Main Substation (MSS1) 13,800 volts. Circulatory System. Building transformers 480 volts. texasheart.org. Analogies: Chest Pain = Corona Minor Stroke = Tracking Cardiac Arrest = Arcing (may not be able to resuscitate electrical system).

birdwell
Download Presentation

texasheart

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Main Substation (MSS1) 13,800 volts Circulatory System Building transformers 480 volts texasheart.org Analogies: Chest Pain = Corona Minor Stroke = Tracking Cardiac Arrest = Arcing (may not be able to resuscitate electrical system)

  2. All pictures of actual conditions: July 2014 Our electrical infrastructure Damaged insulation Rust ~50 yr. old conductor Heat damage Bird caging

  3. Items performed to date (no outage) • Installed temporary power quality monitors • Main substation and key building substations • Ultrasound testing • All substations • Discovered arcing, tracking and corona • Identified arcing in Basic Science Building & Med School • Replaced breakers • Started Electrical Coordination Study • Transformer Oil Sample Testing • Removed LIB (temp. HVAC load) and ALTC (temp. load) • Refurbished main and building substation breakers

  4. Short Term (outage-6hr mid Sept) Open MSS1 and insulate wiring Hi pot MSS1 Replace oil in transformers

  5. Recommendations ( Jan outage) • Replace MSS1 • Main 13,800 volt substation is at its end-of-life. • MSS1 is the heart of the electrical system. It serves as a 13,800 volt “pump” for the entire Long Campus. • MSS1 was purchased, as a used item, from CPS Board (today known as CPS Energy) ~50 years ago. • Replace oldest conductors • MED lines are the oldest. • Rework all building substations transfer switches, breakers, bus bars. • Perform another ultrasound test after outage is complete to compare against prior ultrasound test performed before the outage.