An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. THE WYOMINGStorage Tank Program

  2. BEFORE THE PROGRAM • Tanks were installed without corrosion protection • Filling was done without concern about overfilling • Lines often leaked without being detected because inventory was not carefully checked

  3. RESULTING IN: • Inventory losses due to leakage • Explosions caused by vapors • Contaminated water supplies • Vapors in basements, storm sewers and utilities • Cancer and other serious health problems • Financial Ruin for those responsible for Tanks The Wyoming Water Quality Division, Storage Tank Program, 122 West 25th Street, Cheyenne, WY 82002 (307) 777-7095 and (307) 777-5973 (FAX) and blucht@missc.state.wy.us FOR MORE INFORMATION...

  4. You will find references to Wyoming State regulations and statutes in • this space >> • Each of those references has a link to the actual text of those rules and statutes. On the next screen you will find the “Requirements for Underground Storage Tanks”. Each of those requirements has a link to allow you to start viewing at any of them. This presentation is designed to be viewed without sound.

  5. Requirements for Underground Storage Tanks REQUIRED BY ARTICLE 14, ENVIRONMENTAL QUALITY ACT AND CHAPTER 17 • Annual Registration • Annual Fee • Leak Detection for all Tanks • Leak Detection for all Connected Lines • Minimum Site Assessment • Financial Responsibility • Corrosion Protection • Spill Prevention Equipment • Overfill Prevention Equipment • Permanent Abandonment of Out of Service Tanks • Reporting and Investigation of Suspected Releases

  6. Annual Registration REQUIRED BY W.S. 35-11-1425 and CHAPTER 17, SECTION 7 (B) • Name and Address of Owner/Operator • Location, size, & types of Tanks • Type of Substance Stored The Wyoming Water Quality Division, AUST Program, 122 West 25th Street, Cheyenne, WY 82002 (307) 777-7095 (307) 777-5973 (FAX) and blucht@missc.state.wy.us FOR MORE INFO...

  7. Tank Fees REQUIRED BY W.S. 35-11-1425 • Underground tanks: • Owners pay $200.00 per tank per year • Out of Service Tanks: • Owners pay until removed • Aboveground tanks under 5000 gallons: • Owners pay $50.00 per tank per year • Aboveground tanks over 5000 gallons: • Owners pay $200.00 per tank per year

  8. Leak Detection • At least one method of leak detection is required for the Underground Storage Tank itself. • And… • At least one method of leak detection is required for any underground lines attached to the tank.

  9. deq: Need a Hotlink on each of these Leak Detection Methods - Tanks REQUIRED BY CHAPTER 17 SECTION 14(a) • Manual Tank Gauging • Inventory Control • Tank Tightness Testing • Automatic Tank Gauging • Statistical Inventory Reconciliation • Interstitial Monitoring • Vapor Monitoring Wells • Groundwater Monitoring Wells

  10. MANUAL TANK GAUGING REQUIREMENTS FOR THIS METHOD ARE IN CHAPTER 17 SECTION 16(b) • Manual Tank Gauging or Manual Inventory Control alone for tanks under 1000 gallons • Manual Inventory Control & Tank Tightness Testing for tanks of 1000 to 2000 gallons • Tank Tightness Testing • Overfill • Underfill • Tracer

  11. MANUAL TANK GAUGING REQUIREMENTS FOR THIS METHOD ARE IN CHAPTER 17 SECTION 16 (b) • Requires Shut-in of Tank for a minimum of 36 hours and up to 58 hours depending on size of the tank • Stick Readings taken twice at the beginning of the shut-in period and twice at the end of the shut-in period • Stick Readings must be accurate to 1/8” • Must be done once a week • Usually done on small waste oil tanks

  12. INVENTORY CONTROL REQUIREMENTS FOR THIS METHOD ARE IN CHAPTER 17 SECTION 16 (a) • At least seven stick readings per month and one stick reading for every day of active use • Deliveries preceded by two stick readings and ended with two stick readings • Reconciled both daily and monthly • Inventory must balance within 1% of inventory flow through plus 130 gallons • Stick readings must be accurate to 1/8”

  13. INVENTORY CONTROL • If you are using inventory control in conjunction with an automatic tank gauge, use the automatic tank gauge instead of sticking the tank manually. • If you have a point of sale cash register, use the sales numbers from that system, converted to gallons. • You must close both your sales numbers and your delivery numbers at the same time each day.

