Today’s Session

What is ahead?. Today’s Session. Fault Level Calculations Power-system Overview PU Concept 3 Ph. Fault Level Calculations 1 Ph Fault Level Calculations O/C E/F Relay Time Coordination General information about relay characteristic Worked out example Directional Relay What is MTA

Download Presentation

Today’s Session

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. What is ahead? Today’s Session • Fault Level Calculations • Power-system Overview • PU Concept • 3 Ph. Fault Level Calculations • 1 Ph Fault Level Calculations • O/C E/F Relay Time Coordination • General information about relay characteristic • Worked out example • Directional Relay • What is MTA • How to confirm direction of relay reach while in service

  2. Fault Level Calculations

  3. Fault Level Calculations What is ahead? • Overview of transmission network. • What is mean by fault level • PU Concept • Network Modeling • Fault Level Calculation & Worked out example • Three Phase Fault • SLG Fault

  4. Fault Level Calculations Step-1 Overview of power system grid and transmission network

  5. Fault Level Calculations Typical State Level Power System & our area of interest

  6. Fault Level Calculations Typical State Level Power System & our area of interest

  7. Fault Level Calculations Local Network – or – Sub-Transmission System 400kV S/S - A S/S - C 220kV 220kV 33kV S/S - B 220kV S/S - D 132kV S/S - F S/S - E 132kV 33kV 33kV 11kV

  8. Fault Level Calculations Step-2 What is mean by fault level

  9. Fault Level Calculations What is fault level S/S - A S/S - B S/S - B 14530 MVA 14530 MVA 11300 MVA 18290 MVA 9700 MVA 9730 MVA 9730 MVA 6400 MVA 7200 MVA 8400 MVA 8400 MVA 4630 MVA 5800 MVA S/S - C 2700 MVA 3670 MVA 1185 MVA ABC Transmission Co. Ltd. 3 Ph Fault Levels For 2010-2011

  10. Fault Level Calculations S/S - B 14530 MVA 9730 MVA What is fault level-Continued…. 2450 MVA 2450 MVA 1465 MVA 1465 MVA 2200 MVA 2200 MVA 2300 MVA 8700 MVA 1030 MVA

  11. Fault Level Calculations Step-3 Understanding Per-Unit Measurements

  12. Fault Level Calculations PU Concept • PU impedance values are calculated by • For Transformers • For Lines Base MVA %ImpedanceNew Base MVA = % ImpedanceName Plate Capacity in MVA Base MVA = Ohmic Value %Impedance kV 2

  13. Fault Level Calculations PU Concept • PU impedance values are calculated by • For Transformers • %Impedance = Ohmic Value * ( Base MVA / Name Plate MVA ) • For Lines • %Impedance = Ohmic Value * ( Base MVA / BasekV2 )

  14. Fault Level Calculations PU Concept Base MVA = 200 MVA Sec A Sec B Sec C Sec D 220kV 400kV 132kV 33kV T1 L1 T2 L2 T3 L3 12 Ohm 0.4 ohm/Km 200 Km 0.4 ohm/Km 50 Km 0.4 ohm/Km 30 Km 400/220 kV 15% 315 MVA 220/132 kV 14% 200 MVA 132/33 kV 9.33% 25 MVA

  15. Fault Level Calculations Step-4 Network Modeling

  16. Fault Level Calculations PU Concept T1 L1 T2 L2 T3 L3 0.4 ohm/Km 200 Km 0.4 ohm/Km 50 Km 0.4 ohm/Km 30 Km 400/220 kV 15% 315 MVA 220/132 kV 14% 200 MVA 132/33 kV 9.33% 25 MVA

  17. Fault Level Calculations Short Circuit Current • 3 Phase Short Circuit MVA at fault point Base MVA x 100 = ---------------------------------------------------- Percentage Impedance(from source to fault point)

  18. Fault Level Calculations PU Concept-Continued XT1 XL1 XT2 XL2 XT3 XL3 9.52% 14% 33.05% 22.96% 74.64% 220%

  19. Fault Level Calculations PU Concept 75 Ohm 80 Ohm 34 Ohm 20 Ohm 65 Ohm 12 Ohm 0.4 ohm/Km 200 Km 0.4 ohm/Km 50 Km 0.4 ohm/Km 30 Km 400/220 kV 15% 315 MVA 220/132 kV 14% 200 MVA 132/33 kV 9.33% 25 MVA

