1 / 17

Variable Frequency Drives SED2 Product Overview

Variable Frequency Drives SED2 Product Overview. Introducing SED2 - Siemens Easy Drive. The SED2 family of Variable Speed Drives is designed specifically for the HVAC industry Provides speed control of fan and pump 3 phase motors 230V: ½ - 60HP 480V: 1 – 125HP 575V: 1 – 125HP

ikia
Download Presentation

Variable Frequency Drives SED2 Product Overview

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Variable Frequency Drives SED2 Product Overview

  2. Introducing SED2 - Siemens Easy Drive • The SED2 family of Variable Speed Drives is designed specifically for the HVAC industry • Provides speed control of fan and pump 3 phase motors • 230V: ½ - 60HP • 480V: 1 – 125HP • 575V: 1 – 125HP • 6 frame sizes for every application

  3. SED2 Features • Built-in P1 & N2 Communications • Optional LonWorks or Modbus communication interface • Unique low harmonics design limits emitted noise that may interfere with other devices • Built-in custom PID controls system dynamics, eliminates the need/cost for separate PID controllers • Pump Controller Staging/Cascading eliminates the cost of separate controllers; suited for open loop, constant pressure, constant flow-type systems and applications. • Multi-Level Program Access: Limit, manage, and custom configure the specific parameters unique to the application. • Eliminates the need and cost for separate line reactors and chokes • Allows direct sensor input for room temperature control

  4. SED2 Features • Intuitive, easy-to-use internal programming software leads the operator through quick start-up and commissioning • One Common Interface includes a Basic Operator Panel to operate, set and monitor all drive functions. • Advanced Operator Panel provides inputting of parameters to multiple drives, multi-line/multi-lingual display, scheduling functions, and can control up to 31 drives on the same network • Essential Services Mode/Smoke Purge for critical applications where continuous uninterrupted service is essential. Drive will run regardless of system faults and alarms

  5. Drive and Motor Protection Features • Over-voltage • Motor overload (I2t) • Short circuit • Ground fault • Drive Over-temperature • Motor Over-temperature (Motor PTC required)

  6. SED2 Features • Built-In Hand Auto Selection • Built into Basic/Advanced Operator Keypad in lieu of separate device • Wide Range of I/O • Digital Inputs: 6 • Analog Inputs: 2 • Relay contact Outputs: 2 • Analog Outputs: 2 • Certifications: • UL • cUL • CE

  7. Standard I/O 0-10 V 2-10 V 0-20 mA 4-20 mA Programmablefunctions 0-10 V 2-10 V 0-20 mA 4-20 mA Ni 1000 SED2 2 x analog inputs 2 x analog outputs Insulated Programmablefunctions PNP or NPN (sink/source) Form C contacts Programmablefunctions 30VDC, 5A 240VAC, 2A 6 x digital inputs 2 x digital outputs P1 N2 USS LonWorks (opt.) Modbus (opt.) RS-485 1 x motor PTC

  8. Protective Cover Gland Plate for Conduit NEMA 1 NEMA 12 (IP54) VFD Product Line Configurations • SED2 only • 200-240V: 1/2 – 60HP • 440-500V: 1 – 125HP • 500-600V: 1 – 125HP • For VFD imbedded applications and local bypass (control panel shop) assembly (IP20) Added kit with Protective cover and Gland Plate Meets UL Type 1 (NEMA Type 1) enclosure standards Suitable for direct wall mounting

  9. SED2 Frame Sizes and Power Range IP20 & NEMA Type 1 A-F denotes VFD frame size

  10. BOP - Basic Operating Panel • Commissioning sequence is menu-driven and enables the drive to be set up quickly with only 14 parameters • Filter function arranges parameters to meet user needs • Hand / Auto function for easy commissioning and maintenance • BOP is standard on all drives Start or stop drive Increase or decrease speed Hand over control to your system (I/O terminals or communication)

  11. AOP - Advanced Operating Panel • Provides multilingual clear text information for commissioning and maintenance • 4 x 30 character backlit display • Uploads and downloads parameter settings from one drive to another • Stores 10 parameter sets • 7-day timer function • Broadcast function allows control of up to 31 drives via one AOP 7-Day Timer Function

  12. Ni 1000 PID Controller Feature • Analog or Ni 1000 Sensor Direct Connection • With direct connection of analog or Ni 1000 temperature sensor inputs, implementing low-cost temperature control loops with one cooling or heating sequence is easy. • The built-in PID controller with anti-windup functionality is optimized for HVAC requirements. The PID controller has a hibernation mode which stops the drive if it runs at a user-defined minimum speed for a given time.

  13. Torque Speed V-Belt Monitoring Feature The SED2 ensures reliable V-belt monitoring without the expense of an external sensor. Both speed and torque are compared to a user-defined tolerance band. If the parameters do not match, the drive trips in the event of V-belt failure. Also, the SED2 is also able to monitor a pulse sequence from the sensor detecting rotation on the fan shaft.

  14. Contact out 2 Contact out 1 100% 1 2 3 P Built-in Pump Cascading Feature This function allows for the control of up to two additional, cascaded pumps. With the two relay output contacts, the SED2 performs the cascading logic without additional controllers or I/O cards. Pressure demand Cascade

  15. Menu-driven Quick Commissioning The drive’s initial settings consider the hard wired or direct (P1) connections commonly used with a BAS system. The quick commissioning mode using the standard operating panel, provides for quick and straightforward drive set up. Commissioning Time ~ 10 Minutes BAS 3AC “Hard wiring” • Set point DC 0...10 V- Start / stop- Running / fault- Fault acknowledge • w/ P1: More than 95 parameters or P1

  16. Accessories • Door mounting kitsuitable for BOP and AOP • Modbus interface cable • LonWorks interface module • Harmonics analysis software • Commissioning software • PC interface to SED2 Panel door AOP or BOP Cover (IP56 protection)

  17. Siemens SED2 VFD Advantages • Low harmonics design • Small enclosure size • Many standard features • Reduces operating cost • Low power losses/high efficiency • Minimal effect on customer power • Wide power range – from ½ to 125 HP

More Related