560 likes | 642 Views
World Class Leaders in Fire Detection for over 75 years. HP900. New Proposed Features. HP900. Main Areas: Zones in Test Printouts Recalibration time Networking Time & Date Expansion of the Test Key General Discussion. HP900. Zones in Test
E N D
World Class Leaders in Fire Detection for over 75 years
HP900 • New Proposed Features
HP900 Main Areas: • Zones in Test • Printouts • Recalibration time • Networking • Time & Date • Expansion of the Test Key • General Discussion
HP900 Zones in Test This feature will be expanded so that Multiple zones can be tested simultaneously.
HP900 Printouts -Event Store This will allow a selective printout from the Event Store for a particular loop or a particular condition i.e. Fires,Faults etc. This will still allow the complete Event store to be printed.
HP900 EVENT STORE PRINTOUT PRINTINGS
HP900 EVENT STORE PRINTOUT PRINTER ENABLED
HP900 EVENT STORE PRINTOUT PRINT EVENT STORE PRESS ENABLE TO START PRINTING NOTE IF ENABLE IS PRESSED THEN THE COMPLETE EVENT STORE IS PRINTED
HP900 EVENT STORE PRINTOUT PRINT ONLY MARKED EVENTS OFF NOTE THE ENABLE/DISABLE KEY TOGGLES SELECTION
HP900 EVENT STORE PRINTOUT PRINT FIRES ON NOTE THE ENABLE/DISABLE KEY TOGGLES SELECTION
HP900 EVENT STORE PRINTOUT PRINT PRE-ALARMS ON NOTE THE ENABLE/DISABLE KEY TOGGLES SELECTION
HP900 EVENT STORE PRINTOUT PRINT FAULTS ON NOTE THE ENABLE/DISABLE KEY TOGGLES SELECTION
HP900 EVENT STORE PRINTOUT PRINT MAINTENANCE WARNINGS ON NOTE THE ENABLE/DISABLE KEY TOGGLES SELECTION
HP900 EVENT STORE PRINTOUT PRINT SPECIAL EVENTS ON NOTE THE ENABLE/DISABLE KEY TOGGLES SELECTION
HP900 EVENT STORE PRINTOUT PRINT SYSTEM EVENTS ON NOTE THE ENABLE/DISABLE KEY TOGGLES SELECTION
HP900 EVENT STORE PRINTOUT PRINT EVENTS BY LOOP PRESS ENABLE TO START PRINTING NOTE IF ENABLE IS PRESSED THEN ALL LOOPS ARE PRINTED USING THE PREVIOUS SELECTED OPTIONS
HP900 EVENT STORE PRINTOUT PRINT EVENTS BY LOOP ALL LOOPS PRESS ENABLE TO START PRINTING NOTE IT IS POSSIBLE TO SELECT A PARTICULAR LOOP
HP900 EVENT STORE PRINTOUT PRINT EVENTS BY LOOP 00 PRESS ENABLE TO START PRINTING NOTE IT IS POSSIBLE TO SELECT A PARTICULAR LOOP
HP900 EVENT STORE PRINTOUT PRINT EVENTS BY LOOP 00 PRESS ENABLE TO START PRINTING ENABLE KEY NOTE IT IS POSSIBLE TO SELECT A PARTICULAR LOOP
HP900 Printing Event Store from the Fire Panel EVENT TIME: 09:00.38 01/01/97 RESET NODE 01 A:00.019 065/200 EVENT TIME: 09:00.36 01/01/97 EVACUATE NODE 01 A:00.019 064/200 EVENT TIME: 09:00.11 01/01/97 CHANGED TO ACCESS LEVEL 3 063/200
HP900 Printouts -Event store (Marked Events) The events are marked within the event store, so it is necessary to mark the events before setting “PRINT MARKED EVENTS ONLY” to “ON”
HP900 MARKING EVENTS WITHIN THE EVENT STORE EVENT REGISTER
HP900 MARKING EVENTS WITHIN THE EVENT STORE EVENT REGISTER SCROLLING
HP900 MARKING EVENTS WITHIN THE EVENT STORE CHANGING TO ACCESS LEVEL 3 200/200 EVENT TIME 09:00.53 01/01/97 DISABLE KEY NOTE THE DISABLE KEY WILL MARK ALL EVENTS PREVIOUS TO CURRENT EVENT
HP900 MARKING EVENTS WITHIN THE EVENT STORE CHANGING TO ACCESS LEVEL 3 200/200 EVENT TIME * 09:00.53 01/01/97 NOTE THE ASTERIX SHOWS THAT EVENT HAS BEEN MARKED
HP900 MARKING EVENTS WITHIN THE EVENT STORE CHANGING TO ACCESS LEVEL 2 150/200 EVENT TIME * 09:00.53 01/01/97 DISABLE KEY NOTE THE DISABLE KEY WILL UNMARK ALL EVENTS PREVIOUS TO CURRENT EVENT
HP900 MARKING EVENTS WITHIN THE EVENT STORE CHANGING TO ACCESS LEVEL 2 150/200 EVENT TIME 09:00.53 01/01/97 NOTE NOW A BLOCK OF EVENTS HAS BEEN MARKED BETWEEN EVENT 150 AND 200.