  14. TANK TIGHTNESS TESTING • Provided by an outside company • Types: • Underfill • Overfill • Ullage • Tracer Tight Surveys

  15. Underfill Tank Tightness Tests In the Under fill method, a probe of some type is inserted into the tank to accurately measure product level during a shut-in period. The tank is first filled to near its capacity...

  16. Overfill Tank Tightness Tests In the Over fill method, a tube is connected to the tank to accurately measure product level during a shut-in period. The tank is first filled to the top...

  17. Ullage Tank Tightness Tests In the Ullage method, the tank is pressurized with nitrogen with all the vents and product lines blocked. A microphone inside the tank is used to listen for noise caused by leaks. The ullage is the space in the tank above the product level...

  18. Tracer Tight Tank Surveys In the Tracer Tight method the product in the tank is first “inoculated” with a very volatile organic tracer, which is not normally present in fuel. About a week later, the tester returns to try and find the tracer in the soils around tank tanks and/or lines.

  19. Automatic Tank Gauges REQUIREMENTS FOR THIS METHOD ARE IN CHAPTER 17 SECTION 16 (d) • Measure only the volume of product in the tank. Cannot determine if lines are intact and cannot detect holes above the product surface • Two Types: • Earlier Types shut-in the tank once a day • Continuous Statistical Leak Detection • Must detect a 0.2 gallons per hour leak • Three Types of Detectors:

  20. Automatic Tank Gauges REQUIREMENTS FOR THIS METHOD ARE IN CHAPTER 17 SECTION 16 (d) Sensor Detects Torque in Tape to Float Magnetic Float on Rigid Tape Product Level Magnets

  21. Automatic Tank Gauges REQUIREMENTS FOR THIS METHOD ARE IN CHAPTER 17 SECTION 16 (d) Sensor Measures Buoyancy Force Glass Float Shaped to Account for the Round Tank Product Level

  22. Automatic Tank Gauges REQUIREMENTS FOR THIS METHOD ARE IN CHAPTER 17 SECTION 16 (d) Sensor Receives Ultrasonic Wave and Determines Product Level Product Level Ultrasonic Transmitter

  23. Automatic Tank Gauges REQUIREMENTS FOR THIS METHOD ARE IN CHAPTER 17 SECTION 16 (d) • You must have one passing result for each month... • You must keep those records for three years. • The passing result should be the highest passing result for the month. • If you cannot obtain one passing result in a month, you must declare as suspected release. • You must also do Inventory Control or another equivalent method along with an ATG.

  24. Statistical Inventory Reconciliation REQUIREMENTS FOR THIS METHOD ARE IN CHAPTER 17 SECTION 16 (h) This method requires that all of the measurements made for Manual Inventory Control be taken on a daily basis…... And… the results are sent out to a Consulting firm for statistical analysis by a qualified professional who uses a third party verified method.

  25. Statistical Inventory Reconciliation REQUIREMENTS FOR THIS METHOD ARE IN CHAPTER 17 SECTION 16 (h) If the SIR Company cannot produce a conclusive pass or fail, they report an inconclusive result... If you receive an inconclusive result, you must audit your records and resubmit your records to the SIR Company to attempt to achieve a conclusive result. If you receive an inconclusive result, and that cannot be reconciled, you don’t have a valid leak detection method for that month

  26. Interstitial Monitoring REQUIREMENTS FOR THIS METHOD ARE IN CHAPTER 17 SECTION 16 (g) Monitoring of the space between the two shells of a double wall tank for both products and water

  27. Interstitial Monitoring REQUIREMENTS FOR THIS METHOD ARE IN CHAPTER 17 SECTION 16 (g) If your interstitial monitoring device indicates that product has escaped from your tank, you must declare a suspected release. If your interstitial space is disabled because it is full of rainwater or a cable is broken, you do not have a valid leak detection method for that month.

