1 / 41

Concept of a Wide Area Defense System for the Power Grid

Concept of a Wide Area Defense System for the Power Grid. Chen- Ching Liu University College Dublin National University of Ireland, Dublin. Seminar at NTUA and IEEE PES Greece, June 2009. Catastrophic Power Outages.

eara
Download Presentation

Concept of a Wide Area Defense System for the Power Grid

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Concept of a Wide Area Defense System for the Power Grid Chen-Ching Liu University College Dublin National University of Ireland, Dublin Seminar at NTUA and IEEE PES Greece, June 2009

  2. Catastrophic Power Outages

  3. Western Electricity Coordinating Council (WECC) system - Aug 10th, 1996 Blackout Initiating events Blackout System becomes unstable 15:48 p.m. Keeler-Allston 500-kV line contacts a tree due to inadequate right-of-way maintenance. Additionally the Pearl-Keeler line is forced out of service due to the Keeler 500/230-Kv transformer being OOS. Mild .224 Hz oscillations were seen throughout the system and began to appear on of the PDCI. The WECC broke into 4 asynchronous islands with heavy loss of load. 7.5 million people lost power. Shunt capacitor banks were switched in to raise the voltage but the oscillations were not being damped. With the loss of these 2 lines, 5 lines are now out of service, removing hundreds of MVAR. 15:48:51 p.m. Oscillations on the POI reached 1000MW and 60-kV peak-to-peak. WA MT ND Lines throughout the system begin to experience overloads as well as low voltage conditions. Additional lines trip due to sagging. OR ID PDCI Remedial Action Schemes (RAS) began to actuate. Shunt and series capacitors were inserted. SD WY NV NE UT CO CA 15:47:40-15:48:57 p.m. Generators at the McNary power house supplying 494 MVAR trip. The system begins to experience “mild oscillations”. AZ NM

  4. Eastern Interconnection –August 14th, 2003 Blackout Blackout Initiating events System becomes unstable 265 power plants tripped off line and 50 million people are without power. 1:07 p.m. FE turns off their state estimator for troubleshooting. 4:05:57 p.m. The loss of 138-kV lines overloads the Sammis-Star line. 1:31 p.m. Eastlake 5 generation unit trips and shuts down. 2:02 p.m. Stuart-Atlanta 345-kV line tips off due to contact with a tree. 4:08:59 p.m. Galion-Ohio and Central-Muskinghun 345-kV lines trip on Zone 3 causing major power swings through New York and Ontario and into Michigan. 2:14 p.m. FE’s control room lost alarm functions followed by a number of the EMS consoles. Low voltage/ high load conditions and system disturbances propagate through the system tripping transmission lines and generators. ME ND VT MN NH MI SD NY MA WI CT RI 2:54 p.m. The primary and secondary alarms servers failed. IA PA NE NJ OH DE IL IN MD WV VA KS MO KY 3:05:41-3:57:35 p.m. 3 345-kV lines trip due to contact with trees. This overloads the underlying 138-kV system and depressed voltages. 4:13 p.m. most of the North East and parts of Canada blacked out. There are only a few islands which remain operating. NC TN OK AR SC GA AL MS LA FL 3:39:17-4:08:59 p.m. 16 138-kV lines trip due to overloading.

  5. Hydro-Québec Blackout-April 18th, 1988

  6. Blackout Propagation(without defense systems) Complete System Collapse Triggering Event

  7. Occurrences and Extent of Blackouts in North America 1000 Number of Blackouts 100 10 100 102 104 106 108 Number of customers affected

  8. Strategic Power Infrastructure Defense (SPID) Design self-healing strategies and adaptive reconfiguration schemes • To achieve autonomous, adaptive, and preventive remedial control actions • To provide adaptive/intelligent protection • To minimize the impact of power system vulnerability

  9. SPID System Fast and on-line power & comm. system assessment Hidden failure monitoring Adaptive: load shedding, generation rejection, islanding, protection

  10. Knowledge/Decision exchange Plans/Decisions Check Consistency Update Model Triggering Events Controls Events/Alarms Inhibition Signal Controls Inputs Hidden Failure Monitoring Agents Vulnerability Assessment Agents Power System Reconfiguration Agents Event Identification Agents Planning Agent Comm. Agent Restoration Agents Command Interpretation Agents Model Update Agents Event/Alarm Filtering Agents Frequency Stability Agents Fault Isolation Agents Protection Agents Generation Agents Multi-Agent System for SPID DELIBERATIVE LAYER COORDINATION LAYER REACTIVE LAYER

  11. Multi-Agent System for SPID Global View/Goal(s) Load Shedding Agent Inhibition Signal Under Frequency Relay Local View/Goal(s) Tripping Signal R Subsumption Architecture (Brooks) for Coordination Agents in the higher layer can block the control actions of agents in lower layers

