Annual Fire Door Inspection

Safely Securing the Built Environment. Annual Fire Door Inspection. NFPA 80 & NFPA 101. Introductions. Kurt Roeper – Ingersoll Rand Security Technologies. National Fire Protection Association NFPA 101 – Life Safety Code NFPA 80 – Fire Doors & Rated Opening Protectives

fergus
Download Presentation

Annual Fire Door Inspection

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Safely Securing the BuiltEnvironment Annual Fire Door Inspection NFPA 80 & NFPA 101

  2. Introductions Kurt Roeper – Ingersoll Rand Security Technologies • National Fire Protection Association • NFPA 101 – Life Safety Code • NFPA 80 – Fire Doors & Rated Opening Protectives • NFPA 105 – Smoke Control Door Assemblies • International Code Council – Storm Shelter Committee • Underwriters Laboratories – Standards Technical Panels

  3. NFPA - Annual Fire Door Inspection Today’s Agenda • Background & Context of NFPA Changes • Annual Inspection Requirements • Owner’s Responsibilities • AHJ’s Responsibilities

  4. Why Do We Need This?

  5. Why Do We Need This?

  6. Why Do We Need This?

  7. Why Do We Need This?

  8. Sofa Super Store – Charleston, SC “Investigators Seize More Fire Evidence Items Linked to Possible Code Violations” Charleston Post & Courier August 22, 2007 Jay Lowry, a former Charleston firefighter and fire inspector, said fire doors can serve a vital role in slowing the spread of fire. Keeping exit doors clear also is key because they provide people with a way in and out of a building during emergencies....... “Any businesses out there with locks on their exit doors, I'll tell you, they're setting themselves up for a bad, bad time.”

  9. Fire Door Inspection Process Background & Context Fire Doors are governed by the building code and NFPA throughout design, specification, installation and occupancy permitting.

  10. Fire Door Inspection Process Background & Context Once a Certificate of Occupancy has been issued, the building code is closed. The Fire Code or Life Safety Code is now in effect for the operation and maintenance of the facility.

  11. Fire Door Inspection Process The International Fire Code now contains language requiring post-occupancy inspections of swinging fire doors

  12. Fire Door Inspection Process The Life Safety Code now contains language requiring post-occupancy inspections of swinging fire doors and doors in the means of egress

  13. NFPA 80 2007 – Standard for Fire Doors Chapter 5 Care & Maintenance 5.2.1* Fire door assemblies shall be inspected and tested not less than annually, and a written record of the inspection shall be signed and kept for inspection by the AHJ. 

  14. NFPA 80 2007 – Standard for Fire Doors Chapter 5 Care & Maintenance 5.2.3.1 Functional testing of fire door and window assemblies shall be performed by individuals with knowledge and understanding of the operating components of the type of door being subject to testing. 

  15. NFPA 80 2007 – Standard for Fire Doors Chapter 5 Care & Maintenance 5.1.1.2 The requirements of this chapter shall apply to new and existing installations.

  16. 5.2.4.2 As a minimum, the following items shall be verified:  •  No open holes or breaks exist in surfaces • (2)   Glazing, vision light frames, and glazing • beads are intact • (3)   The door, frame, hinges, hardware, and • noncombustible threshold are secured, • aligned, and in working order • (4)   No parts are missing or broken.  NFPA 80 2007 – Standard for Fire Doors

  17. NFPA 80 2007 – Standard for Fire Doors (4) No parts are missing or broken. 

  18. NFPA 80 2007 – Standard for Fire Doors 5.2.4.2 As a minimum, the following items shall be verified:  (5)   Door clearances do not exceed the clearances listed

  19. NFPA 80 2007 – Standard for Fire Doors Door clearances at the door edge to the frame, on the pull side of the door, do not exceed clearances listed in 4.8.4.1 and 6.3.1.7 • Hollow metal door -1/8” (+/- 1/16”), door to frame and at meeting stiles of pairs – 6.3.1.7 • Wood door - 1/8” maximum, door to frame and at meeting stiles of pairs – 6.3.1.7 • 3/4” between bottom of door and floor or threshold – 4.8.4.1

  20. NFPA 80 2007 – Standard for Fire Doors Chapter 5 Care & Maintenance 5.2.4.2 As a minimum, the following items shall be verified: (6)    The self-closing device is operational 

  21. NFPA 80 2007 – Standard for Fire Doors Self Closing or Automatic Closing? 3.3.101 Self-Closing Doors – Doors that when opened and released return to the closed position 3.3.7 Automatic-Closing Doors – A door that normally is open but that closes when the automatic closing device is activated

  22. NFPA 80 2007 – Standard for Fire Doors Chapter 5 Care & Maintenance 5.2.4.2 As a minimum, the following items shall be verified: (7)    If a coordinator is installed, the inactive leaf closes before active leaf. 

  23. NFPA 80 2007 – Standard for Fire Doors Chapter 5 Care & Maintenance 5.2.4.2 As a minimum, the following items shall be verified:  (8)  Latching hardware operates and secures the door when it is in the closed position. 

  24. NFPA 80 2007 – Standard for Fire Doors Chapter 5 Care & Maintenance 5.2.4.2 As a minimum, the following items shall be verified: (9)   Auxiliary hardware items that interfere or prohibit operation are not installed

  25. NFPA 80 2007 – Standard for Fire Doors Chapter 5 Care & Maintenance 5.2.4.2 As a minimum, the following items shall be verified: (10)  No field modifications to the door have been performed

  26. NFPA 80 2007 – Standard for Fire Doors Chapter 5 Care & Maintenance 5.2.4.2 As a minimum, the following items shall be verified:  (11)  Gasketing and edge seals are inspected

  27. NFPA 80 2007 – Standard for Fire Doors Chapter 5 Care & Maintenance 5.2.2 Performance-Based Option 5.2.2.1 As an alternate means of compliance with 5.2.1, subject to the AHJ, fire door assemblies shall be permitted to be inspected, tested, and maintained under a written performance-based program. 

  28. NFPA 80 2007 – Standard for Fire Doors Chapter 5 Care & Maintenance 5.2.2 Performance-Based Option.  5.2.2.2 Goals established under a performance-based program shall provide assurance that the fire door assembly will perform its intended function when exposed to fire conditions.  5.2.2.3 Technical justification for inspection, testing, and maintenance intervals shall be documented. 

  29. NFPA – Annual Fire Door Inspection

  30. NFPA – Annual Fire Door Inspection AHJ’s Responsibilities

  31. NFPA 80 – Annual Fire Door Inspection Questions Comments Discussion