  28. Vapor Monitoring Wells REQUIREMENTS FOR THIS METHOD ARE IN CHAPTER 17 SECTION 16 (e) Wells must be monitored for vapors at least monthly Monitoring Wells Tank Tank Basin Water Table

  29. Vapor Monitoring Wells • Cannot be used on any site which is already contaminated in such a way as to prevent detection of any new release. • Unfortunately, vapor monitoring wells tend to be a one shot deal. Once they detect a leak, it may not be possible to clean them up sufficiently that they can be used to detect a second leak later.

  30. Groundwater Monitoring Wells REQUIREMENTS FOR THIS METHOD ARE IN CHAPTER 17 SECTION 16 (f) Wells must be monitored at least monthly for free product Monitoring Wells Water Table Tank Tank Basin

  31. Leak Detection Methods - Lines REQUIRED BY CHAPTER 17 SECTION 14 (b) • Pressurized Lines • Pressure Check of the Lines - Annually • Automatic Line Leak Detector (ALLD) • Annual Check of the ALLD • Suction Lines • Exposed Lines FOR MORE INFORMATION... The Wyoming Water Quality Division, AUST Program, 122 West 25th Street, Cheyenne, WY 82002 (307) 777-7095 (307) 777-5973 (FAX) and blucht@missc.state.wy.us

  32. PRESSURIZED LINES REQUIRED BY CHAPTER 17 SECTION 14 (b) and SECTION 17 All systems which use pressurized lines must have an automatic line leak detector (ALLD) ALLD SOLENOID VALVE ALLD’s only detect leaks between the solenoid valve in the dispenser and the ALLD itself Tank All ALLD’s must detect any leak of 3 gallons per hour at 10 psi within one hour

  33. SUCTION LINES SEE CHAPTER 17 SECTION 14 (b)(ii) All systems which use suction pumps AND have no pressure on the lines. These systems cannot have to have an (ALLD) CHECK VALVE Systems which have only one check valve are exempt from release detection requirements (Exempt Suction) Tank Systems which have a second check valve are not exempt (US Suction)

  34. Minimum Site Assessment REQUIREMENTS FOR MSA’S ARE IN CHAPTER 17 SECTION 27 • Number of Drill holes or Test Pits depends on size and number of tanks • May be met during removal or replacement of a tank • Tanks installed before Sept 22, 1988 AND in use after September 22, 1988 were required to have an MSA by December 22, 1998 Drill hole or test pit Tank Basin

  35. Financial Assurance REQUIRED BY W.S. 35-11-1428 • $1,000,000 liability per release • (Federal Requirement) • $30,000 deductible • Compliance with the AUST Program makes a site eligible for the: • Wyoming Corrective Action Account • Wyoming Financial Responsibility Account

  36. CORRECTIVE ACTION ACCOUNT SET UP BY W.S. 35-11-1425 • Pays 100% of the cleanup cost of a release from a regulated tank system • The DEQ contracts directly for cleanup • No deductible • Major funding from a set aside equal to 1 cent per gallon of fuel taxes • Wyoming is the only State with this type of coverage.

  37. Financial Responsibility Account SET UP BY W.S. 35-11-1427 • Pays only after a judgement is rendered against the owner or operator of the site • Pays the first $1,000,000 of any judgement • $30,000 deductible • Meets the Federal Financial Assurance Requirement

  38. 1998 UPGRADES REQUIRED BY CHAPTER 17, SECTION 5 AND SECTION 6 • Overfill Protection • Spill Prevention • Corrosion Prevention

  39. Overfill Prevention Equipment Three Types of Overfill Prevention: SEE CHAPTER 17 SECTION 5 (C)(I)(B) Butterfly Valve in Fill Tube Check Valve in Vent Lines Automatic Alarm System

