440 likes | 587 Views
2. Overview. ERCOT Settlement highlights Residential Annual Validation Heating Fuel Type Residential SurveyImpact of Miss-Assignment of Residential Load Profile ID AssignmentNew Residential Algorithm Q
E N D
1. 1 AEIC Annual Load Research Conference September 12, 2006 - Reno, NV
2. 2
3. 3 ERCOT requires a fifteen (15) minute settlement interval
Vast majority of Customers do not have this level of granularity.
Profiles are created using adjusted static models
Models are dependent on season, day of week, time of day and weather
Backcasted Profiles are generated the day following a trade day and used for all settlements (initial, final and true-up)
Load Profiling:
Converts monthly NIDR reads to fifteen (15) minute intervals
Enables the accounting of energy usage in settlements
Allows the participation of these Customers in the retail market (reduces barrier to entry)
4. 4
5. 5 Minimum of two weather stations per weather zoneMinimum of two weather stations per weather zone
6. 6 ERCOT in conjunction with Profiling Working Group establishes the rules for Profile ID assignment and publishes in the form of a Decision Tree on the ERCOT website
Annual Validation is a process established by the Market to annually review and update Profile ID assignments based on the rules defined in the Decision Tree
Historically, May 1 thru April 31 meter reads were used to determine the Annual Validation assignment. The process normally began in June and completed in January.
7. 7 Oct. 2001 Initial Validation
Profile IDs were assigned by TDSPs prior to Market Open
Validation started in 2001 and was not completed until Sept. 2002
2002 Annual Validation
Not performed due to 2001 Initial Validation still in progress
PWG sub team changed methodology from using billing month to usage month
2003 Annual Validation
Large volume of migrations (1.5 million out of 4.9 million ESIIDs)
2004 Annual Validation
Large volumes of changes were identified (1.0 million out of 5.4 million ESIIDs)
Annual Validation suspended to allow time to improve assignment process
2005 Annual Validation
Some methodology changes were identified which still resulted in large volumes of migrations (0.5 million out of 5.1 million ESIIDs)
Market delayed sending in transactions and ultimately decided to only send in a subset of changes identified
8. 8 Residential Assignment Rules2001 - 2004 Winter Ratio >=1.5 RESHIWR
Winter Ratio < 1.5 RESLOWR
9. 9 Preliminary Residential Assignment Rules for Annual Validation 2005 Do not replace a non-default assignment with a default assignment
Apply Dead-Bands
RESHIWR goes to RESLOWR if WR = 1.0
RESLOWR goes to RESHIWR if WR > 1.8
Dead-Bands do not apply if currently a default assignment
kWh Minimums
WR numerator = 20 then assign RESLOWR
10. 10 Additional Profile Assignment Improvement Ideas
Use a statistical approach to correlate premise usage to profile usage.
Use a residential survey to obtain the necessary data to relate usage patterns to heating system type.
More accurately account for weather variations
Account for periods of low/no occupancy
Move calculation responsibility to ERCOT from TDSPs
Change time period for submission of assignment change transactions
During the original October/November timeframe for submitting changes, the RESHIWR and RESLOWR profiles are significantly different
RESHIWR and RESLOWR profiles are quite similar during the summer months
11. 11
Design:
41,000 bilingual survey forms mailed
Stratified by Weather Zone and Profile Type
2,563 RESHIWR per Weather Zone
2,562 RESLOWR per Weather Zone
Response
Survey responses were identified to allow connecting the response to usage history
4,669 responses as of 09/30/2005
11.4% response rate
12. 12 Questions from Residential Survey pertinent to Electric Heat Analysis
13. 13 8.5% 12.6% 10.5% 9.9% 13.6% 11.3% 10.6% 14.1%
14. 14
15. 15
16. 16
17. 17
18. 18 Performed visual inspection of usage patterns for each survey response
4,630 responses indicated either a “Single-Family Dwelling” or “Multi-Family Dwelling” and a primary home heating type of either “Electricity” or “Natural gas or bottled gas (propane/butane)
673 (14.5%) responses to the home heating type were deemed invalid by examination of their seasonal usage pattern
3,957 (85%) responses were used to develop an improved Profile Type classification algorithm
19. 19 Survey Response Validation - Electric Heat Example
20. 20 What we found out from the Survey Saturation of Electric Heat varied considerably across weather zones
Saturation of Electric Heat was inconsistent with breakdown between RESHIWR and RESLOWR
30% of Survey responders reporting Electric Heat were assigned to RESLOWR
14% of Survey responders reporting No Electric Heat were assigned to RESHIWR
There is very little year-to-year change in heating system fuel actually occurring
The percent of newer homes using electric heat varies considerably across weather zones
(37% Coast – 84 South %)
21. 21 Why Does Assignment Accuracy Matter? Profile assignment errors create two types of load profile estimation errors
Assignment of billing kWh to the days within the billing period
(RESHIWR assigns more kWh than RESLOWR to cold days)
Assignment of daily kWh to the intervals within the day
(RESHIWR assigns more kWh to morning intervals)
22. 22
23. 23 Residential Profile Comparison - FWEST Reshiwr vs. Reslowr
24. 24 Findings and Next Steps ERCOT’s Profile ID Assignment process has resulted in unacceptably high migration rates
Dead - bands would reduce migration but could do more harm than good in terms of assignment accuracy
The impact of Profile ID miss-assignment is significant at the ESIID level
Undertake an effort to develop a new and improved assignment process with a goal of reducing migration and improving accuracy
