Correlations for Divertor Thermal-Hydraulic Performance at Prototypical Conditions

Correlations for Divertor Thermal-Hydraulic Performance at Prototypical Conditions. M. Yoda, S. I. Abdel-Khalik, D. L. Sadowski, B. H. Mills and M. D. Hageman G. W. Woodruff School of Mechanical Engineering. Objectives / Motivation. Objectives

bryce
Download Presentation

Correlations for Divertor Thermal-Hydraulic Performance at Prototypical Conditions

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Correlations for Divertor Thermal-Hydraulic Performance at Prototypical Conditions M. Yoda, S. I. Abdel-Khalik, D. L. Sadowski, B. H. Mills and M. D. Hageman G. W. Woodruff School of Mechanical Engineering

  2. Objectives / Motivation Objectives • Develop generalized parametric design curves for estimating maximum heat flux and pumping power requirements for the helium-cooled flat-plate (HCFP) divertor with and without fins • Similar curves already developed for modular finger-type design • Adding fins to HCFP increased maximum heat flux qmax to 18 MW/m2 (air results extrapolated to He) Motivation • Provide design guidance • Develop correlations that can be used in system design codes (Lane, Mark) ARIES Meeting (7/11)

  3. Approach • Conduct experiments with air on test modules that match initial HCFP design • Four configurations: two slot widths (W = 0.5 and 2 mm); “bare” cooled surface and cooled surface with 806 1 mm  2 mm fins • Incident heat fluxes q = 0.220.75 MW/m2 • Coolant flow rate in terms of Reynolds number Re = 1.2104, 3.0104, and 4.5104, spanning prototypical Rep = 3.3104 • Measure cooled surface temperatures and pressure drop p  Heat transfer coefficients h and loss coefficients KL • Extrapolate results to He at prototypical conditions • Generate parametric design curves relating qmax to Re, maximum surface temperature Ts, and pumping power as a fraction of incident thermal power  ARIES Meeting (7/11)

  4. GT Plate Test Module q q Armor Brass shell 0.1 • Air issues from 0.5 or 2 mm  7.62 cm slot, impinges on bare or finned surface 2 mm away • Heated by Cu heater block • Measure cooled surface temperatures with 5 TCs • Measure P, T at module inlet, exit  P • Measure mass flow rate  Re In In 2.4 cm 6 5.4 Out Out 2.2 cm Al cartridge ARIES Meeting (7/11)

  5. Effective and Actual HTCs Ac = cooled surface area Ap = base area btw. fins Af = side area of fins ARIES Meeting (7/11) • hact = spatially averaged heat transfer coefficient (HTC) at given operating conditions • heff = HTC for bare surface to have same Ts as surface with fins subject to the same q • For bare surfaces, hact = heff • q = Electrical power to heater / Ac • Ts avg. extrapolated surface temp. • For surfaces with fins • Fin efficiency η depends on hact  iterative solution • Assume adiabatic fin tip condition • As hact ↑, η ↓ and heff ↓

  6. HTC for Helium • Extrapolate experimental data for air to estimate performance of He-cooled divertor at prototypical operating conditions • He at inlet temperature Tin = 600 °C and 700 °C • Correct actual HTC for changes in coolant properties • Cases with fins: correct for changes in effective HTC,  ARIES Meeting (7/11)

  7. Calculating Max. q • Maximum heat flux • Surface temperature Ts = 1200 °C and 1300 °C: maximum allowable temperature for pressure boundary • Total thermal resistance RT due to conduction through pressure boundary, convection by coolant • P = 2 mm = thickness of pressure boundary • kP = 101 W/(mK) [pure W at 1300 °C] = thermal conductivity of pressure boundary ARIES Meeting (7/11)

  8. Calculating Loss Coeffs. • To extrapolate pressure drop data to prototypical conditions, determine loss coefficient based on conditions for air at slot • Determine pumping power based on pressure drop for He under prototypical conditions at same Re • average of He densities at inlet, outlet • Pumping power as fraction of • total thermal power incident on divertor ARIES Meeting (7/11)

  9. Parametric Design Curves • Provide guidance among different plate configurations and operating conditions • Plot q as a function of Re for a given Tin at constant pressure boundary surface temperature Tsand corresponding pumping power fraction  for W = 2 mm • W appears to have little effect on HTC, and W = 0.5 mm has slightly higher KL • Heat flux defined using area of pressure boundary: heat flux on tile • Plot  as a function of q and heff as a function of  for all four configurations ARIES Meeting (7/11)

  10. Max. q vs. Re : Bare At Rep = 3.3104 •  > 10% • q  10 MW/m2 for Ts = 1200 °C • q  12 MW/m2 for Ts = 1300 °C • Compare with q  15 MW/m2 for Tin = 600 °C, Ts = 1300 °C Tin = 700 °C q[MW/m2] Ts = 1300 °C 1200 °C  = 10% 5% Re (/104) ARIES Meeting (7/11)

  11. Max. q vs. Re : Fins At Rep = 3.3104 •  > 10% (less than bare case) • q  13 MW/m2 for Ts = 1200 °C • q  16 MW/m2 for Ts = 1300 °C • Compare with q  18 MW/m2 for Tin = 600 °C, Ts = 1300 °C Tin = 700 °C q[MW/m2] Ts = 1300 °C 1200 °C 5%  = 10% Re (/104) ARIES Meeting (7/11)

  12. βvs. Max. q: W = 2 mm Correlations (lines) • Also for W = 0.5 mm • For all Tin = 600 °C, and Tin = 700 °C, surfaces with fins: • For Tin = 700 °C, bare surfaces: • A, B, C, D constants Tin = 600 °C Tin = 700 °C   Bare  Fins q[MW/m2] ARIES Meeting (7/11)

  13. Eff. HTC vs.β: W = 2 mm heff [kW/(m2K)] Correlations (lines) • For W = 0.5 mm and 2 mm • C, D, E constants  Bare  Fins Tin = 600 °C Tin = 700 °C  ARIES Meeting (7/11)

  14. Summary Developed generalized parametric design curves for plate-type divertor based on experimental data of Hageman Maximum heat flux related to Re for a given surface temperature and corresponding pumping power fraction Raising coolant inlet temperature Tin from 600 °C to 700 °C decreases thermal performance In all cases, pumping power exceeds 10% of incident thermal power for Tin = 700 °C Obtained exponential and power-law correlations (R2 0.996 in all cases) for pumping power fraction at a given incident heat flux, and effective HTC at a given pumping power fraction ARIES Meeting (7/11)

  15. β Correlations I ARIES Meeting (7/11)

  16. β Correlations II ARIES Meeting (7/11)

  17. heff Correlations ARIES Meeting (7/11)