HP900 MARKING EVENTS WITHIN THE EVENT STORE FIRE ALARM 112/200 EVENT TIME 09:00.53 01/01/97 ENABLE KEY NOTE THE ENABLE KEY WILL MARK ONE EVENT AT A TIME
HP900 MARKING EVENTS WITHIN THE EVENT STORE FIRE ALARM 112/200 EVENT TIME * 09:00.53 01/01/97 NOTE THIS EVENT IS NOW MARKED, AS WELL AS THE PREVIOUSLY DEFINED BLOCK
HP900 Printouts -Status In addition to the current information this will show if a device is Enabled or Disabled, if a device is disabled for a period of time when the automatic enablement will take place. Sensor delay time would also be shown.
HP900 STATUS PRINTOUT PRINTINGS
HP900 STATUS PRINTOUT PRINTER ENABLED
HP900 STATUS PRINTOUT PRINT STATUS BY ZONE PRESS ENABLE TO START PRINTING NOTE IF ENABLE IS PRESSED THEN THE STATUS OF ALL THE DEVICES ARE PRINTED
HP900 EVENT STORE PRINTOUT PRINT STATUS BY ZONE ALL ZONES PRESS ENABLE TO START PRINTING NOTE IT IS POSSIBLE TO SELECT A PARTICULAR ZONE
HP900 EVENT STORE PRINTOUT PRINT STATUS BY ZONE 01 PRESS ENABLE TO START PRINTING ENABLE KEY NOTE IT IS POSSIBLE TO SELECT A PARTICULAR ZONE
HP900 Printing from the Fire Panel 09:05.14 01/01/97 OEM-APP- NETWORKING VERSION XX ZONE 01 NUMBER OF SUB ADDRESS 03 EVACUATE:ON SILEN:ON RESET:ON DEF:ON UNIT IS DISABLED - ENABLED IN 30 MINS DUAL SOUNDER CONTROLLER & MONITOR CHQ-B ADDRESS A:02:064.1 ZONE 01 THRESHOLD 030 PRE-ALARM:ON Z:052 F:179 UNIT IS DISABLED- ENABLED IN 30 MINS PHOTO SMOKE SENSOR ALE/ALG ADDRESS A:02:093 ZONE 01
HP900 Recalibration time At present the sensors are recalibrated at the time the system is powered up, this new feature will allow the user to set the time for recalibration to occur.
HP900 Recalibration SET CALIBRATION TIME
HP900 Recalibration CALIBRATION TIME 04:00 NOTE 24 HOUR CLOCK 30 MINUTE STEP
HP900 Recalibration CALIBRATION TIME 05:00 NOTE 24 HOUR CLOCK 30 MINUTE STEP
HP900 Recalibration CALIBRATION TIME 04:00 NOTE 24 HOUR CLOCK 30 MINUTE STEP
HP900 Day/ Night mode This feature will allow each sensor to be selected to be on Day/Night Mode. The Day/Night Mode allows reduced sensitivity during a user defined time period.
HP900 Networking - Time Each panel on the network has its own real time clock, this new feature would allow the real time clock to be set by any panel on the network. Setting the time on one panel, will set the time on all the panels on the network.
HP900 Networking - Alerts This would allow a fire on any panel on the network to put any other panel on the network in the Alert condition.
HP900 Networking - Common Zones This allows each panel on the network to have zones that are common with other panels on the network. This allows a stairwell to be in one zone within a building when each floor has a separate control panel.
HP900 Networking - Cause & Effects This will allow Cause & Effects across the network, this gives the user the capability of 99 virtual wires across the whole network.
C&E TABLE C&E TABLE s s C&E TABLE s s HP900 Networking - Cause & Effects VIRTUAL WIRE 1 CHQ-B CONTROL PANEL 1 CONTROL PANEL 2 PIO OUTPUT C&E TABLE VIRTUAL WIRE 2
HP900 Time & Date This would prevent the control panel from losing the time and date when power is removed from the panel.
HP900 Test Key The function of the Test key will be expanded to work on the Event Store, so it will toggle the bottom line between Event Time/User Text/Device Type and Fault Code if the Event was a fault.
HP900 USING THE TEST KEY WITHIN THE EVENT STORE EVENT REGISTER