What you will learn. L7224U Product OverviewKey FeaturesInstallationSet UpTroubleshootingProduct Cross ReferenceL7224U Advantages. L7224U Universal Electronic Aquastat?. What is the L7224U1002?Universal electronic Aquastat that provides circulator, burner and boiler temperature control with electronic temperature sensing in an oil fired hydronic heating appliance. Provides status and diagnostic information through an LED display to enhance the diagnostic process..
E N D
1. Universal Electronic Aquastat®L7224U1002Training Module
2. What you will learn L7224U Product Overview
Key Features
Installation
Set Up
Troubleshooting
Product Cross Reference
L7224U Advantages
3. L7224U Universal Electronic Aquastat® What is the L7224U1002?
Universal electronic Aquastat that provides circulator, burner and boiler temperature control with electronic temperature sensing in an oil fired hydronic heating appliance.
Provides status and diagnostic information through an LED display to enhance the diagnostic process.
4. Aquastat® Key Features
5. L7224U Universal Electronic Aquastat Why choose the Honeywell L7224U1002?
Universal Compatibility
Replaces over 40 existing Honeywell controls
Easy Installation
Redesigned to simplify wiring
Direct or remote mount
Superior Performance and Accuracy
+/- 2 degree accuracy
Multi-Function LED Display
Speeds installation and troubleshooting
Push button product set up & configuration
Get set point, temperature and diagnostic info
EnviraCOMTM communications enabled
Easily add outdoor reset with 3 wires
Remote diagnostics
OnWatch Diagnotic compatible
6. Additional L7224U features Remote 48” sensors available
One Amp slow-blow fuse
Improved terminal layout and multiple knockouts
Vertical, Horizontal, and Flush-Mounting - configurable for single-function use
Low Limit can be disabled (cold start boiler applications)
Outdoor reset functionality enabled when combined with W8735S1000 AquaReset® kit
7. L7224U Features
8. Ranges and Ratings
9. Installation
10. Wiring of the L7224U
11. Wiring of the L7224U -- Thermostat
12. Wiring of the L7224U – Line Voltage
13. Connecting AquaReset®
14. Connecting AquaReset®
15. Set Up
16. Set Up of the L7224U To adjust the settings
Press the UP, DOWN, and I buttons simultaneously for three seconds
Press the I button until the desired feature is displayed
Then press UP and/or DOWN to move the set points to desired values
After 60 seconds without any buttons pressed, the control automatically goes back to READ mode
Display
In RUN mode the Aquastat will flash boiler temp (bt) followed by the temperature
To read settings press the I key to scroll thought the functions
17. Set Point Adjustments
18. L7224U Electronic Aquastats® (LED LIGHTS)
19. Digital Readout of System Conditions
20. Digital Readout of System Outdoor Reset Functions
21. L7224U Electronic Aquastats® (Digital Readout of System Conditions)
22. Troubleshooting
23. Is there an error code on the display?
Error
Code Cause/Action
Err 1 Sensor fault; check sensor
Err 2 ECOM fault; check EnviraCOM™ wiring
Err 3 Hardware fault; replace control
Err 4 B1 fault; check B1 wiring/voltage
Err 5 Low line voltage; check L1-L2 110 Vac
Err 6 Fuse; check ECOM wires, replace fuse
Err 7 EEPROM, HL, LL, Hdf, Ldf; Reset to default values. Restore desired settings.
Err 8 Repeated B1 fault (voltage present at B1 when output is
turned off); check B1 wiring/voltage Troubleshooting: L7224U Electronic Aquastats® (Error Codes)
24. Is there an error code on the display?
Error
Code Cause/Action
Err 9 Outdoor reset system failure, check wiring
Err 10 Boost Failure, check outdoor reset curve settings
Err 11 Domestic Hot Water module failure, check wiring
Error codes 9, 10 and 11 only apply when AquaReset and/or Domestic Hot Water priority modules connected to Aquastat
Troubleshooting: L7224U Electronic Aquastats® (AquaReset Error codes)
25. Troubleshooting: L7224U Electronic Aquastats®
26. Product Cross Reference
27. Product Cross Reference Where do I find Honeywell universal electronic aquastat cross reference information?
www.customer.honeywell.com
Honeywell Application Selection and Cross
Reference Guide – Form 63-9575
Honeywell Laminated Truck Visor – Form 63-9581O
Honeywell Residential Technical Support: 1-800-468-1502
28. Aquastat® Cross Reference Table
29. www.customer.honeywell.com See Cross Reference Search box in right column.
30. L7224U Advantages When promoting the Honeywell L7224U1002 keep these advantages in mind:
This Universal control replaces over 40 existing Honeywell controls.
Save time searching for the exact replacement parts
Stock less parts on the shelf and in the truck
Installation is easy with this redesigned control.
Wiring has been simplified
Mounting choices - control can be direct or remote mount
Performance and accuracy are superior to past controls.
+/- 2 degree accuracy
The multi-function LED display means less time spent on installation and troubleshooting.
Push button product set up & configuration
EnviraCOMTM communications enabled is an added advantage providing remote diagnostic capabilities.
31. L7224U Universal Electronic Aquastat Knowledge Test Now that you completed this training module, take the short quiz to test your knowledge.
32. Test The L7224U provides temperature control of circulators, burners and boilers with electronic temperature sensing? T of F
The L7224U is considered a single function aquastat which provides high limit and low limit control? T or F
The L7224U is accurate within +/- 2 degrees? T or F
A 48” sensor is available to accommodate application requirements? T or F
Setpoints are easily adjusted with the up and down push buttons? T or F
33. Test The “I” button cycles through settings and conditions? T or F
Error codes can be read only through the LED display? T or F
The low limit can be disabled for a cold start boiler application? T or F
Honeywell provides cross reference information for replacing over 40 existing controls? T or F
The L7224U has a LED light that shows whether the burner is energized? T or F
34. Answer Key T
F
T
T
T
T
F
T
T
T