530 likes | 1.02k Views
Subpart E of OSHA's 1910 Standard Concerns Safe and Efficient Means of Leaving a Building or Facility in an EmergencyEgress: A place or means of going out.Subpart E contains: definitions general requirements that are fundamental to safe and efficient egress from facilities detailed requirements to ensure qualitative/quantitative factors are covered.
E N D
1. Means of Egress & Fire Protection
3. Why is Important to Properly Mark Exits & Know The Way Out?
5. Each hazard can be compounded by: Panic and confusion
Poor visibility
Lack of information
and/or
Misinformation
6. Subpart E - Means of Egress The 1913 Life Safety Code was used extensively until
1921, when the Building Exits Code became the
comprehensive guide to exits
In 1966 the code was changed again - from the Building
Exits Code to The Code for Safety to Life from Fire in
Buildings & Structures (known as the Life Safety Code)The 1913 Life Safety Code was used extensively until
1921, when the Building Exits Code became the
comprehensive guide to exits
In 1966 the code was changed again - from the Building
Exits Code to The Code for Safety to Life from Fire in
Buildings & Structures (known as the Life Safety Code)
8. Definitions (1910.35)
9. Definitions (1910.35)
10. Means of Egress:General Requirements (1910.36) This subpart contains general fundamental requirements essential to providing a safe means of egress from fire and like emergencies.
These are minimum requirements.
They do not apply to exits from vehicles, vessels, or other mobile structures.
11. Means of Egress:General Requirements (1910.36) Fundamental Requirements:
All buildings, new and old, intended for human occupancy shall have
exits sufficient for prompt and convenient escape in an emergency
exits of a certain design that do not depend solely on any single safeguard
structures that do not cause danger to occupants during periods of escape
12. Means of Egress: Fundamental Requirements:
All buildings, new and old, shall have:
no locks or devices to prevent an exit in an emergency except in specialized facilities (mental, penal, or corrective institutions where attendants are on duty)
clearly visible and understandable means to egress
doorways and passageways that are clearly marked Not an Exit to prevent them from being mistaken for exits
13. Means of Egress: Fundamental Requirements:
All buildings, new and old, shall have:
adequate and reliable illumination for all exits in every building or structure equipped with artificial illumination
fire alarm systems (when a fire may not provide adequate warning to occupants of a building)
emergency provisions that shall not cause a hazard under normal occupancy (i.e., enough exits)
14. During Construction & Repair
15. During Maintenance
16. Means of Egress, General (1910.37)
17. Fire Resistance
18. Means of Egress (1910.37) Rules to observe:
Level exits are limited to the use of no more than 100 persons; inclined exits - 60 persons
The capacity at an exit (means of egress) shall be sufficient for occupant load of a space served
Occupant load is the maximum number of persons that may be in a space at any time
Exits must be readily accessible at all times
19. Means of Egress (1910.37)
20. Exterior Exit Routes
21. Discharge from Exits Must discharge directly to the street, yard, court, or other open space leading to the street
The discharge area (including the street) shall be large enough to accommodate all who leave the building from the exit
Stairs and other exits shall be so arranged as to make clear the direction of exit to the street
22. Means of Egress - A Wrap-up
23. Means of Egress - A Wrap-up
24. Emergency & Fire Prevention Plans (1910.38)
25. Alarm System (1910.165)
26. Evacuation
27. Emergency Training Employees must be trained before implementing emergency plans
Training for each type of disaster response is necessary (so employees know what to do)
Employer shall review emergency plan with each employee when:
the plan is developed
employee responsibilities or actions change
the plan is changed
28. Personal Protection
29. Medical Assistance Employers are required to have:
-- personnel trained to render first aid
-- eye wash stations (where employees are
exposed to corrosive materials)
-- the ready availability of medical personnel
for advice and consultation on matters
of employee health (health care does
not need to be provided, but medical help
must be available to resolve problems
30. Fire Prevention Plan
31. Fire Prevention Plan
32. Fire Protection - Subpart L 1910.155 - Scope, Application & Definitions
1910.156 - Fire Brigades
1910.157 - Portable Fire Extinguishers
1910.158 - Standpipe & Hose Systems
1910.159 - Automatic Sprinkler Systems
1910.160 - Fixed Extinguishing Systems, General
1910.161-163 (Other types of fixed systems)
1910.164 - Fire Detection Systems
1910.165 - Employee Alarm Systems
33. Fire Protection - Definitions
34. Fire Protection - Definitions
35. Fire Protection - Definitions
36. Fire Protection - Definitions Class D Fire - A fire involving combustible metals such as magnesium, titanium, zirconium, sodium, lithium and potassium.
Extinguisher rating - The numerical rating given to an extinguisher which indicates the extinguishing potential of the unit based on standardized tests developed by Underwriters Laboratories Inc.
37. Fire Brigades - 1910.156 Fire Fighting Equipment:
Shall be maintained and inspected at least annually
Portable fire extinguishers and respirators shall be inspected at least monthly
38. Portable Fire Extinguishers - 1910.157
39. Portable Fire Extinguishers - 1910.157
40. Portable Fire Extinguishers - 1910.157
41. Portable Fire Extinguishers - 1910.157
42. Automatic Sprinkler Systems - 1910.159 Complete coverage is necessary
Equipment and devices must be approved
Systems must be properly maintained
A main drain flow test must be performed on each system annually
The inspectors test valve shall be opened at least every two years to assure proper system operation
New systems shall have proper acceptance tests conducted
43. Automatic Sprinkler Systems - 1910.159 Sprinkler system must provide at least 1 automatic water supply for at least 30 minutes
To prevent interference and provide for a maximum protection area, the vertical clearance between sprinklers and material below shall be at least 18 inches
44. Fixed Extinguishing Systems, General - 1910.160 Systems using dry chemical, gaseous agents, water spray and foam are regulated by 1910.161 through 1910.163
Fixed systems must be designed and approved for use on the specific fire hazards they are expected to control
If the system becomes inoperable, employer must:
Notify employees
Take precautions to assure their safety (install temporary system, etc.)
45. Fixed Extinguishing Systems, General - 1910.160 Except where discharge is immediately recognizable, a distinctive alarm or signaling system shall be provided
Safeguards must warn employees against entry into hazardous discharge atmospheric areas
Hazard warning or caution signs shall be posted at the entrance to, and inside, areas protected by use of agents in hazardous concentrations
Systems must be inspected annually by a knowledgeable person
46. Fixed Extinguishing Systems, General - 1910.160 Total Flooding Systems:
Emergency action plan for each area required where agent concentrations exceed maximum safe levels (as specified in 1910.162(b)(5) and (b)(6))
Pre-discharge alarm needed for all systems
Alarm must be seen above ambient light or noise levels
Alarm must give employees time to safely exit from the discharge area prior to discharging
47. Fixed Extinguishing Systems, General - 1910.160 Total Flooding System:
Automatic system actuation shall be provided by an approved fire detection device interconnected with the pre-discharge employee alarm system
48. Fire Detection Systems - 1910.164
49. Fire Detection Systems - 1910.164
50. Employee Alarm Systems - 1910.165
51. Employee Alarm Systems - 1910.165
53. Hour 3 Quiz - Answers 1. False. Means of egress must be from any point in a building or structure - not a specific point.
2. C.
3. True.
4. C.
5. C.