Aboveground Storage Tanks (AST) Enhanced Vapor Recovery Regulation September 27, 2006. Topics. Background AST Field Study AST Field Study Results Projected Emission Reductions Statewide AST Population and Emission Inventory AST EVR Regulatory Proposal Costs and Cost Effectiveness
E N D
Aboveground Storage Tanks (AST)Enhanced Vapor Recovery RegulationSeptember 27, 2006
Topics • Background • AST Field Study • AST Field Study Results • Projected Emission Reductions • Statewide AST Population and Emission Inventory • AST EVR Regulatory Proposal • Costs and Cost Effectiveness • Timeline
Background • Considered Going to Board In 2004 • Needed More Public Outreach • Needed to Get a Better Estimate on the Number of ASTs in California • Identified Need to do More Research on Control Techniques • Since Then: • Met with Stakeholders and Facilitated Workshops • Conducted Survey to Estimate the Number of ASTs • Developed and Conducted Field Study
Vent pipe Em Vent Fill port Nozzle Tank gauge AST Emissions Pressure 3” 2” 1” 0”
1000 Gallon 550 Gallon 550 Gallon 350 Gallon
350 Gallon • Control Tank Open To Atmosphere Through Flip Top Cap • Test Tank P/V Valve and Insulation
550 Gallon • Control Tank Open To Atmosphere Through Flip Top Cap • Test Tank # 1 Open To Atmosphere Through Carbon Canister and Flip Top Cap • Test Tank # 2 P/V Valve, White Paint, and Shade structure • Test Tank # 3 P/V Valve and Insulation
1000 Gallon • Control Tank Open To Atmosphere Through Flip Top Cap • Test Tank P/V Valve, White Paint, Shade Structure, and Carbon Canister
Emission Measurements in AST Field Study • Daily fuel surface temperature measurements using thermocouples (AP-42 Methodology) • However, AP-42 underestimates emissions from uncontrolled tanks (open systems). • Does not account for emissions escaping through the vent due to ambient conditions. • Gravimetric Measurements using Load Cells • Test and control tanks were weighed before and after the completion of each respective test. • Difference in the weight of the tanks = Amount of Emissions • More accurate method.
Comparison Between AP-42 and Load Cell Measurements for Uncontrolled ASTs Grams of gasoline/gallon/day
Evaporative Emissions Measured in Summer Months • Using different measurement techniques. Gallons of gasoline Grams of gasoline / gallon / day
Average % Emission Reduction from Uncontrolled ASTs(Calculated Using *Modified AP-42 Methodology) % EmissionReduction Type of Control Technologies *correction factor of 1.6 applied to control tanks (open systems) **3”W.C. PV valve
Statewide AST Population • Based on Survey results • Extrapolated ~ 9600 tanks statewide • 33% (3200) non-agricultural applications • 67% (6400) agricultural applications
Size Distribution 36% # of Tanks 17% 15% 15% 12% 5% Note: Percentages are of total population.
Statewide AST Emission Estimates (2005) (Calculated Using *Modified U.S. EPA AP-42 Methodology) 1540 Gal./day 1020 Gal./day Tons of HC/Day Note: Almost 50% of the emissions are from ASTs<750 Gallon *correction factor of 1.6 applied to open systems
District Permitted AST Emission Estimates (Calculated Using *Modified U.S. EPA AP-42 Methodology) 320 Gal./day 310 Gal./day Tons of HC/Day 10 Gal./day ~3000 ~2200 ~800 *correction factor of 1.6 applied to open systems
Statewide Survey Results Summary SOURCEPROTECTEDSINGLE WALLTOTAL REPORTED 2006 Districts 2,359 752 3,111 2004 Fuel Carriers 1,962 7,620 9,582 2003 Districts -- -- 1,892 Fuel Carriers 2,873 4,760 7,633
AST Proposal Topics • Vaulted and Non-vaulted Tanks – Definitions • Standing Loss Emission Control • New Installations • Existing Facilities (Retrofits) • Phase I EVR • Phase II EVR
Vaulted Tank • Below grade, top fill, remote dispensing • CP-201 Phase I and Phase II Requirements
Non-Vaulted Tank • Non-Vaulted Tanks • Above grade, top or side fill • CP 206 Phase I and Phase II Requirements
Standing Loss Emission Control • Existing and New Facility Emission Factors • Controls Performance During Periods of No Transfers • Interchangeable with Phase I and Phase II Systems
Standing Loss Emission ControlProposed Emission Factors • New Installations: 0.26 g/gal/day (90%)* • Existing Facilities: 0.61 g/gal/day (76%)* *compared to open system
Standing Loss Emission ControlCertification Testing • Evaluate Systems and Components: • Fuel Surface and Ambient Temperature Ratio (Attenuation) • Hydrocarbon Emissions (Processors) • Emission Factor = Attenuation + Processor Controls Meets • New Installations: 0.26 g/gal/day • Retrofit: 0.61 g/gal/day
Standing Loss Emission ControlTemperature AttenuationSingle Wall Tank
Standing Loss Emission ControlTemperature AttenuationProtected Tank
Standing Loss Emission Control • Performance Based Approach • Components Field Tested as System • System Meets Emission Factor (New or Retrofit) • System Issued Executive Order • System Must Stay Together • Design Based Approach • Technologies/Tanks Field Tested Once • Components Meet Emission Factor (New or Retrofit) • Certified Components Added to Executive Order • Mix and Match Certified Components from Table
Phase INew and Existing Facilities • Cargo Tank to AST • Currently 90% Efficiency • Proposed 98% Efficiency • Minimum 180 Day Test
Phase IINew and Existing Facilities • AST to Motor Vehicle • Currently 90% Re-fueling Efficiency • Proposed efficiency increase to 95% • Does not include: • Fugitives • Pressure Profile • Certified with Phase I System • Minimum 180 Day Test
Phase IIState Requirements • California Health and Safety Code: • Liquid Retention (Dispensing Nozzle or Vapor Return Line) • No Excessive Liquid Spillage • ORVR Compatibility • Operating Hold Open Latch • ARB Required to Test for Certification
AST ProposalSummary • Vaulted (CP-201) • Non-vaulted Tanks (CP-206) • Standing Loss Emission Control • New: 0.26 grams/gallon/day • Retrofit: 0.61 grams/gallon/day • Phase I EVR System • Phase II EVR System
Retrofit Costs, Cost Effectiveness of Different Standing Loss Controls on a 550 Gallon *Permitted AST *Assuming a permitted AST already has a PV Valve which controls ~40% of the emissions from an uncontrolled AST
Retrofit Costs, Cost EffectivenessAssumptions for Standing Loss Controls • Life of an AST is 15 years • Permitted ASTs already have a PV valve • Cost of gasoline is $2.50 per gallon • Net cost = Cost of control – Lifetime cost savings of gasoline • Negative costs indicate the amount of money saved by using the respective controls on ASTs.
Cost Effectiveness for Phase I and Phase II Vapor Recovery Systems • Currently Being Evaluated
December 2006 Workshop for Certification Procedure and Test Methods March 2007 Staff Report and Regulatory Proposal April 2007 Board Meeting Timeline (Tentative)
CONTACTS • Field Study • Jim Watson (916) 327-1282 or jwatson@arb.ca.gov • Pamela Gupta (916) 324-4458 or pgupta@arb.ca.gov • Regulatory • Joe Guerrero (916) 324-9487 or jguerrero@arb.ca.gov • Michael Werst (916) 449-5289 or mwerst@arb.ca.gov