250 likes | 416 Views
Large Boilover experiments in Japan. Hiroshi Koseki National Research Institute of Fire and Disaster, Japan. Tomakomai, Japan. Abstracts.
E N D
Large Boilover experiments in Japan Hiroshi Koseki National Research Institute of Fire and Disaster, Japan Tomakomai, Japan
Abstracts • In order to know boilover phenomenon in large tanks, large scale boilover experiments in a 5 m diameter pan using crude oil were conducted. Initial fuel thickness was 0.7m. • To know repeatability we tested twice in the same conditions. • About 80 minutes after ignition, large boilover was occurred. Radiation from fire increased about twenty times as much as that of steady burnings. • Times to boilover were within our expecting which we obtained with smaller pans and other reports.
Background Past boilover accidents in Japan We had twice boilover accidents in Japan • Heavy oil C, Yokkaichi,October 15, 1954 (2) Crude oil, Nigata, June16, 1964 Nigata, June 1964
Earthquake damages in Oil facilities • In Japan we have many earthquakes in Japan • Sometimes, oil tanks were damaged, and some were caught fires • Two Tomakomai fires in 2003 were reported by Mr. Hirai • Nigata earthquake damaged tanks and continued more than two weeks in 1964, and made boilover in crude oil tanks
Recent Fire Tests in Japan • Joint work among NRIFD, U. Tokyo and Oil company 20m pan fire test • Large crude oil fire tests in 20 m pan(1997) • Boilover tests(1999) Tests were conducted in Tomakomai, Hokkaido, Japan 20m pan fire test
Kinds of boilover • Boilover: Fuel layer thickness is 0.55 m Clear hot zone (isothermal zone) is made Our target: 1) normal boilover 2) Effects of water existence Water emulsion crude oil was burnt • Slopover • Frothover • Thin-layer boilover: Fuel layer is very thin
Mechanism of boiloverHigh temperature zone was made after long burn, and then increase its width,Details were shown in many text books
1m pan boilover tests were done in NRIFD large test facilities using several oilsCrude oil, Heavy oil made boilover
1m pan test using Arabian crude oilHot zone was made in NRIFD
Temperature inside the liquid, using keroseneNo hot zone was made
Temperature measurementThermocouples were bedded along with pan pole
Crude oil • Crude oil we used, is equivalent to Arabian light crude oil supplied by Idemitsu Oil Co., which is most popular crude oil. • That is, we bought from Idemitsu Hokkaido Refinary, in which large oil tank fires occurred in 2003.
Results-Fuel and water temperatureHot zone was made and its temperature increase
ConclusionTime to boilover Time to boilover can be estimated with fuel thickness because hot zone regression rate is known from many our data and real accidents. According to API data, we obtain these lines, and our data were within these lines. Time (hour) Fuel thickness (m)
Conclusion • About 70 minutes after ignition, we had boilover, and external radiation increased about 22 times as much as steady burning. • We measured temperature inside the fuel, and found that there might be three steps 1) no isothermal zone was observed 2) Isothermal zone was made, but not high temperature 3) Then, temperature of isothermal zone increased, and reached water layer
Conclusion • Our data support results of our small test and other group did • Data is open, anybody can use our data, because large boilover test is difficult to do so often • Publication: Fire safety Journal vol.41, 2006 • Other information is available Contact me, koseki@fri.go.jp