RPEWG Palo Verde – North Gila #2 Upgrade Request

RPEWG Palo Verde – North Gila #2 Upgrade Request. PCC 10.06. RPEWG. APS Proposed new 500kV circuit Hassayampa – North Gila #2 Full length, 117 miles, in Common Corridor Approval Process RPEWG RS PCC Board. RPEWG. RPEWG Members Brian Keel – SRP – Chair Nevida Jack – SRP

efuru
Download Presentation

RPEWG Palo Verde – North Gila #2 Upgrade Request

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. RPEWGPalo Verde – North Gila #2Upgrade Request PCC 10.06

  2. RPEWG • APS • Proposed new 500kV circuit • Hassayampa – North Gila #2 • Full length, 117 miles, in Common Corridor • Approval Process • RPEWG • RS • PCC • Board

  3. RPEWG • RPEWG Members • Brian Keel – SRP – Chair • Nevida Jack – SRP • Baj Agrawal – APS • Sara Majok – SMUD • Brad Bentley – SDGE • Donald Davies – WECC • Mohan Kondragunta - SCE

  4. RPEWG • Seven Step Process for Performance Category Upgrade Request – PCUR • Phase I of Probabilistic Based Reliability Criteria Implementation Procedure, JUN 2001 • Step 1 • Project Description • Step 2 • Outage Database • Actual data if available • If not exist, use similarly situated lines • Step 3 • MTBF Calculation

  5. RPEWG • Step 4 • Robust Line Design • In event an MTBF calculation is not possible due to limited data, an upgrade application may be made using only the Robust Line Design Features.

  6. RPEWG • Robust Line Design • Risk Factors R1 – R11 • Risk of fire, falling tower, lightning striking at same time, station related, natural disasters, aircraft, vandalism, vegetation or single breaker fail • Design Variables D1 – D18 • Breaker configuration, tower spacing and design, shield wires, grounding, protective relaying, etc. • WECC Board Approved 12.05.03

  7. RPEWG • Step 5 • Exposure Analysis • Hours per year customers exposed to compliance violation • Step 6 • Consequences of Outage • Step 7 • Final Report

  8. RPEWG • Conference Call JUN 20 • Intro & review Process • Meeting with RPEWG JUL 28 • Presentation by APS & Q & A • Conference Call AUG 10 • RPEWG Approval vote • Reliability Subcommittee Vote • 8.17.06 Approval