  12. Cascaded Events • Some Basic Patterns • Line tripping due to overloading • Generator tripping due to over-excitation • Line tripping due to loss of synchronism • Generator tripping due to abnormal voltage • and frequency system condition • Under-frequency/voltage load shedding Identifying the basic patterns of cascaded events and explore how these patterns can be combined into sequences

  13. Cascaded Zone 3 Operations Zone 3 Relay Operations Contributed to Causes of Blackouts. Heavy Loaded Line Low Voltage High Current Zone 3 Relay Operation(s) Lower Impedance Seen by Relay Loss of Transmission Lines Other Heavy Loaded Lines Catastrophic Outage

  14. Prediction of Zone 3 Relay Tripping Based on On-Line Steady State Security Assessment Contingency Evaluation Performed On Line Every Several Minutes Contingency Evaluation … Post-Contingency Power Flow FIS Post-Contingency Apparent Impedance Fuzzy Inference System (FIS) Developed Using Off-Line Time-Domain Simulations Corrected Post-Contingency Apparent Impedance

  15. Impedances Obtained by Power Flow and Time Domain Simulation Post-Contingency Impedance Obtained by Power Flow Does Not Coincide with Impedance Obtained by Time-Domain Dynamic Simulations

  16. Automatic Development of Fuzzy Rule Base Wang & Mendel’s algorithm is a “learning” algorithm: 1) One can combine measured information and human linguistic information into a common framework 2) Simple and straightforward one-pass build up procedure 3) There is flexibility in choosing the membership function Pre-determine number of membership functions N Give input and output data sets FIS created automatically (Inp1, Inp2, Out) = (10, 1, -2) (Inp1, Inp2, Out) = (8, 3, -1) (Inp1, Inp2, Out) = (5, 6, -4) (Inp1, Inp2, Out) = (2, 8, -5) … In this example, N is 7

  17. Case A Fault Location Relay Location

  18. Impedance on R-X (Case A) Z obtained by power flow solution is outside Zone 3 circle. Case A

  19. Load Shedding • Studies have shown that the August 10th 1996 blackout could have been prevented if just 0.4% of the total system load had been dropped for 30 minutes. • According to the Final NERC Report on August 14, 2003, Blackout, at least 1,500 to 2,500 MW of load in Cleveland-Akron area had to be shed, prior to the loss of the 345-kV Sammis-Star line, to prevent the blackout.

  20. Automatic Load Shedding • Under Voltage • Under Frequency • Rate of Frequency Decrease • Remedial Action Scheme

  21. Adaptive Self-healing:Load Shedding Agent • A control action might fail • Unsupervised adaptive learning method should be deployed • Reinforcement Learning • Autonomous learning method based on interactions with the agent’s environment • If an action is followed by a satisfactory state, the tendency to produce the action is strengthened

  22. Load Shedding Options frequency Time (multiples of 0.02 sec)

  23. Adaptive Self-healing:Load Shedding Agent • 179 bus system resembling WSCC system • ETMSP simulation • Remote load shedding scheme based on frequency decline + frequency decline rate • Temporal Difference (TD) method is used for adaptation: Need to find the learning factor for convergence

  24. Adaptive Load Shedding Agent 179 bus system

  25. Adaptive Load Shedding Agent Expected normalized system frequency that makes the system stable “The load shedding agent is able to find the proper control action in an adaptive manner based on responses from the power system” Normalized frequency Number of trials

  26. Flexible Grid Configuration to Enhance Robustness • Flexible Grid Configuration can play a significant role in defending against catastrophic events. • Power infrastructure must be more intelligent and flexible. • To allow coordinated operation and control measures to absorb the shock and minimize the potential damages caused by radical events .

  27. Cascading Events • A Cascading Event Refers to a Series of Tripping Initiated by One or Several Component Failures in a Power System • Here the initial component(s) failure is designated as “shock” to the power infrastructure

  28. Simulated Cascading Events (179 Bus System) • Compute Power Flows after Tripping • Six lines are found on limit violation • Trip these lines • Identify New Network Configuration and Solve Power Flows Again • Fifteen lines are found with limit violations • Trip these lines • Continue This Simulation Procedure • Finally system collapses: most transmission lines are tripped and most loads are lost

  29. 2-Area Partitioning Algorithm (from VLSI) • Spectral 2-way Ratio-Cut Partitioning • Theorem Given an edge-weighted graph G = (V, E), the second smallest eigenvalue λ2 of the graph’s Laplacian matrix Q yields a lower bound on the cost c of the optimal ratio cut partition, with c = e(U,W)/(|U|·|W|) ≥ (λ2/n) • Cut-Size: e(U,W) ≥ (λ2/n) (|U|·|W|)

