650 likes | 852 Views
MDS Selection. Contents. Introduction Selection Consideration Selection Process Software Demonstration. Introduction. Sample of Installation. Selection Consideration. Unit & Piping Selection. Main Factors to consider during Piping Selection Location of equipment Indoor Unit
E N D
Contents • Introduction • Selection Consideration • Selection Process • Software Demonstration
Unit & Piping Selection Main Factors to consider during Piping Selection • Location of equipment • Indoor Unit • Outdoor Unit • Refnet & Distributor Joint These item will influence the piping layout and length of the design
Unit & Piping Selection Some other factors to consider during Piping Selection • Equivalent Piping Length • Type of Joint for branches • Outdoor capacity factor • Piping length & height factor • Refrigerant Pipe Specification
Equivalent Piping Calculation Equivalent length is the converted length and includes parts such as elbow, which has pressure losses in the pipe. The formula is as follow: Equivalent length = Real length of tubing + No. of elbow × Equivalent length of each elbow + No. of oil trap ×Equivalent length of each oil trap
Important Factor to Consider Example: Outdoor Model : MDS100BR Pipe Diameter : 28.6 mm Main Pipe : 80m Branch Length: 20m Elbows: 10 units Oil traps: 3 units Equivalent Length = Real length of tubing + No. of elbow × Equivalent length of each elbow + No. of oil trap ×Equivalent length of each oil trap = (80 + 20) + (10 X 0.5) + (3 X 3.7) = 116.1 m
Important Factor to Consider Criteria 1 When the equivalent length is more than 90% of the maximal real length of the main tubing , the gas pipe need to be increase to one size bigger (diameter). Criteria 2 After expanded the gas pipe to a larger diameter, the equivalent length need to be recalculate. The formula is as follow: Expanded Equivalent Length = Equivalent length of main piping X 0.5 + equivalent length of the branch
Important Factor to Consider Example: Maximum allow actual length for 10Hp is 125m Calculated Equivalent Length is 116.1m Ratio of Equivalent Length over Maximum allow Actual Length= 92.88% Equivalent length is more than 90% of the maximal real length. Hence the gas Pipe of MDS100BR need to change.
Unit & Piping Selection Refrigerant Copper Pipe Specification : MDS-B
Important Factor to Consider Example: Hence the gas Pipe of MDS100BR need to change from 28.6 mm to 39.40 mm After expanded the gas pipe to a larger diameter, the equivalent length need to be recalculate. Expanded Equivalent Length = Equivalent length of main piping X 0.5 + equivalent length of the branch Main Pipe : 80m Branch Length: 20m Elbows: 10 units Oil traps: 3 units Equivalent Length = Real length of tubing + No. of elbow × Equivalent length of each elbow + No. of oil trap ×Equivalent length of each oil trap = (80 + 20) + (10 X 0.5) + (3 X 3.7) = 116.1 m Expanded Equivalent Length = [80 + (10 X 0.5) + (3 X 3.7)] X 0.5 + 20 Expanded Equivalent Length = 68.05 m
Unit & Piping Selection • Type of Joint for branches • Influence the piping layout design • Outdoor capacity factor • Influence by the design ambient temperature and indoor temperature • Piping length & height factor • Influence by the location of outdoor and the total piping length • Refrigerant Pipe Specification • Use to determine the branches diameter
Unit & Piping Selection Selection of branch joint / distributors for MDS
Unit & Piping Selection MDS-Y1~Y4 dimensional drawing
Unit & Piping Selection MDS-Y6 dimensional drawing
Unit & Piping Selection MDS-Y7 dimensional drawing
Unit & Piping Selection MDS-C1 dimensional drawing
Unit & Piping Selection MDS-C2~C3 dimensional drawing
Unit & Piping Selection Caution Using Distribution Header may lead to imbalance refrigerant flow.
