1 / 14

2.0 ANALYSIS AND DESIGN

2.0 ANALYSIS AND DESIGN. 2.2 STRUCTURAL ELEMENT Reinforced Concrete Column. Rearrangement by :- NOR AZAH BINTI AIZIZ KOLEJ MATRIKULASI TEKNIKAL KEDAH. Column is defined as a structural members subjected to compressive force. Strut – a small compressive member in a framed structure.

dara-craft
Download Presentation

2.0 ANALYSIS AND DESIGN

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 2.0 ANALYSIS AND DESIGN 2.2 STRUCTURAL ELEMENT Reinforced Concrete Column Rearrangement by :- NOR AZAH BINTI AIZIZ KOLEJ MATRIKULASI TEKNIKAL KEDAH

  2. Column is defined as a structural members subjected to compressive force. Strut – a small compressive member in a framed structure. Column – a larger member, such as the main support for a beam in a building. INTRODUCTION

  3. Axially loaded compressive member can fail in two principal ways: - short fat member fail by crushing or splitting of the material. - long thin members fail by sideways buckling. INTRODUCTION

  4. i) Braced column(tiangdirembat) – the lateral loads are resisted by wall or some other form of bracing ii) Unbraced column(tiangtidakdirembat) – the lateral loads are resisted by the bending of the column iii) Short Column (tiangpendek) lex/h and ley/b < 15 for a braced column lex/h and ley/b < 10 for an unbraced column iv) Slender(Long) Column ( tianglangsing) lex/h @ ley/b >15 for a braced column lex/h @ ley/b >10 for an unbraced column Types of column

  5. Short column (p> pcr)usually fail by crushing when the material achieved its ultimate strength. Slender column is liable to fail by buckling The end moment on slender column cause it to deflect sideways exceed a critical values until the column buckles. Failure Mode

  6. Slender Column - fails by sideways buckling - The load at which a slender column buckles, is known as its critical buckling load, Pcrit. Pcrit. = ΩEI / L2 Where; E = Modulus of Elasticity I = second moment of area L = length between pins Failure Mode

  7. Column detail

  8. Longitudinal steel bar - A minimum of 4 bars is required in a rectangular column and 6 bars in a circular column. - The size of the bars should be not less than 10mm Links - Minimum size = ¼ x size of the largest compression bar but not less than 6mm - Maximum spacing = 12 x size of the smallest compression bar Reinforcement detail

  9. Types of Reinforced Concrete Column Circular column Rectangular column

  10. Load transfer on column for design

  11. Factored Axial Load (N) for Column Design Interior Column – 1.25 Edge/face column – 1.5 Corner column – 2 Corner column Interior column Edge /face column

  12. Short Axially Loaded Column Design Equation N = 0.4 fcuAconc+0.8 fyAsc Where N – Ultimate Axial load fcu – Characteristic of concrete strength Aconc – area of concrete cross section fy – Characteristic of reinforcement strength Asc – area of reinforcement cross section N

  13. Example: A column with 200 mm x 200 mm resists a factored axial load 500kN. Calculate the area of steel required if fy = 460 N/mm2 and fcu = 30 N/mm2 Table 1 Diameters and areas of reinforcing bars Bar dia.(mm) 6 8 10 12 16 20 25 32 40 C/s area (mm2) 28 50 79 113 201 314 491 804 1256

  14. Formula for design column N = 0.4 fcuAconc+ 0.8 fyAsc 500x103 = 0.4 (30) (40000 - Asc) + 0.8 (460) Asc = 480000 – 12 Asc+ 368 Asc = 480000 + 356 Asc Asc= 56.18mm2 Asc (for each bar) = 56.18mm2/4 = 14mm2 Asc = Πj2= ΠD2/4=14mm2 D = 14 x 4 / Π = 4.22mm Standard required 4 number of steel reinforcement bars size 10mm minimum) . So size column = 4 T 10 4T10

More Related