  40. Spill Prevention Equipment SEE CHAPTER 17 SEC 5(C)(I)(A) SPILL BUCKET FILL TUBE A spill bucket is designed to catch spills during the filling of the tank Tank

  41. Corrosion Prevention SEE CHAPTER 17 SEC 5(A) • Non Corrodable Tanks and Lines • Steel Tanks and Lines • Sacrificial anode cathodic protection • Impressed Current cathodic protection • Fiberglass Clading • Lining

  42. Corrosion PreventionNon Corrodable Tanks SEE CHAPTER 17 SEC 5 (A)(I) NON-CORRODABLE TANKS ARE MADE ENTIRELY OF FIBERGLASS REINFORCED PLASTIC OR... THEY ARE MADE OF STEEL WHICH HAS BEEN COMPLETELY CLAD WITH A SECOND TANK MADE OF FIBERGLASS REINFORCED PLASTIC (COMPOSIT STEEL/FIBERGLASS TANK)

  43. Corrosion PreventionComposite Steel/Fiberglass Tanks STEEL TANK SHELL FIBERGLASS SHELL The fiberglass shell is more than a coating, it is a complete tank in and of itself. Composite Tanks may or may not have an interstitial space between the steel and the fiberglass shells

  44. Corrosion PreventionCathodic Protection of Steel Tanks SACRIFICIAL ANODE OR IMPRESSED CURRENT SYSTEMS SACRIFICIAL ANODES MUST BE CHECKED BY A CATHODIC PROTECTION TESTER ONCE WITHIN SIX MONTHS OF INSTALLATION AND AGAIN ONCE EVERY THREE YEARS THEREAFTER CATHODIC PROTECTION EXPERTS AND TESTERS MUST MEET THE QUALIFICATIONS FOUND IN CHAPTER 17, WATER QUALITY RULES AND REGULATIONS CATHODIC PROTECTION SYSTEMS MUST BE DESIGNED BY A CATHODIC PROTECTION EXPERT

  45. Corrosion PreventionCathodic Protection of Steel Tanks SACRIFICIAL ANODE SYSTEM SEE CHAPTER 17 SECTION 9 POTENTENTIAL DIFFERENCES MUST BE: STI-P3 TANKS HAVE DIELECTRIC FITTING LINES -.85 VOLTS -.85 VOLTS TANK OR 200 MILLIVOLTS ABOVE BACKGROUND SACRIFICIAL ANODES

  46. Corrosion PreventionCathodic Protection of Steel Tanks IMPRESSED CURRENT SYSTEM SEE CHAPTER 17 SECTION 9 POTENTIAL BETWEEN THE TANK, LINES AND ANODES MUST BE: RECTIFIER LINES TANK -.85 VOLTS OR 200 MILLIVOLTS ABOVE BACKGROUND POTENTIAL NON-SACRIFICIAL ANODES

  47. CRITERIA REQUIRED FOR CP CHECKS SEE CHAPTER 17, SECTION 9(b), Wyoming Water Quality Rules and Regulations • Must be in accordance with the National Association of Corrosion Engineers Standard RP-02-85, “Control of External Corrosion on Metallic Buried, Partially Buried or Submerged Liquid Storage Systems”.

  48. CORROSION EXPERT Certified by the National Association of Corrosion Engineers or A Registered Professional Engineer with education and experience in corrosion control CATHODIC PROTECTION TESTER a person who can demonstrate understanding of the principles and measurements education and experience in soil resistivity, stray current, structure to soil potential, and isolation measurements CP EXPERT vs. CP TESTER SEE CHAPTER 17, SECTION 4(K) AND 4(O) Wyoming Water Quality Rules

  49. IDEAL REPORT OF A CP CHECK rectifier TANK 1: 6000 GALLON SUPER TANK 2: 10000 GALLON UNLEADED TANK 3: 6000 GALLON PLUS 1 TANK 4: 6000 GALLON UNLEADED 4 5 6 7 2 8 9 10 Island 12 11 13 5 14 15 16 Island 3 Facility ID 0-002357

  50. IDEAL REPORT OF CP CHECK Facility ID 0-002357