Sockets AND PLUGES PROBLMES IN THE SAUDI MARKET

Sockets AND PLUGES PROBLMES IN THE SAUDI MARKET The unstandard sockets and plugs could cause many problems not only for human being but also for buildings , factories …..etc and may be all of towns . Many disasters were happened in everywhere around the world because of bad connections.

evan
Download Presentation

Sockets AND PLUGES PROBLMES IN THE SAUDI MARKET

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Sockets AND PLUGES PROBLMES IN THE SAUDI MARKET The unstandard sockets and plugs could cause many problems not only for human being but also for buildings , factories …..etc and may be all of towns . Many disasters were happened in everywhere around the world because of bad connections .

  2. أمثلة من الحرائق الناتجة عن استخدام التمديدات غير المطابقة للواصفات حريق بسبب ماس كهربائي يلتهم برجين في قطر بعد انتهاء 95% من إنشائهما

  3. التماس كهربائي يؤدي إلى نشوب حريق هائل بأحد المحلات

  4. ماس كهربائي يثير الرعب لـ( 3000) طالبة

  5. ماس كهربائي يحرق أحد المراكز التجارية

  6. So, MOWE and SASO cooperated to carry out various tests on 115 random samples from ( sockets , plugs , power bars , and adaptors ) according to the flowing tables :

  7. Test results of Socket samples

  8. Test results of Socket samples

  9. Test results of electric connection& adaptor samples

  10. Test results of electric connection& adaptor samples

  11. Test results of electric plug, double socket and outer frame samples

  12. This study gives the following indicators : • Local samples are not exceeding 20 %. • Complied specimens of socket not exceed 20%. • Complied specimens of plug not exceed 10%. • Complied specimens of power bars not exceed zero %. • Complied specimens of adaptor not exceed zero %.

  13. The results above show that the power bars and adaptors are the very danger things and can cause a disaster in any time when they not comply with the standard.

  14. Tests • Visual inspection • Dimensions • Entrance shape • Dielectric test • Heat resistance test • High voltage test • Measuring of wire cross section .

  15. Insulation resistance test 500V /1min ≥ 5 M Ω . • Dielectric test 2000 V / 1min. • Contact resistance test ≤ 0.05 Ω .

  16. Withdrawal force test .

  17. Resistance to upnormal heat and fire test . • 850 C / 30 sec.

  18. Sockets comply with the specifications

  19. Sockets comply with the specifications

  20. Power bars not comply with the specifications

  21. Adaptors notcomply with the specifications

  22. Bad and danger connections

  23. Power bars not comply with the specifications

  24. Recommendations • All authorities , ministries , and public sectors which care of standards must join to implement and activate the standards . • Support and develop the national laboratories to update the modified standard . • Applying the conformity program to ban the un- complying products . • Improving the local products by complying with Saudi Standard .

  25. Thank you…