1 / 21

無塵室節能式全外氣空調箱

無塵室節能式全外氣空調箱. 莊人聿 力晶半導體 12AB 廠務部 ( 空調技師 ) E-mail : jenyu @psc.com.tw (03)579500 ext.6723 06.30.2006. 簡報綱要. 前言 全外氣空調箱原理簡介 改善前 / 後差異說明 節能效益說明. 1. 前言. 1.1 依據半導體廠的耗能比例調查,廠務系統 的耗能佔了整廠耗能的 56.6﹪ ,而 空調系 統約佔了全部耗能的 40﹪ 是最大的部分 。. 1.2 節能式全外氣空調箱因增加 熱交換盤管 , 利用空調箱內部熱能回收的作用, 節省冰

Download Presentation

無塵室節能式全外氣空調箱

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 無塵室節能式全外氣空調箱 莊人聿 力晶半導體 12AB廠務部 (空調技師) E-mail:jenyu@psc.com.tw (03)579500 ext.6723 06.30.2006

  2. 簡報綱要 前言 全外氣空調箱原理簡介 改善前/後差異說明 節能效益說明

  3. 1.前言 1.1依據半導體廠的耗能比例調查,廠務系統 的耗能佔了整廠耗能的56.6﹪,而空調系 統約佔了全部耗能的40﹪是最大的部分。

  4. 1.2節能式全外氣空調箱因增加熱交換盤管, 利用空調箱內部熱能回收的作用,節省冰 水及溫水供應量,進而達到節省冰水主機 之耗電量與鍋爐產生熱水之瓦斯消耗量。

  5. 2.全外氣空調箱原理簡介 2.1無塵室空調系統簡介 • 無塵室內因有大量製程排氣,又為避免受到外界環境污染, • 因此必須隨時補充足夠外氣。 • 此外如無塵室內人的呼吸、污染物質濃度的稀釋、濕度控制 等都依賴外氣來對無塵室作一微調功能,因此無塵室空調系 統對無塵室之功能就類似人類對呼吸需求一樣重要。

  6. 全外氣空調箱 2.2無塵室空調系統圖示 ExhaustFan T 監測 T INV T INV P MAU T P T H P 監測 監測 監測 無塵室 監測 P

  7. 2.3全外氣空調箱簡介 • 溫度控制 • 濕度控制 • 外氣清淨度控制 • 無塵室與外氣正壓控制 Pre-heating Coil Cooling Coil-1 Air Washer Cooling Coil-2 Re-heating Coil HEPA Filter 預 熱 控 制 降 溫 控 制 加 濕 控 制 除 濕 控 制 回 溫 控 制

  8. Pre-heating Coil Cooling Coil-1 Air Washer Cooling Coil-2 Re-heating Coil HEPA Filter 空氣品質之控制 -夏季 Outside Air in Summer (35℃, 80%) Cooling Coil-1 Cooling Coil-2 Re-heating Coil Cleanroom Specification (23 ±1℃, 43 ±5%)

  9. Pre-heating Coil Cooling Coil-1 Air Washer Cooling Coil-2 Re-heating Coil HEPA Filter 空氣品質之控制 -冬季 Re-heating Coil Cleanroom Specification (23 ±1℃, 43 ±5%) Outside Air in Winter (5℃, 50%) Per-heating Coil

  10. 浪費能源 浪費能源 浪費能源 3.改善前/後差異說明 3.1節能改善前狀況 • 既設之全外氣空調箱全部利用冰水將外氣從35℃降 溫除濕至9.5℃, • 再利用溫水加熱到16℃。

  11. 改善前之設計

  12. Re-heater Cooling coil-1 Pre-heater Cooling coil-2 既設空調箱

  13. 3.2節能改善說明 採用節能式全外氣空調箱,增加兩道熱交換盤管,利用內部熱能回收,節省冰水及溫水供應量。

  14. 3.3節能改善方案 • 利用外氣進入之高溫空氣作交換,使循環水溫度升 高,上升後循環水送到第二道省能盤管。 • 以高溫之循環水將除濕後低溫空氣昇溫至16℃,熱 交換後循環水溫度降低,再送回第一道盤管做預冷。

  15. Heat recover Coil-1 Cooling Coil-1 Heat recover Coil-1 Cooling Coil-2 HEPA Filter Air Washer Heat recover Coil-2 空氣品質之控制 -夏季 Heat recover Coil-1 Outside Air in Summer (35℃, 80%) Cooling Coil-1 Cooling Coil-2 Cleanroom Specification (23 ±1℃, 43 ±5%) Heat recover Coil-2

  16. 改善後之設計 第一道 省能盤管 第二道 省能盤管

  17. 第一道省能盤管 第二道省能盤管 修改後空調箱

  18. 4.節能效益說明 4.1節能說明-冰水耗電量 1.改善後冰水節省能量為每年2,552,994 (KW-Hr) 2.依本廠冰機每KW冰水需求電力為0.16KW 3.每年節省電力為2,552,994*0.16 =408,479 (KW-Hr) 每年節省電費為 408,479 (KW-Hr)*1.8(元/KW-Hr)=735,262元

  19. 4.2節能說明-溫水瓦斯量 1.改善後,熱回收故溫水省能與冰水相同2,552,994 (KW-Hr) 2.天然氣=9.71元/M3,熱值=10.347 KW 3.故每年節省天然氣2,552,994 ÷ 10.347 =246,737 M3 每年節省瓦斯費用 246,737(M3)*9.71(元/M3)=2,395,816元

  20. 4.3投資效益說明 1.改善後,每年可節省電費為735,262元 改善後,每年可節省瓦斯費用為2,395,816元 每年節省費用總共3,131,078元 2.裝設熱回收盤管工程所需費用為2,000,000元 3.回收年限: 2,000,000(元)/ 3,131,078(元/年)= 0.64年

  21. 報告結束,謝謝各位參與