Good Manufacturing Practice Heating, Ventilation and Air- Conditioning (HVAC) Part 2: HVAC systems and components Section 7
HVAC Objectives In the following slides, we will study the components of air- handling systems in order to: Become familiar with the components Know their functions Become aware of possible problems
HVAC General • Design of HVAC is dependent on required degree of air cleanliness • Suitable components should be selected including: • fans, • driers, • filters, • ducts, grilles, etc. 7.
Exhaust air treatment Fresh air treatment (make-up air) Terminal air treatment at production room level + Production Room Central air handling unit HVAC Main subsystems
HVAC Components Components in HVAC may include, depending on need: • Filters • Fans • no fan failure; including supply air fans, return air fans, exhaust air fan, dust extract system fans • Driers • Drying of air with chemical driers, e.g. rotating desiccant wheel • Frost coils for preheating air 7.1.1 – 7.1.7
HVAC Components Components in HVAC may include, depending on need: • Snow eliminators • Dust eliminators • Moisture eliminators • Precooling coils • Alarm systems, grilles/diffusers, etc. 7.1.1 – 7.1.7
Overview components Flow rate controller Silencer Fan Filter Weather louvre Control damper + Humidifier Prefilter Terminal filter Production Room Cooling coil with droplet separator Heating coil HVAC Exhaust Air Grille Heater Secondary Filter Recirculated air
HVAC Components (1) • Weather louvre • Silencer • Flow rate controller • Control damper • To prevent insects, leaves, dirt and rain from entering • To reduce noise caused by air circulation • Automated adjustment of volume of air (night and day, pressure control) • Fixed adjustment of volume of air
HVAC Components (2) • Heating unit • Coolingunit/ dehumidifier • Humidifier • Filters • Ducts • To heat the air to the proper temperature • To cool the air to the required temperature or to remove moisture from the air • To bring the air to the proper humidity, if too low • To eliminate particles of predetermined dimensions and/or microorganisms • To transport the air
Adsorber wheel Humid room air Regeneration air Humid room air Air heater Control damper for airflow HVAC Air-handling unit Dry air AHU with fan Variable Speed Controller Filter Pressure Gauges De-humidification
Humidifier Silencer Heating and cooling units HVAC
Filter classes HVAC Dust filters Standard Aerosol Coarse Fine HEPA ULPA Dp > 10 µ m 10 µ m > Dp > 1 µ m Dp < 1 µ m G1 - G4 F5 - F9 H 11 - 13 U 14- 17 EN 779 Standard EN 1822 Standard
HVAC HEPA or tertiary filter Primary panel filter Secondary filter
+ Production Room Production Room HVAC Positioning of filters (1) AHU mounted final filter Filter in terminal position HEPA Filter HEPA Filter
HVAC Positioning of filters (2) Prefilter AHU Main filter Ceiling exhausts 2 3 1 Low level exhausts
Positioning of filters (3) Final filter AHU Prefilter 1 2 HVAC
Swirl Type air diffusors with terminal filters HVAC 1 2 3 4 1 Filter 2 Tightening frame 3 Register outlet 4 Screw fixation for register
HVAC Low induction swirl diffusor (preferred) High induction office type diffusor (avoid)
Regulation of room pressure – pressure differentials concept HVAC Room pressure gauges Room pressure indication panel
HVAC Problems with components • Flow ratecontroller • Control damper • Humidifier • Cooling battery • Filters • Ducts • Blocked • Poorly adjusted, bad pressure differential system • Bad water/steam quality/ poor drainage • No elimination of condensed water/ poor drainage • Incorrect retention rate/damaged/badly installed • Inappropriate material/internal insulator leaking
HVAC In the next slides Consider different air types, e.g.: • Supply air • Return air (recirculated air) • Fresh air (make-up air) • Exhaust air And: Concepts of air delivery to production areas: • Recirculation systems • Full fresh-air systems
Air types Exhaust air + Fresh air (make-up air) Supply air Production Room Return air (recirculated) HVAC
HVAC Recirculation systems • There should be no risk of contamination and cross-contamination when air is recirculated • Normally, HEPA filters (EN1822 H13) needed in supply air stream • Not required in single product facility with no risk of cross-contamination • Not required where no dust generation (e.g. secondary packaging) • HEPA filters placed in AHU or terminally • Dust from highly toxic processes should not be recirculated 7.2.1 – 7.2.6
HVAC Ventilation with recirculated air + make-up air Exhaust Unit Central Air-Handling Unit Return air
HVAC Full fresh-air systems • 100% fresh air - normally where toxic products are processed, and recirculation not recommended • No contamination from fresh air – sufficient filtration needed • Degree of filtration on exhaust dependent on exhaust air contaminants and environment regulations • Energy-recovery wheels • Should not be source of contamination • Relative pressure between supply and exhaust air 7.3.1 – 7.3.3
HVAC Ventilation with 100% fresh air (no air recirculation) Washer (optional) Exhaust Unit W Central Air-Handling Unit Production Rooms