  20. Fault Level Calculations Step-5 Finding Source Impedance, Worked out Example

  21. Fault Level Calculations Typical State Level Power System & our area of interest 4630 MVA 4630 Xs(pu) Base MVA= 100 Xs(pu) Xs (pu) = 0.0216 Or Xs% = 2.16%

  22. Fault Level Calculations 220/132kV Padegaon Solved Example 132kV 33kV 2850 MVA 50 MVA 10.21% 50 MVA 10.21% 132/33-11 kV Harsool 50 MVA 10.88 % 50 MVA 10.88 % 132/33-11 kV Chikalthana 0.4 Ohms / Km 132kV 33kV 25 MVA 9.73 % 25 MVA 9.73 % 50 MVA 10.03% 8 Km 25 MVA 10.04 % 25 MVA 10.04 % 25 MVA 10.52 % 11kV 0.4 Ohms / Km 25 MVA 10.21 % 5 Km 25 MVA 9.84 % 11kV

  23. Fault Level Calculations 220/132kV Padegaon Solved Example 132/33-11 kV Harsool 132kV 33kV 2850 MVA 132/33-11 kV Chikalthana 668 MVA 2257 MVA 132kV 33kV 538 MVA 1998 MVA 11kV 11kV

  24. Fault Level Calculations Unsymmetrical Faults-Sequence Network • Up till now we have discussed 3 Phase faults which are rear. Most of the fault in power system are single line to ground faults. • To find out the short circuit MVA due to single phase to ground fault it is necessary to use Sequence Network • Let us have a closer look of sequence network

  25. Fault Level Calculations Unsymmetrical Faults-Sequence Network M1 T2 L T1 G XM11 XM21 M2 XT21 XL1 XT11 Xg1 SLD F +Ve Sequence Network XM10 XM20 XM12 XM22 XT20 XL0 XT10 Xg0 XT22 XL2 XT12 Xg2 F F Zero Sequence Network -Ve Sequence Network

  26. Fault Level Calculations Single Line to Ground Fault-Sequence Network Connections XM11 XM21 X1 XT21 XL1 XT11 Xg1 F X2 XM12 XM22 XT22 XL2 XT12 Xg2 Ia = 3 / (X1 + X2 + X0) F X0 XM20 XT20 XL0 XT10 Xg0 F

  27. Fault Level Calculations 220/132kV Padegaon Single Line to Ground Fault-Solved Example 132kV 33kV 3Ph 2850 MVA 50 MVA 10.21% 50 MVA 10.21% 132/33-11 kV Harsool 1Ph 2230 MVA 50 MVA 10.88 % 50 MVA 10.88 % 132/33-11 kV Chikalthana 0.4 Ohms / Km 132kV 33kV 25 MVA 9.73 % 25 MVA 9.73 % 50 MVA 10.03% 8 Km 25 MVA 10.04 % 25 MVA 10.04 % 25 MVA 10.52 % 11kV 0.4 Ohms / Km 25 MVA 10.21 % 5 Km 25 MVA 9.84 % 11kV

  28. Fault Level Calculations Single Line to Ground Fault-Solved Example 3Ph 2850 MVA 3Ph 2850 MVA 1Ph 2230 MVA 1 Ph Short Circuit MVA at 132kV Harsool Bus 3*BaseMVA*100 ( ) + ( XS0 + (XL10 || XL20) ) 2*( XS1 + (XL11 || XL21) )

  29. Fault Level Calculations 220/132kV Padegaon Solved Example 132/33-11 kV Harsool 132kV 33kV 3Ph 2850 MVA 3Ph 2257 MVA 3Ph 668 MVA 1Ph 2230 MVA 132/33-11 kV Chikalthana 1Ph 1662 MVA 1Ph 604 MVA 132kV 33kV 538 MVA 1998 MVA 11kV 11kV

  30. Fault Level Calculations Thank You