Energy Efficient Fluid Flow

Energy Efficient Fluid Flow. Pumping System Fundamentals. V = volume flow rate D P total = pressure gain to overcome inlet/outlet affects and friction D P static (pressure difference between inlet and outlet) D P velocity (velocity difference between inlet and outlet)

haru
Download Presentation

Energy Efficient Fluid Flow

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Energy Efficient Fluid Flow

  2. Pumping System Fundamentals • V = volume flow rate • DPtotal= pressure gain to overcome inlet/outlet affects and friction DPstatic (pressure difference between inlet and outlet) DPvelocity(velocitydifference betweeninlet and outlet) DPelevation(elevation difference between inlet and outlet) DPfriction • Eff = efficiencies of pump, drive, motor Welec= V DPtotal / [EffpumpxEffdrivexEffmotor]

  3. Pumping System Savings Opportunities • Reduce volume flow rate • Reduce required pump head DPstatic DPvelocity DPelevation DPfriction • Increase pump, drive, motor efficiency Welec = V DPtotal / [Effpumpx Effdrivex Effmotor ]

  4. Fluid Flow System Saving Opportunities • Reduce Required Pump/Fan DP • Employ Energy Efficient Flow Control • Improve Efficiency of Pumps/Fans

  5. Reduce Pump/Fan DP

  6. Minimize Elevation GainIncrease Initial Reservoir Level • Welev = V DPelevation difference between inlet and outlet • Reducing elevation difference reduces work to overcome elevation by 20%

  7. Minimize FrictionUse Large Diameter Pipes/Ducts • Wfriction = V DPfriction • DPfriction=k / D5 • Wfriction= V k / D5 • Work to overcome friction varies inversely with 5th power of pipe diameter • Doubling pipe diameter reduces work to overcome friction by 97%

  8. Minimize FrictionUse Smooth Pipes/Ducts • Wfriction= V DPfriction • DPfriction~ friction factor f • fsteel = 0.021 fplastic = 0.018 • Smoother pipes reduce work to overcome friction by: (0.021 – 0.018) / 0.018 = 17%

  9. Minimize FrictionUse Gradual Elbows Long radius elbows reduce work to overcome friction by 90%

  10. Employ Energy Efficient Flow Control

  11. Flow Control • Systems designed for peak flow • Systems operate at less than peak flow • Use energy efficient method to control (reduce) flow

  12. Inefficient Flow Control • By-pass loop • (No savings) • By-pass damper • (No savings) • Outlet valve/damper • (Small savings) • Inlet vanes • (Moderate savings)

  13. Efficient Flow Control • Trim impellor for constant-volume pumps • Slow fan for constant-volume fans • VFD for • variable-volume pumps or fans

  14. Energy Efficiency of Flow Control

  15. Pump/Fan and System Curves W = V DP = area of rectangle Pump/Fan Curve DP System Curve V

  16. Bypass Flow: Zero Energy Savings • When bypassing, V through pump is constant • Thus, pump work is constant and no savings Pump/Fan Curve DP System Curve V V2 = V1

  17. Throttle Flow: Small Energy Savings Throttled System Curve • With throttling and inlet vanes, V decreases but P increases • Thus, net decrease in W (area under curves) is small DP Design System Curve V2 = V1 / 2 V1 V

  18. Reduce Pump/Fan Flow: Big Energy Savings • W = V DP = V (k V2) = k V3 • When flow reduced by pump/fan rather than system, W varies with cube of flow • Reducing flow by 50% reduces work to overcome friction by 88% Pump/Fan Curve DP System Curve V1 V2 = V1 / 2 V

  19. Three Ways to Reduce Pump/Fan Flow • Trim impellor for constant-flow pumping applications • Slow fan for constant-flow fan applications • Install VFD for • variable-flow pumps or fans

  20. Constant Flow Pumping:Cooling Towers With Throttling Valves

  21. Constant Flow Pumping:Process Pumps with Throttling Valves

  22. Constant Flow Pumping: Open Throttling Valve and Trim Pump Impellor A: Flow throttled by partially closed valve B: Max flow with valve open C: Valve open and impellor trimmed

  23. Constant Flow Fans:Slow Fan by Changing Pulley Diameter

  24. Constant Flow Fans:Slow Fan by Changing Pulley Diameter A: Flow throttled by partially closed damper B: Max flow with damper open C: Damper open and fan speed (RPM) reduced

  25. Variable Flow Pumping:Process Cooling Loop • W2 = W1 (V2/V1)3 • Reducing flow by 50% reduces pumping costs by 87%

  26. Variable Flow Pumping: HVAC Chilled Water Loops

  27. Variable Flow Pumping:Open Throttling Valve and Install VFD

  28. Full-Open Pumping:Install 2-Way Valves and VFDs

  29. Big Cooling Towers

  30. Big Cooling Loop Pumps

  31. Worlds Largest Bypass Pipe

  32. Savings From Installing VFDs A B C A: Flow throttled by partially closed valve B: Max flow with valve open C: Valve open and pump slowed by VFD Wsav for throttle to VFD = A – C Wsav for bypass to VFD = B – C Wsav for bypass to VFD W2 = W1(V2/V1)2.5 Wsav = W1 – W2

  33. Pump Long, Pump Slow • Identify intermittent pumping applications • More energy to pump at high flow rate for short period than low flow rate longer • Example: • Current: Two pumps in parallel for four hours • Recommended: One pump for six hours • Estimated Savings: $500 /yr Reason: Wfluid = V DP = k V3

  34. Optimize Efficiency of Pumps/Fans

  35. Correct Fan Inlet/Exit Conditions No Yes

  36. Resize Over-sized Pumps • Pump operating at off-design point M • Eff = 47% • Replace with properly sized pump • Eff = 80% • Savings: $14,000 /yr

  37. Fluid Flow Summary • Reduce Required Pump/Fan Head • Reduce excess elevation head • Use larger diameter pipes • Use smoother pipes/ducts • Use long-radius elbows and low-friction fittings • Employ Energy Efficient Flow Control • Constant flow pumping: trim impellor blade • Constant flow fans: Slow fan • Variable flow pumps and fans: Install VFDs • Pump slow, pump long • Improve Efficiency Pumps/Fans • Correct fan inlet/exit conditions • Resize miss-sized pumps/fans