536 Residential 51,415 Commercial

benjamin
Download Presentation

Wireless Remote Monitoring and Control DistribuTECH 2002 March 1, 2002

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Wireless Remote Monitoring and ControlDistribuTECH 2002March 1, 2002 by Carl R. Goeckeler, P.E. 1997 DA/DSM “Best Utility Project” Innovation Award, KCP&L

  2. KCP&L Service Territory 2000 System Peak • 3,374 MW • 91% Metro Load Customer Retail Base • 409,536 Residential • 51,415 Commercial • 2,367 Industrial • 119 Other

  3. Communications - Wish List • Two-Way • Secure • Use Public Infrastructure/Leverage Available Systems • Broad Coverage • Broad Bandwidth • Low Cost Data Charge • Low-Cost Radio Deployment • Reliable System • RTU Growth Easy and Convenient/Scaleable • Supports Multiple Protocols/Flexible

  4. LiveData Software on Typical PC Utility WAN using Ethernet or TCP/IP Capacitor Control KCP&L D.A. ArchitectureLinks SCADA to Corporate LAN Operator Switch Consoles Control Schlumberger/Sema Communications Other DA Field Equipment (reclosers, regulators, etc.) Planning Engineer Workstations LiveData Serversrunning WinMon S/W (PC-based, with WinMon®) Capacitor Control Switch Control Schlumberger/Sema Advanced Communications Applications LiveData Software Other DA On Typical PC Field Equipment (reclosers, regulators, etc.) UTILITY LAN (UCA over TCP/IP)

  5. KCP&L Fixed Network System • Advantages for User • Full Two-Way Capability for D.A. • No Communications Layout Design • No Radio or Communications System Maintenance • No Capital Outlay for System • Disadvantages for User • Not in “Control” of Communications • Dependent upon Protocol by Provider • Dependent upon Performance/Availability by Provider • Public Communications Systems Not Leveraged • Recurring Lease Charges • Capacitor Automation Lower Priority than Meter Reading

  6. D.A. Features Supported by Two-Way Communications Features Supported: • Present Alarms and Analogs • Remote Control Operation • Read and Change Setpoints • Launch Global Commands • Access to Diagnostics • Historical Analog Profiles • Reports • On-Line Graphing • Download Electronic Files

  7. Graphing Data On Line

  8. Use of Global Command to Change Setpoints / Force Capacitors On Line July 27, 1999, Early Morning: • Needed All Banks On • Query - 168 Banks Off Line • Global Command Issued • All Available Banks On Line • 99.99% Leading Power Factor • Proactive Voltage/VAr Support

  9. KCP&L Fixed Network – Lessons Learned • Two-Way Communications is Important • Verify Switching • Setpoint Changes and Verification • Supplies Data for Distribution Engineering Analysis • Look for Ways to Leverage Available Communication • SchlumbergerSema for AMR • Public Communications Systems • Metropolitan Coverage has Been Good • Rural Areas - Not Cost Justified • Adequate for Capacitor Automation • Communication Performance Generally Acceptable

  10. KCP&L Need for Rural Coverage • Expansive Area/Travel Time an Issue • 48 Substations (34 – 12 kV) with No Automation • No Automated Outage System in Place • Volt/VAr Support Needs Improvement • Voltage Rise from Capacitors Significant • Voltage Regulators • Reclosers • Line Monitors/Fault Detectors • Few Economical Communication Solutions

  11. How Telemetric Works

  12. KCP&L/Telemetric DNP Project • Develop Remote Telemetry Module (DNP-RTMTM) • Configurable for All DNP RTUs/IEDs • Supports Local Rule-Based Criteria • RTUs/IEDs - Now Electronic and “Radio Ready” • Integration Plans • Now - Capacitors, Regulators, Load Tap Changers, Switches • Future - Reclosers, Fault Indicators, Line Monitors • Develop DNP- XchangeTM • Delivers DNP to Utility • Integration into WinMon® • Integration into EMS/CADs

  13. Remote Telemetry Module (RTM) • Connects to DNP Speaking RTUs/IEDs • Near Real-Time • Works with various DNP-based Devices • Local Configurable Program • User Specifies Up to 99 Data Points • Rule Based Algorithm • Can Receive Up to 500 Commands • Polls Connected RTUs/IEDs • Data Transmitted - Report By Exception • Supports Queries • Supports Time-Scheduled Call Reports • May View Data on Secure Web Page • Can Also Tunnel to Utility EMS Terminal Serial Connection (DNP 3.0 Protocol) Field RTU Remote Telemetry Module DNP Rule Radio Master Engine I/F

  14. DNP X-changeTM Features • Connects Telemetric NOC to Utility • Functions as DNP Slave to SCADA System • All DNP Packets Include • Utility ID Number • Unit ID Number • Data Point Number • Two Reporting Models • Report By Exception • Polling SSL Connection DNP-Xchange™ Telemetric NOC Telemetric Micro RTU or DNP-RTM™ Cellular Data Network SCADA System TCP/IP DNP

  15. Distribution Capacitor Neutral Current Detection Detects and Alarms for: • Blown Fuse • Failed Capacitor Switch • Failed Capacitor Unit • Damaged Control Cable Wiring • High Harmonic Current

  16. The Need to Monitor Fixed Banks Year 2000 – Fixed-Bank Capacitor Patrol Results • 400 Capacitor Banks Patrolled • 16% Capacitor Banks with “As Found” Problems • 26.1 MVAr Out of Service (8.3% of Fixed Capacity) • Additional 2% Banks with Switching Problems • Higher Percentage of Problems in Non-Automated (Outlying Regions) Areas

  17. Develop Fixed Bank Detector • Need  Results • Reduce O&M Costs  Eliminate Capacitor Patrols • Additional Monitoring  Reduce O&M Field Checks • Notification for Blown Fuses  Reduces System Losses • Better VAr Regulation  Install Fewer Banks • Outage Notification  Voltage Loss Detector • Possible Solution • Integrate into 4-Jaw Socket • Accepts Neutral Current Sensor • Low Target Price • Low Annual Communications Cost • Remote Monitoring / Switching Capability • Reports Capacitors Switched Off Line • Reports Analog Neutral Current Value • Outage Detection • DNP to Utility SCADA

  18. Plans for the Present and Future • Capacitor Automation • Target Use of Fixed Bank Controls • Develop/Deploy Neutral Sensing Option • Develop/Deploy Lower Cost Capacitor Controls • Distribution Automation • Use Fixed Network for Full Featured Controls • Use Control Channel Solution as Appropriate • Monitor Growing Communication Solutions • Add DNP to Protocol Suite • Integrate RTM into Other RTUs • Regulators • Reclosers • Fault Detectors • Line Monitors