  30. Area-Partitioning Algorithm 6-Bus System

  31. Partition {U, W} Cut Set Size e(U,W) e(U,W) / (|U|·|W|) λ2 / n {(4), (5 6 3 2 1)} 1.1 1.1 / (1  5) = 0.22 {(4 5), (6 3 2 1)} 1.2 1.2 / (2  4) = 0.15 {(4 5 6), (3 2 1)} 0.3 0.3 / (3  3) = 0.0333 0.1966 / 6 = 0.0328 {(4 5 6 3), (2 1)} 2.1 2.1 / (4  2) = 0.2625 {(4 5 6 3 2), (1)} 1.1 1.1 / (5  1) = 0.22 Area-Partitioning Algorithm Partition Results of 6-Bus System

  32. Flexible Grid Configuration to Absorb the Shock • Solve Power Flows of Area One • All 35684.71 MW loads are supplied, no line flow constraints violations • Solve Power Flows of Area Two • Seven lines on limit violation: • (Bus158-Bus164), (163-8), (64-163), double lines (16-19), and double lines (150-154)

  33. Bus # Original Load (MW) Load Shed (MW) Load Supplied (MW) 8 239 188 51 16 793.4 64.4 729 154 1066 60 1006 Flexible Grid Configuration to Absorb the Shock • Use “Power Redispatching & Load Shedding” in Area Two • Totally, 188 + 64.4 + 60 = 312.4 MW load are shed

  34. Split System into Two Areas

  35. Flexible Grid Configuration to Absorb the Shock • Shed Load vs. System Total Load • K=1 • K=2 • K=3 

  36. Flexible Grid Configuration to Avoid Cascaded Failures • Step 1 : Compute power flows after initial tripping event(s). • Step 2 : Convert power network to an edge-weighted graph G, weight of each edge is absolute value of real power flow. • Step 3: Multilevel graph partitioning with minimum edge-cut. • Network is separated into k areas to minimize generation / load imbalance. • Graph COARSENED to a smaller number of vertices, • Bisection PARTITIONING of much smaller graph, • UNCOARSENING back toward original graph. • Coarsest graph small, Coarsening can be parallelized, Partitioning efficiency high.

  37. Emergency Control with Multilevel Graph Partitioning • Partitioning a 22,000 bus and 32,749 branch system into 2, 3, 4 islands with 0.07s, 0.081s and 0.09s on 2 GHz Pentium CPU and 1GB RAM. • Fast computational speed makes it possible to determine partitioning strategy and identify new network configuration in on-line environment. An adaptive relaying architecture for controlled islanding • CCUs acquires system data, generates system separation strategy. • SCUs receive system separation commands from CCU and send breaker opening commands to specific auxiliary relays.

  38. Flexible Grid Configuration to Avoid Cascaded Failures • Controlled islanding on a 200-bus system: • 199 buses, 31 generators, 248 branches. • Sequence of cascading events: • At t=0 s, three transmission lines out-of-service. • At t=60 s, line 72-197 tripped due to line fault. • At t=120 s, line 78-196 tripped due to line fault. Generator G70 at bus 70 overloaded. • At t=240 s, generator G70 tripped by over-excitation protection. At t= 260 second, system collapses.

  39. Flexible Grid Configuration to Avoid Cascaded Failures Load bus voltages without/with islanding strategy • System islanding initiated at 241s. • Islanding strategy results in balanced generation / load in both islands. • All loads in the system are served. Load shedding scheme not applied. • Islanding strategy successfully prevents the collapse of the system.

  40. Conclusion • Cascading failures remain a grand challenge • New communication, information and computer technologies enable wide area protection and control • Connectivity also brings cyber vulnerability • “Smart” grid? • “Self-healing” grid?

  41. Further Information • J. Li, C. C. Liu, “Power System Reconfiguration Based on Multilevel Graph Partitioning,” IEEE PES Power Tech, Bucharest, Romania, 2009. • K. Yamashita, J. Li, C. C. Liu, P. Zhang, and M. Hafmann, “Learning to Recognize Vulnerable Patterns Due to Undesirable Zone-3 Relay Operations,” IEEJ Trans. Electrical and Electronic Engineering, May 2009, pp. 322-333. • J. Li, K. Yamashita, C. C. Liu, P. Zhang, M. Hoffmann, “Identification of Cascaded Generator Over-Excitation Tripping Events,” PSCC, Glasgow, U.K., 2008. • H. Li, G. Rosenwald, J. Jung, and C. C. Liu, “Strategic Power Infrastructure Defense,” Proceedings of the IEEE, May 2005, pp. 918-933. • J. Jung, C. C. Liu, S. Tanimoto, and V. Vittal, “Adaptation in Load Shedding under Vulnerable Operating Conditions,” IEEE Trans. Power Systems, Nov. 2002, pp. 1199-1205. • H. You, V. Vittal, J. Jung, C. C. Liu, M. Amin, and R. Adapa, “An Intelligent Adaptive Load Shedding Scheme,” Proc. 2002 PSCC, Seville, Spain, June 2002. • C. C. Liu, J. Jung, G. Heydt, V. Vittal, and A. Phadke, “Strategic Power Infrastructure Defense (SPID) System: A Conceptual Design,” IEEE Control Systems Magazine, Aug. 2000, pp. 40-52.

More Related