An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Example The following figureshows a reaction system in which the temperature increases with the feed rate of flow-controlled stream D. Heat is removed by water circulation through an exchanger. Normal reactor temperature is 200 F, but a catastrophic runaway will start if the reactor temperature reaches 300 F.

  2. Example In view of this situation, • The reactor temperature is monitored; • Rising temperature is alarmed at 225 F 9see horn); • An interlock shuts off stream D at 250 F, stopping the reaction (see solenoid and valve A); • The operator can initiate the interlock by pushing the panic button.

  3. Assumptions • Secondary failures are neglected. • The alarm signal always reaches the operator whenever the horn sounds