100 likes | 330 Views
Ultima ® XL/XT Gas Monitors. Ultima XL / XT Gas Monitors. Presentation Overview HART: General Information Network Topology Ultima XL/XT Features Calibration Options Approvals Sales Support . Ultima XL / XT Gas Monitors. General Information HART (Highway Addressable Remote Transducer)
E N D
Ultima XL / XT Gas Monitors • Presentation Overview • HART: • General Information • Network Topology • Ultima XL/XT Features • Calibration Options • Approvals • Sales Support
Ultima XL / XT Gas Monitors • General Information • HART (Highway Addressable Remote Transducer) • MSA device is a slave in a polled network • HART is a software protocol running over 4-20mA Hardware • Point to point • 1200 baud FSK
Ultima XL / XT Features • Non-display versions of XE & XA • Single sensor gas monitor • Enclosure options • Stainless steel - XL • Polycarbonate G.P. - XT • Condulet has openings for: • Sensor entry • Intrinsically Safe HART Port (optional) • Signal and Power Wiring • Internal Push-button & LEDs for Calibration • Available in Remote Condulet Versions
Ultima XL / XT Features Main board configuration • Similar to the Ultima X main board • Single removable design with standoffs • No tools required for insertion into the condulet
Ultima XL / XT Calibration Options • Calibration utilizing: • Internal push-button and LEDs (intrusive) • Portable handheld communicator, host DCS or laptop • Disconnect under power (in-shop calibration) • Sensor X-change program
Ultima XL / XT Global Approvals • FM APPROVAL • US/Canada • Class I Div 1&2 Groups A,B,C,D • Class I Zone 1&2 Groups IIC, IIB, IIA, T6 • Type 4X, IP 66 • Europe • ATEX II 2G 3G EEx d nA [ib] IIC T6 • IP 66 • International • IEC Ex d nA [ib] IIC T6 • IP 66
Ultima XL / XT Sales Support • Customer requirements • HART handheld controller • Must be compatible with the Emerson 375 • Emerson 275 will NOT work • HART Rev 6 or Rev 7 • Latest DD’s downloaded to handheld controller • A Device Description (DD) is an electronic data file prepared in accordance with Device Description Language specifications that describes specific features and functions of a device including details of menus and graphic display features to be used by host applications (including handheld devices) to access all parameters and data in the corresponding device. • Download from Emerson website (or other handheld controller that subscribes to the HART foundation updates) • Through HART membership www.hartcomm2.org • Available from MSA
Detailed device information 4-20 output calibration Alarm set points Calibration Ultima XL / XT Menu Tree