AFPS. Introduction. AFPS: Automatic Floor Pressurization System. This special application, which modulates the fan speed by means of a differential pressure sensor installed underneath the floor, detects any pressure drops caused by air leaks or by a floor panel being removed. Introduction.
E N D
Introduction AFPS: Automatic Floor Pressurization System This special application, which modulates the fan speed by means of a differential pressure sensor installed underneath the floor, detects any pressure drops caused by air leaks or by a floor panel being removed.
Introduction Modular Access Floor AFPS external pressure sensor head: not in direct air flow
Introduction SPD: Differential Pressure Sensor internal pressure sensor head external pressure sensor head
ElectricalConnections internal pressure sensor head external pressure sensor head + _
Configuration • Put the unit in stand-by and wait for the fans to stop; • From the main screen press the Prg key, select Service Menu and press Enter; • Type in the Service Password and press Enter to confirm; • Select Hardware Settings and press Enter to confirm; • Scroll through the screens by pressing the Down key until the screen for setting the parameters appears (see the detailed masks below): Air pressure transducer regulation mask Range Start: starting value of the transducer Range End: end value of the transducer Read value: reading taken by the sensor Delta: maximum variation which doesn’t activate the filter Time: duration of the filter Value: value read by the sensor Evaporating fan regulation mask Fan supply: fan power supply (Monophase / Triphase); Modulation with air pressure enabled: fan modulation activated by the air pressure transducer; Minimum speed: minimum evaporating fan speed during modulation; Maximum speed: maximum evaporating fan speed during modulation.
Configuration Evaporating fan regulation mask Setpoint: reference pressure value which needs to be maintained by the modulation of the fans; Dead Band: dead band regulation; Regul. Band: proportional regulation band; Integral Time: integral time; Derivat. Time: derivative time; Air pressure: reading taken by the sensor; Evaporating Fan: evaporating fan regulation percentage. Alarm parameters mask Alarm Level: low air pressure alarm activation level; Alarm Delay: low air pressure alarm activation delay time. After having set the parameters press the Escape key several times until the main screen appears; to memorise the data which has been entered, it is advisable to turn off the unit for several seconds and then turn it back on again.
Configuration • If there are several units connected within a Lan network, it is possible to carry out fan speed modulation by using a local sensor or by calculating the average reading of all of the sensors which are connected and configured for each unit which is operating. This setting must be carried out in the Lan configuration mask for each single unit by carrying out the following procedure: • From the main screen press the Prgkey, select Settings Menu and press Enter; • Insert the Password Settings and press Enter to confirm; • Select Lan Settings and press Enter to confirm; • Scroll through the screens by pressing the Down key until the mask concerning the parameters setting appears (see the detailed masks below): Air pressure control configuration masks Local Values: modulation of the fan speed is controlled by the pressure reading taken by the sensor on each single unit; Mean Values: modulation of the fan speed is controlled by the average pressure reading taken by the sensors on all of the units which are connected in a local network.