1 / 17

Annex for EPBD-related CEN standards for Low Energy Cooling and Thermal Comfort

This project evaluates the applicability of adapted approaches for buildings with limited cooling capacity and formulates recommendations for the revision of EN 15251. It also prepares a guidebook on low energy cooling.

hillmaria
Download Presentation

Annex for EPBD-related CEN standards for Low Energy Cooling and Thermal Comfort

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. http://www.thermco.org/ Establishing an annex for EPBD-related CEN-standards for buildings with high energy efficiency and good indoor environment LOW ENERGY COOLING and THERMAL COMFORT Jarek Kurnitski, D.Sc., Adjunct ProfessorSitra, the Finnish Innovation FundHelsinki University of Technology, HVAC-Technology

  2. Objectives • Low energy cooling can mean limited capacity cooling (groundwater, earth to air, slab cooling, night ventilative cooling, etc passive) which is somewhere in between air conditioning and free running buildings not addressed in the standards (EN 15251, ASHRAE 55) • EN 15251 deals with buildings which either have mechanical cooling (full cooling capacity, PMV index) or buildings without mechanical cooling systems (adaptive approach) • ThermCo project: • evaluated how do people perceive “limited cooling capacity” • assessed the applicability of adapted approach for such buildings • formulated recommendations for revision of EN 15251 regarding thermal comfort criteria for buildings with low energy cooling in summer • prepared REHVA guidebook on low energy cooling

  3. Background of the project Large German study (Pfafferott et al. 2007) with 12 low-energy office buildings with ‘‘mixed-mode systems’’ such as hybrid day ventilation, enhanced night ventilation, earth-to-air heat exchanger and TABS with ground cooling Such buildings can show low energy use, but they don’t keep temperature (especially with earth-to-air) due to limited cooling/ventilation capacity and control Can adaptive thermal comfort model used in such buildings?

  4. PMV modelEN 15251, ISO 7730, CR 1752, ASHRAE 55 a cornerstone of thermal comfort theory leading to target values to be achieved with heating/ cooling season design temperatures depending on indoor climate category (activity & clothing) Includes behavioral adaptation through clothing value (1.0 clo in winter/0.5 clo in summer)

  5. Adaptive modelEN 15251, ASHRAE 55 For free running buildings with openable windows Arguably people have lower expectations in such buildings and adapt to accept higher temperatures (productivity data is not available from the adaption studies)

  6. PMV vs. adaptive PMV Adaptive

  7. Use of the adaptive approach ThermCo project did not established any conclusive evidence on the use of adaptive approach in buildings with limited cooling capacity/control It was concluded that the same expectancy can be expected as in mechanically cooled buildings, i.e. PMV-model shall be used It was also proposed that the PMV model has to be used for sizing of the room conditioning units, but the system capacity may be undersized according to adaptive model, but there was no scientific evidence available supporting this (also no evidence against that exists) It can be expected that some (minor) adaptation to outdoor temperature can be seen in every building with room controllers (non-centrally controlled, non-overcooled buildings), but no evidence exists As no evidence exists one shall use PMV-model.

  8. Energy saving doesn’t always mean energy performance increment Relative performance as a function of temperature REHVA Guidebook 6 (2006)

  9. Recommendations for revision of EN 15251 • The recommendation is to write a guideline in the standard saying that: • some cooling is better than no cooling and if a system with limited cooling capacity is installed the designer must shown how often the room temperatures is expected to exceed the temperature limits specified for mechanical cooled buildings in EN15251and also show this for the adaptive approach. • This will provide the client with data for the expected performance. • It is stressed that the intention of the standard should not be that a building must be in one category the whole year; but rather use the categories to provide a footprint of the performance by showing the % of occupied time in each category. This should also be made clearer in the standard

  10. Limited cooling/ventilation capacity/control Report % of occupied time in each category to the client …

  11. Revision of EN 15251/ the season change The season change from cooling to heating season should be clearly addressed 15C outdoor temperature should be used for season change independently of direction from heating to cooling or cooling to heating In many offices there may be significant long periods with cooling demand in winter, but the clothing level chosen by people may be winter levels as the outside temperature is low. So the criteria is an upper limit for the heating room temperature of 23-25 C depending of the category chosen It is also addressed that the present formulation of adaptive model may result in some climatic zones lower room temperatures required for the buildings without mechanical cooling. (As the criteria for buildings without mechanical cooling vary with outside temperatures in summer, but criteria for mechanical cooled buildings stay the same for the summer.

  12. Lower temperatures required for free-running The problem disappears when the season change limit is corrected to 15C

  13. Low energy cooling REHVA-guidebook • As there are many low energy cooling solutions (including passive and mechanical cooling) not compromising air quality and thermal comfort if properly implemented it was decided to prepare REHVA-guidebook • Guidebook will include • Definitions of seasonal performance • Guidance on thermal comfort criteria • Description and examples of technical solutions

  14. Seasonal performance system boundaries Example of Aachen (Germany) office building: Whereas the heat pump itself has a COP of 4.8 the system efficiency over the whole heating period, expressed here as a "seasonal performance factor (SPF)", varies between 12 and 2.6 depending on the system boundaries (and the corresponding auxiliary energy for pumps) – same applies for the cooling

  15. Energy efficiency of cooling Seasonal COSP (called also SEER, SCOP or SPF) should be estimated by energy simulation calculation. Seasonal COSP is a weighted average COSP for a year. Manufactures give performance data at full load according to EN 14511-2:2007 and at part load according to prEN 14825:2008 (ESEER, the seasonal value SEER for Europe) EER values include the compressor unit (effective power input definition of EN 14511-1:2007). The values do not include the condenser fans (despite of integral condenser in the liquid chilling package) and the distribution system, so the application seasonal ESEER value has to be recalculated for the distribution system used in the real building.

  16. Calculated example • Simulation example for the building with conventional cooling (COP=2.7): • Delivered cooling energy by plant is 42.8 kWh/(m2 a) consisting of: • 29.7 kWh/(m2 a) to chilled beams (with central water distribution system) • and 13.1 kWh/(m2 a) to cooling coils of air handling units. •  Electrical energy use of cooling system is 9.5 kWh/(m2 a), consisting of: • 8.6 kWh/(m2 a) electricity use of compressor unit • 0.6 kWh/(m2 a) electricity use of condenser fans • 0.3 electricity use of circulation pumps. • the application seasonal SEER is 42.8/9.5 = 4.5

  17. Read also ThermCo article on high temperature room conditioning solutions: REHVA Journal, August 2009 2. Ceiling panels 3. Floor cooling and heating (pipes in the slab) Additional features (not included in basic cases): • demand controlled ventilation • night ventilation • shorter chiller operation time / operative temperature control 1. Chilled beams(water radiators for heating)

More Related