Duct Free System

Duct Free System. DFS Long Line Guide. DFS Long Line Guide. DFS Long Line Guide. “ accessories ”. DFS Long Line Guide. “ all specifications ”. DFS Long Line Guide. “ DFS Pistons…”. New DFS Puron Units. 40/38 MVC & 40/38MVQ. Carrier brand picture. DFS PRODUCT CONCEPT.

gusty
Download Presentation

Duct Free System

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Duct FreeSystem

  2. DFS Long Line Guide

  3. DFS Long Line Guide

  4. DFS Long Line Guide “ accessories ”

  5. DFS Long Line Guide “ all specifications ”

  6. DFS Long Line Guide “ DFS Pistons…”

  7. New DFS Puron Units 40/38 MVC & 40/38MVQ

  8. Carrier brand picture DFS PRODUCT CONCEPT • 13 SEER fixed speed, R410A • Carrier • Phase 1: • 115 volt • 9 & 12 KBTU/Hr • Cool only & heat pump • 208/230 volt • 18 KBTU/Hr • Cool only • Phase 2: • 208/230 volt • 12 KBTU/Hr cool only & heat pump • 18 heat pump • 24 KBTU/Hr cool only & heat pump

  9. High wall unit’s Control The remote control and emergency control are the only way to operate and control the highwall units. 76 F set point No wired control available. Remote control only or emergency button. One way communications.

  10. High wall display board ( Cooling and Heat Pump ) 9 K

  11. High wall display board ( Cooling and Heat Pump ) 12 K

  12. High wall display board ( Cooling Only 018 & 024 )

  13. High wall display board ( Cooling and Heat Pump 018 & 024 )

  14. Operating Conditions Cooling: Outdoor Ambient: 55° F – 125° F Low ambient: -20° F to 55° F Indoor Set point range: 64° F – 85° F Heating: Outdoor Ambient: 5° F – 75° F Low ambient: -20° F to 55° F Indoor Set point range: 55° F – 80° F

  15. Operation… Run time: Minimum run time – (3 seconds), none…. Minimum off time – 3 minutes Reversing valve: Energized in the heating mode Temperature offset: 1°C above and below set point. 3.6°F swing

  16. System Wiring 009 & 012 K units Field Wiring 35 VDC 115 V

  17. System Wiring Field Wiring 012 K units 35 VDC 208/230 V

  18. Field Wiring System Wiring 18 & 24 K units 208/230 V The “S” terminal – signal terminal carriers a 24vdc voltage. However if you measure VAC from the “S” terminal to L1 or L2 you will measure approximately 200VAC. There are no amps behind this voltage > 0.5ma.

  19. High wall (system) trouble shooting LED’s indicators: solid or flash code for errors

  20. Line lengths….. Minimum line of 10 feet… Unit’s charged for 25’ If line set is over 25’ a crankcase heater is required…

  21. Service Manual – board voltages

  22. Service Manual – flow charts

  23. Service Manual – flow charts

  24. Service Manual – sequences

  25. Service Manual – sequences

  26. Service Manual – long line/charge

  27. Service Manual – piping diagram

  28. Service Manual – wiring diagram