1 / 22

Introduction to Construction General Permit Inspections

Introduction to Construction General Permit Inspections. Field Monitoring at Construction Sites. Outline of the Module. Background and summary of requirements Visual Monitoring Water Quality Monitoring Water Quality Sampling Requirements for Risk Levels 2 and 3 Field Equipment

gretel
Download Presentation

Introduction to Construction General Permit Inspections

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Introduction to Construction General Permit Inspections Field Monitoring at Construction Sites

  2. Outline of the Module • Background and summary of requirements • Visual Monitoring • Water Quality Monitoring • Water Quality Sampling Requirements for Risk Levels 2 and 3 • Field Equipment • Calibration and Use of Sampling Equipment • Calibration and Use of pH Meter • Calibration and Use of Turbidity Meters • Selection and Location of Effluent Sampling Locations • Compliance Sampling Data Management • Sampling Results • Sample Naming Convention • Receiving Water Monitoring • Bioassessments

  3. Summary of Monitoring Requirements

  4. Summary of LUP Monitoring Requirements

  5. Reasons for Inspectors to Conduct Field Monitoring or Sampling Identify problems with BMP performance or poor coverage of BMPs Confirm contractor compliance; or Gather evidence of a NAL exceedance or a NEL violation

  6. Storm Water Sampling References • Caltrans Stormwater Monitoring Protocols (Caltrans, July 2003) http://www.dot.ca.gov/hq/env/stormwater/pdf/CTSW-RT-03-105.pdf or, • EPA NPDES Storm Water Sampling Guidance Document (EPA 833-B-92-001, 1992) http://www.epa.gov/npdes/pubs/owm0093.pdf • Surface Water Ambient Monitoring Program (SWAMP) 2008 Quality Assurance Program Plan (QAPrP) http://www.swrcb.ca.gov/water_issues/programs/swamp/tools.shtml#qa

  7. Health and Safety • The inspector must: • Understand and follow safety precautions, • Use proper safety equipment, and • Exercise good judgment when conducting field monitoring activities. • Preparation of Health and Safety Plans is not covered in this training • The inspector should refer to their office’s health and safety program policies and procedures.

  8. Visual Monitoring • Visual monitoring is required of all projects. • Inspectors should be familiar with the CGP requirements for visual monitoring of construction sites: • Pre-Rain Event; within 48 hours in advance of predicted qualifying rain event (e.g., when NOAA predicts a probability of precipitation of 50% or more in the project area) • Daily-Rain Event; during every extended rain event • Post-Rain Event; within 48 hours following an actual qualifying rain event • Non-Storm Water Inspections; Routine quarterly non-storm water inspections of all project drainage areas • Weekly Visual; year round

  9. Risk Level 2 Monitoring Requirements

  10. Risk Level 3 Monitoring Requirements

  11. LUP Monitoring Requirements

  12. LUP Monitoring Requirements

  13. Required Field Equipment • Personal protection equipment (PPE) as required by the inspector’s organization Health and Safety Plan • Latex Gloves • Safety Glasses • Hard hat and vest (per site requirements) • Proper shoes • Sample collection device(s) • Sample collection pole or rope. • Dippers • Beakers • Sheet flow sampler

  14. Required Field Equipment • Onsite testing equipment • Handheld pH meter (e.g. LaMotte Model# 2020 or equivalent) • Handheld turbidity meter (e.g. Oakton Eco-Testr pH #WD-35423-10 or equivalent)Standard calibration solutions (per manufacturer’s instructions) • Spare batteries • Other supplies • Plastic squirt bottle for rinsing probes filled with distilled water • Lab wipes for blotting probes dry between uses • Sampling jars and tubes (usually lab provided) if Suspended Sediment Concentrations (SSC) or other parameters are required.

  15. Calibration and Use of pH Meter • Proper calibration is required • pH measurements may be used for potential compliance or enforcement actions, • Calibration should be carefully documented in the inspector’s field log book. • Calibrate prior to each daily use • Calibrating a pH probe typically requires three standard solutions of known pH. • Acidic pH=4, • Neutral pH=7, and • Basic pH=11

  16. Calibration and Use of pH Meter • Run the calibration program for the meter and follow the instructions to calibrate. • Immerse the probe in a solution when prompted to by the program. • Probe should be clean prior to calibration, and rinsed clean and blot dried between immersions into the calibration solutions. • Measurements • Samples should be contained in a beaker or other approved sample container.  • Place the pH probe in the sample, above the bottom and away from the sides of the beaker and take a reading. • Probe should be rinsed and blot dried between measurements. • Record the reading with information on the sample, date, time, and construction site.

  17. Calibration and Use of Turbidity Meters • Inspectors should carefully follow the manufacturer’s instructions for the calibration and use of turbidity meters. • Daily calibration prior to testing any site sample • Calibration typically uses a minimum of two standards • Run the calibration program for the meter and follow the instructions to calibrate. • Ensure that the calibration standard vial is clean and free of scratches, moisture, lint, or fingerprints which could impact the reading.

  18. Calibration and Use of Turbidity Meters • Measurements • Handheld turbidity meters typically require filling a glass vial with a representative sample of the discharge • Make sure no bubbles are trapped in the sample vial and that the outside of the vial is completely clean, free of scratches, moisture, lint, or fingerprints which could impact the reading • Sample should be swirled prior to insertion into the meter so that it remains well mixed during the measurement. • If the sample readings are outside of the calibration standard limits, recalibrate with a different standard

  19. Calibration and Use of Turbidity Meters • Measurements • If the sample readings are outside of the calibration standard limits, recalibrate with a different standard • The sample vial should be rinsed between measurements and blot dried with lab wipes • A field blank should be created by filling the glass vial with distilled water after triple rinsing • Field blank measurements should be <0.1 NTU and • Conducted every 10 field measurements. • The turbidity meter calibration should be re-checked for calibration drift, typically at the end of each day’s use • Inspector should always diligently record the results of any field blanks, calibration, and standards measurements

  20. Selection and Location of Effluent Sampling Locations • The inspector should pay close attention to the following conditions or areas (hot spots) at a construction site that may cause sediment, silt, and/or turbidity in storm water discharges: • Exposed soil areas with inadequate erosion control measures; • Areas of active grading; • Poorly stabilized slopes; • Lack of perimeter sediment controls; • Areas of concentrated flow on unprotected soils; • Poorly maintained erosion and sediment control measures; • Tracking sediment onto roads and paved surfaces   • At minimum, the inspector should evaluate the site’s indicated sampling locations as valid and representative of the effluent, and sample at similar locations.

  21. Receiving Water Monitoring • Required at Risk Level 3 sites if a NEL is exceeded and there is a direct discharge to receiving waters. • Monitoring required for turbidity and SSC (if turbidity NEL exceeded), and pH (if pH NEL exceeded). • Sampling is required upstream and downstream of point of discharge in to receiving water. • Typically conducted by a water quality specialist retained by the discharger. • The inspector should review the monitoring procedures and verify that the procedures are being followed. • The inspector may want to collect a grab sample at the monitoring location(s) to confirm that the discharger is accurately reporting the results

  22. Bioassessments • Typically will be executed by a specialty contractor, not covered in this training • Required at Risk Level 3 sites where the ground disturbance is greater than 30 acres • Upstream of the project discharge • Downstream of the projects discharge • Any freshwater wadeable stream listed as impaired due to sediment • Any freshwater stream tributary to a water body that is listed as impaired due to sediment • The inspector might verify that: • The site meets the minimum criteria for requiring a bioassessment • Sampling locations are correctly located relative to the construction site • Proper bioassessment procedures and QA/QC procedures are being followed

More Related