More improvements are needed
25. 25 Classification Algorithm Overview Use Residential Survey response data in conjunction with responder usage data to build an algorithm to predict heating fuel
Use regression between actual meter readings for a premise and the RESHIWR and RESLOWR profile kWh for the same time periods
Use reads during shoulder and winter months for several (4.5) years
Omit reads during periods of very low use (no/low occupancy)
Omit outlier reads and require some reads to exceed a minimum kWh/day threshold in order to assign RESHIWR
Assign the better fitting profile to the ESIID
26. 26 For each ESI ID with a survey response usage values were selected from Lodestar for the January 2002 – September 2005 time period
Each usage value was converted into units of kWh/day and any read covering a period longer than 44 days was dropped
Each usage value was classified as a winter or shoulder reading
Only shoulder and winter readings were used in the analysis
Winter/Shoulder: start > September 20 and stop < May 11
Winter: start > November 15 and stop < March 15
Shoulder: all others
Usage values were screened for high and low outlier usage values
27. 27
For each ESI ID compute a mean and standard deviation of the kWh/day values for the winter and shoulder readings and use these to “normalize” each usage value
Usage value dropped if:
Z > 3 and kWh/day > 100
Z > 3.5
Z < -2
kWh/day < 5 Low Occupancy
28. 28
29. 29
30. 30 1,006 ESI IDs (21.7%) with one or more usage values screened
2,414 usage values were screened out
1,825 usage values screened out because < 5 kWh/day
If an ESI ID had fewer than 3 winter readings or fewer than 3 shoulder readings it was classified as “RESLOWD” (Residential Low Winter Ratio Default) and was not used for fine tuning the algorithm
31. 31 If an ESI ID has (and uses) electric heating, then the winter and shoulder usage values for that premise should be more similar to the RESHIWR profile kWh than to the RESLOWR profile kWh
The profile kWh for a day reflects the weather conditions associated with that day in the specific weather zone as well as the day type (day-of-week/holiday) and season of the year
To perform the comparison for an ESI ID, the profile kWh is summed across the intervals for the days in each of its meter reading periods (shoulder and winter months only)
32. 32
For each fall-winter-spring time period e.g., fall 2004 – spring 2005 the profile kWh is scaled to equal the sum of the ESI ID’s meter kWh for that time period
The correlation between the actual metered kWh and the scaled profile kWh for those readings is computed for each ESI ID
The R2 correlation is determined with a weighted linear regression analysis with no intercept term
Each reading is weighted as follows:
Shoulder reading weight = 1
Winter reading weight =
Winter reading weight = 1 if RESHIWR kWh < RESLOWR kWh
The weighting process associates more importance with winter readings for which the RESHIWR kWh is greater than the RESLOWR kWh
33. 33 New Algorithm Improvement Example
34. 34
35. 35
If the highest winter reading kWh/day is less than 15 kWh/day
then assign “RESLOWR”
If R2RESHIWR > 0.60 and R2RESHIWR > R2RESLOWR
then assign “RESHIWR”
If the number of readings available > 9
and R2RESHIWR > 0.90
and (R2RESHIWR + 0.010) > R2RESLOWR
and Winter Max kWh/day > 50
then assign “RESHIWR”
If the number of readings available > 9
and R2RESHIWR > 0.95
and (R2RESHIWR + 0.015) > R2RESLOWR
and Winter Max kWh/day > 60
then assign “RESHIWR”
Otherwise assign “RESLOWR”
36. 36
Algorithm fine tuning was an iterative process to tune each classification criterion on the previous slide individually
Each classification criterion was adjusted to minimize misclassification error based on validated survey responses
For each iteration, misclassified ESI IDs were examined graphically to assess the accuracy of the Profile Type assignment and to establish new criteria
When the fine tuning was complete 184 (4.6%) validated survey responses regarding heating system type were different than the algorithm classification … most had usage patterns which were ambiguous
37. 37
38. 38
39. 39
For the final version of the algorithm 3,773 (95.4%) validated survey responses regarding heating system type agreed with the algorithm classification
40. 40 62% of the 578,572 AV 2005 Profile Type changes agreed with the algorithm classification
Changes to RESHIWR were significantly more accurate (78.4%) than changes to RESLOWR (43.5%)
Accuracy of the changes by weather zone ranged from a low of 59.8% in the SOUTH zone to a high of 68.8% in the EAST zone
The Residential population would have had somewhat more accurate Profile Type assignments as a result of conducting AV 2005 (81.4% vs. 78.7%)
The market decided to allow only changes which were in agreement with the algorithm (358,000 changes were submitted)
41. 41
42. 42
43. 43 Conclusions The survey successfully provided data necessary to build a classification algorithm for electric heating and establish its accuracy.
The classification algorithm at 96% accuracy was a significant improvement over the winter ratio method
The improved accuracy will lead to assignment stability
Profile assignments and shapes are in a feedback loop and improve each other
The new algorithm uses load profile shapes to make profile assignments
With updated load research analysis based on the new assignments, more accurate load profile shapes will be developed as a result of a more homogeneous population
The more accurate load profile shapes should lead to better assignments
ERCOT has completed load research analysis using the new profile assignments and is developing new profile models based on those latest estimates
44. 44