Refnet Joint Refrigerant Pipe Work Connection Type of Refnet Joint/Distributors Allow
Distributor Refrigerant Pipe Work Connection Type of Refnet Joint/Distributor Allow
Refrigerant Pipe Work Connection Type of Refnet Joint/Distributors Allow Refnet Joint Distributor
Refrigerant Pipe Work Connection Type of Refnet Joint/Distributors Not Allow Refnet Joint Distributor
Unit & Piping Selection Cooling Capacity Correction Factor
Unit & Piping Selection Heating Capacity Correction Factor
Unit & Piping Selection Cooling Capacity Correction Factor Cooling cap. factor
Unit & Piping Selection Heating Capacity Correction Factor
Unit & Piping Selection Refrigerant Pipe Specification : MDS-A
Unit & Piping Selection Refrigerant Pipe Specification : MDS-B
E A B F C D Unit & Piping Selection Example Building Type: Bungalow
Unit & Piping Selection Example Requirement Cooling only model • Ambient temperature : 40.0 °C • Indoor temperature : 21.0 °C Other Information • Piping length:70m • Height between I/O:4m • Outdoor Unit located below indoors
Unit & Piping Selection Indoor Requirement
Unit & Piping Selection Example • Total Indoor capacity is 32.3 kW
Unit & Piping Selection Example Selection Criteria • Total Indoor capacity must be range between 50% ~ 120% of the outdoor capacity. • We recommend that the outdoor capacity equals to the total indoor capacity or a little larger than the indoor capacity
Unit & Piping Selection Example Selected Outdoor : MDS120B Cooling Capacity : 32.5kW Comply to selection criteria
Unit & Piping Selection Example • Selected Outdoor and Indoor Model
Unit & Piping Selection Example Outdoor Capacity factor • Cooling only model • Ambient temperature : 40.0 °C • Indoor temperature : 22.0 °C 1.03
Unit & Piping Selection Example Piping length & height factor • Piping length:70m • Height between I/O:4m • Outdoor Unit located below indoors 91%
Unit & Piping Selection Example Total Capacity • = Outdoor Capacity X Outdoor Capacity Factor • X Piping length & height Factor • = 32.5 kW X 1.03 X 94% • = 31.47 kW Comply to requirement
E A B F C D Unit & Piping Selection Example Building Type: Bungalow
Unit & Piping Selection Example • Selection pipe diameter MDS120B A B C WMD 20G WMD 10G CCD 25C 5.6 kW 2.8 kW 6.5 kW E D WMD 10G CKD 30A WMD 20G 2.8 kW 9.0 kW 5.6 kW
Unit & Piping Selection Refrigerant Pipe Specification : MDS-B
Unit & Piping Selection Example Downstream capacity Point A A-B-C : 14.9kW A-D-E : 17.4 kW Point BB-C : 8.4 kW D-E : 8.4 kW Main pipe diameter : ø 15.88mm / ø 28.6mm MDS120B A B C WMD 20G WMD 10G CCD 25C 5.6 kW 2.8 kW 6.5 kW D E WMD 10G CKD 30A WMD 20G 2.8 kW 9.0 kW 5.6 kW
Unit & Piping Selection Refrigerant Pipe Specification : MDS-B Point A A-B-C : 14.9kW A-D-E : 17.4 kW
Unit & Piping Selection Example Main pipe diameter : ø 15.88mm / ø 28.60mm A-B diameter : ø 9.52mm / ø 19.05mm MDS120B A B C WMD 20G WMD 10G CCD 25C 5.6 kW 2.8 kW 6.5 kW D E WMD 10G CKD 30A WMD 20G A-D diameter : ø 12.70mm / ø 22.23mm 2.8 kW 9.0 kW 5.6 kW
Unit & Piping Selection Example Point B B-C : 8.4 kW B-CCD25C : 6.5kW MDS120B A B C WMD 20G WMD 10G CCD 25C 5.6 kW 2.8 kW 6.5 kW D E WMD 10G CKD 30A WMD 20G 2.8 kW 9.0 kW 5.6 kW