Unity Application Generator. How Can I… Manage devices over Profibus. I have got many devices (field instruments /IOs and some special third party devices) to be connected over Profibus. I want to make each devices available in my architecture so that I can use IO in my control modules. Issue.
E N D
Unity Application Generator How Can I… Manage devices over Profibus
I have got many devices (field instruments /IOs and some special third party devices) to be connected over Profibus. I want to make each devices available in my architecture so that I can use IO in my control modules. Issue
UAG offers a possibility to include devices connected to PLC over Profibus and made it available in architecture so that IOs can be used in control modules. Complete profibus configuration (from ProSoft /SyCon) can be imported directly into UAG. Goal: To import a profibus configuration file from ProSoft. Assign addresses to each device. Use IO variables from each device in control modules Generate application in Unity with IO scanning for Profibus devices and sections. How to do.. Basic explanation
In UAG, a PLC capable of handling profibus module should be configured. Under the PLC, an appropriate module capable of handling Profibus should be inserted. How to do.. In UAG
By left -clicking on the module, a small menu with ProSoft options will appear. “Create Profibus configuration” should be selected. How to do.. In UAG
ProSoft can be opened by clicking “Open Profibus “option How to do.. In UAG /ProSoft
In ProSoft, the master should be configured and address /module position should be adapted. How to do.. In UAG /ProSoft
Addresses of can be found in the “Properties” of CPU in UAG How to do.. In UAG
Addresses window in UAG looks like this: Field-bus addresses should be noted as these are addresses for Profibus How to do.. In UAG
Please use “Configure” option of the Master under ProSoft: How to do.. In UAG /ProSoft
The addresses and module position in ProSoft should be the same as it is given in UAG (see slide 9). How to do.. In UAG /ProSoft
The Profibus nodes can be configured by opening “Configure” on “Profibus DP” in ProSoft This screen will appear: User has to click on “Configure Profibus” How to do..In UAG /ProSoft
Profibus node editor will appear. How to do.. In UAG /ProSoft
User can find all the available profibus nodes – these are SE devices which can be connected to a Profibus. How to do.. In UAG/ProSoft
By “Drag-n-Drop” user can build a complete bus with addresses of each node. How to do.. In UAG/ProSoft
VERY IMPORTANT NOTE: User can include third party devices (like field instruments /drives etc) by importing “GSD files” provided by the supplier. How to do.. In UAG/ ProSoft
User has to save and close the node editor. This screen will appear. By clicking on “Show Unity Map” user can see the addressing in Unity mapping How to do.. In UAG /ProSoft
Unity address mapping User has to close ProSoft.. How to do.. In UAG /ProSoft
System will get back to UAG. User can import “Profibus configuration. UAG will import and a report of import will be generated. How to do.. In UAG
All the Profibus nodes configured inside ProSoft will be appear in UAG. How to do.. In UAG
By using normal “drag-n-drop” function in UAG, variables can be connected to required node in ProSoft. How to do.. In UAG
Unity application can be generated by using “Generate PLC” function in UAG. How to do.. In UAG
UAG will generate all required sections in Unity for communications. Variables will be generated with proper Profibus address. How to do.. In Unity..
Conclusion • In UAG, user can configure Profibus using ProSoft /SyCon tool for Quantum and Premuim PLCs. • Third party devices like field instrumentation can be included by importing related *GSD files into ProSoft afterwards in UAG. • In addition to Profibus devices, Advantys Island can also be included using Advantys software Thanksfor your attention!