520 likes | 1.36k Views
電路學 ( 二 ). Chapter 12 Three-Phase Circuits. 12.1 Introduction (1). Three-Phase Four Wire Systems. Single-Phase Systems. two-wire type. three-wire type. 12.1 Introduction (2). Nearly all electric power is generated and distributed in 3-phase.
E N D
電路學(二) Chapter 12 Three-Phase Circuits
12.1 Introduction (1) Three-Phase Four Wire Systems Single-Phase Systems two-wire type three-wire type
12.1 Introduction (2) • Nearly all electric power is generated and distributed in 3-phase. • Instantaneous power in a 3- system can be constant. • The 3- system is more economical than single-phase system.
12.2 Balanced Three-Phase Voltages (1) Van Vbn Vcn A three-phase generate
12.2 Balanced Three-Phase Voltages (2) Y-connected source -connected source
12.2 Balanced Three-Phase Voltages (2) negative sequence負向序 positive sequence正相序 Balanced phase voltages are equal in magnitude and are out of phase with each other by 120
12.2 Balanced Three-Phase Voltages (3) a Y-connected load. a -connected load. A Balanced Load is one in which the phase impedance are equal in magnitude and in phase. For a balanced Y-connected load Z1 = Z2 = Z3 = ZY For a balanced -connected load Za= Zb = Zc= Z
12.2 Balanced Three-Phase Voltages (4) Y- transformation • There are four possible connections in three-phase systems: • Y-Y connection • Y- connection • - connection • -Y connection
12.2 Balanced Three-Phase Voltages (5) Example 1 Determine the phase sequence of the set of voltages
12.3 Balanced Y-Y Connection (1) ZY = Zs + Zl+ ZL
12.3 Balanced Y-Y Connection (2) Assuming the positive sequence, The line-to-line voltages (line voltage) Similarly,
12.3 Balanced Y-Y Connection (4) Example 2 Calculate the line currents in the three-wire Y-Y system.
12.4 Balanced Y- Connection (1) Assuming the positive sequence,
12.4 Balanced Y- Connection (2) Example 3 A balanced abc-sequence Y-connected source with Van = 10010 V is connected to a -connected balanced load (8 + j4) per phase. Calculate the phase and line currents.
12.5 Balanced - Connection (1) Assuming the positive sequence,
12.5 Balanced - Connection (2) Example 4 A balanced -connected load having an impedance 20 – j15 is connected to a -connected, positive-sequence generator having Vab = 3300 V. Calculate the phase currents of the load and the line currents.
12.6 Balanced -Y Connection (1) • Using KVL. • Replacing the -connected source with its equivalent Y-connected source. • Transforming the Y-connected load to an equivalent Y-connected load.
12.6 Balanced -Y Connection (3) Example 5 A balanced Y-connected load with a phase impedance 40 + j25 is supplied by a balanced, positive-sequence -connected source with a line voltage of 210 V. Calculate the phase currents. Use Vab as reference.
12.7 Power in a Balanced System (1) • The advantage of 3-phase systems for power distribution • The total instantaneous power in a balanced 3-phas system is constant. • The 3-phase system uses a lesser amount of wire than the single-phase system for the same line voltage VL and the same absorbed power PL. For a Y-connected load, the phase voltages are
12.7 Power in a Balanced System (2) If ZY = Z, the phase currents Appling
12.7 Power in a Balanced System (3) The complex per phase The total complex power where Vp, Ip, VL, and IL are all in rms values and is the angle of the load impedance. for Y-connected loads, for -connected loads,
12.7 Power in a Balanced System (5) Example 6 Determine the total average power, reactive power, and complex power at the source and at the load.
12.7 Power in a Balanced System (6) Example 7 A three-phase motor can be regarded as a balanced Y-load. A three-phase motor draws 5.6 kW when the line voltage is 220 V and the line current is 18.2 A. Determine the power factor of the motor.
12.7 Power in a Balanced System (7) Example 8 Two balanced loads are connected to a 240-kV rms 60-Hz line, as shown in the figure (a). Load 1 draws 30 kW at a power factor of 0.6 lagging, while load 2 draws 45 kVAR at a power factor 0.8 lagging. Assuming the abc sequence, determine: (a) the complex, real and reactive powers absorbed by the combined load, (b) the line currents, and(c) the kVAR rating of the three capacitors -connected in parallel with the load that will raise the power factor to 0.9 lagging and the capacitance of each capacitor.
12.10 Applications (1) • Three-Phase Power Measurement.
12.10 Applications (2) Consider the balanced Y-connected load
12.10 Applications (3) • If P2 = P1, the load is resistive. • If P2 > P1, the load is inductive. • If P2 < P1, the load is capacitive.
12.10 Applications (4) Example 9 The two-wattmeter method produces wattmeter readings P1 = 1560 W and P2 = 2100 W when connected to a -connected load. If the line voltage is 220 V, calculate: (a) the per-phase average power, (b) the per-phase reactive power, (c) the power factor, and (d) the phase impedance.
12.10 Applications (5) Example 10 The three-phase balanced load in the figure has impedance per phase of ZY = 8 + j6 . If the load is connected to 208-V lines, predict the readings of W1 and W2. Find PT and QT.