FWEC max, fanmotor output. I = MAX. 3.2 A No additional power contactor needed !. +. I = MAX. 10 A !!. Power contactor. FWV / FWL / FWM/ FWB /FWD. Remote electronic controller: The EPIMSB6 power interface is used for connecting up to 4 units in parallel to 1 controller.
E N D
FWEC max, fanmotor output I = MAX. 3.2 A No additional power contactor needed ! + I = MAX. 10 A !!
Power contactor FWV / FWL / FWM/ FWB /FWD • Remote electronic controller: • The EPIMSB6 power interface is used for connecting up to 4 units in parallel to 1 controller. • The power interface is to • be installed on a DIN • guide, usually housed in • the electric boards cabinet. • Remote Electronic controller Up to 4 units EPIMSB6
EPIMSB6 EPIMSB6 EPIMSB6 EPIMSB6 Up to three EPIMSB6 can be connected to the FWEC Up to four fancoils (max current < 3,2 A drawn per FCU unit) can be connected to EPIMSB6. So up to twelve units can be controlled by one controller I < 3,2 A
EPIB6 EPIB6 When current drawn by FCU > 3,2 A an EPIB6 needs to be used. Only one FCU can be connected on an EPIB6 I > 3,2A
EPIMSB6 EPIB6 EPIB6 EPIB6 EPIB6 EPIMSB6&EPIB6 Solution when multiple fancoils with current > 3.2A needs to be connected to same control I > 3.2A I > 3.2A I > 3.2A I > 3.2A